Search NASA⌕ Search

SEARCH · Search NASA

Results for “phasor simulation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 73 records · Page 4

Dynamic Performance Comparison and Prediction based on Distribution-level Phasor Measurement Units

This paper introduces a new distribution level Phasor Measurement Unit (PMU) which adopts advanced hardware components and structure. The hardware parameters from the new PMU and the existing PMU are used to build a simulation model to predict the PMU performance. Therefore, a real-world testbench is built and four distribution level PMUs are tested under the steady-state and dynamic tests. The quantitative experiment result confirms the prediction model which could guide future PMU design, and also verifies the accuracy of the new PMU on the synchrophasor and frequency measurements in multiple scenarios.

Wu, Yuru↗

Dynamic Parameter Estimation with Physics-based Neural Ordinary Differential Equations

Accurate estimation of dynamic parameters of gen-erators is crucial to building a reliable model for dynamical studies and reliable operation of the power system. This paper develops a physics-based neural ordinary differential equations (ODE) approach to learn the parameters of generator dynamic model using phasor measurement units (PMU) data. We design a physics-based neural network to represent the swing equations of the power system dynamics. A loss function is defined as the difference between dynamic simulation results from the physics-based neural networks and pseudo PMU measurements. The parameters of generator dynamic model are iteratively updated using the neural ODEs and the adjoint method. By exploiting the mini-batch scheme in neural ODE training, the parameter estimation performance is significantly improved. Numerical study results on a 3-machine 9-bus system show that the proposed algorithm outperforms state-of-the-art baseline method in both computation time and dynamic parameter estimation accuracy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Local Phasor-Based Control of DER Inverters for Voltage Regulation on Distribution Feeders

We introduce a new control paradigm termed Phasor-Based Control (PBC) to coordinate Distributed Energy Resources (DER) for improved voltage regulation and other objectives. PBC is a multi-layer control framework where the state of the distribution grid is represented by voltage phasors, and Phasor Measurement Units (PMUs) measure the state at critical points in the distribution grid. In the PBC paradigm, a supervisory controller (S-PBC) sets phasor targets which local controllers track. In this paper, we propose a Proportional Integral (PI) implementation for the local control layer (LPBC), to regulate real and reactive power output of distributed inverters to track a voltage phasor target computed by the supervisory layer. We tune the PI controller gains offline with a genetic algorithm that yields better performance than the Ziegler-Nichols method. We benchmark the proposed L-PBC controller against droop volt-var control (DVVC) and observe improved voltage regulation in simulation on the IEEE 13 node unbalanced test feeder (IEEE 13NF). Furthermore, by means of numerical simulation we observe the response of the L-PBC controllers to small and large grid disturbances. Simulations on larger feeders, IEEE 123-node and 647-node, demonstrate challenges with tuning controllers in setups with different amounts of power-voltage coupling.

42 ENGINEERING↗

Sensor enabled data-driven predictive analytics for modeling and control with high penetration of DERs in distribution systems

The electric power grid is undergoing a tremendous transformation due to the increasing penetration of renewable energy resources beginning with wind and more recently with the distributed energy resources (DERs) such as solar and battery storage. DERs have dramatically changed the role of the distribution systems in the overall power grid, and they are expected to contribute a significant portion of power generation in the future. If current trends for DERs continue, system operation and control will need to change dramatically for improved grid reliability and resiliency. As renewable resources increase in penetration, new and challenging operational, planning, and design problems are expected to emerge. Some of the key challenges that arise in the planning and operation of the future grid are: 1) Quantifying the impact of high DER penetration in distribution systems on bulk grid behavior over multiple time scales. 2) Identifying whether a particular DER configuration/settings have a large impact on the overall grid behavior. These challenges can be addressed in an offline manner using detailed T&D grid models and they can also be addressed in an online manner using sensor measurements. In particular, the advancement and planned growth in sensor technology in power grid over various voltage levels provide us with a unique opportunity to tackle these challenges from a data analytic perspective without needing detailed T&D grid models. A few questions that naturally arise when addressing the challenges from DERs using sensor data are: 1) How can we use limited sensor measurements to monitor & control voltage stability and small signal stability of the bulk system? 2) How can we ensure that the developed data analytic methods are robust to data availability and quality issues? 3) How can we compute the developed analytics in a scalable manner using streaming measurements? In this project, we addressed the aforementioned challenges arising from DERs and answered the questions raised above on how to effectively use the sensor measurements to enhance the reliability and performance of the electric grid. Thus, the overarching goal of this project is to develop effective reduced/representative system models from data that make the computational complexity sufficiently manageable so as to be useful to simulate, analyze, and even control complex non-linear power systems dynamics with large penetrations of DERs. In order to achieve the objective, the project team established a four-fold technical approach 1) Formulated a combined transmission-distribution co-simulation framework for data generation and validation, 2) Derived reduced/representative models of power systems based on data-driven methods for efficient computation and appropriate representation of system behavior, 3) Developed data driven characterization of power system behavior based on transfer operator theory, machine learning and optimization for model estimation, 4) Incorporated a scalable data management and processing architecture using distributed Kafka streaming applications that coordinate input data streams to the developed data analytics. The key accomplishments of the project are: 1) Development of a scalable multi-timescale T&D co-simulation framework (both for steady state and for dynamic co-simulation) using commercial solvers (PSSE and GridLAB-D). The steady-state T&D co-simulation interface is shared with our industry partner (PJM). 2) A structured reduced order dynamic model of distribution systems that can represent partial motor stalling along with a systematic procedure to derive the model parameters. 3) A PMU based online method to monitor, localize and mitigate fault-induced delayed voltage recovery using DER reactive support and load control in distribution systems. 4) Development of linear operator based robust methodologies for dynamic state estimation, uncertainty quantification, system identification and trajectory prediction for power system dynamics. 5) An adaptive damping control for utilizing wind energy resources to provide oscillation damping and system stability. 6) Implementation of Kafka-based framework for efficient processing of streaming data using Linux-based local virtual environment.

DER integration↗

Islanding Detection in Rural Distribution Systems

This paper summarizes the literature on detection of islanding resulting from distributed generating capabilities in a power distribution system, with emphasis on the rural distribution systems. It is important to understand the legacy technology and equipment in the rural distribution electrical environment due to the growth of power electronics and the potential for adding the new generations of intelligent sensors. The survey identified four areas needing further research: 1. Robustness in the presence of distribution grid disturbances; 2. the future role of artificial intelligence in the islanding application; 3. more realistic standard tests for the emerging electrical environment; 4. smarter sensors. In addition, this paper presents a synchro-phasor-based islanding detection approach based on a wireless sensor network developed by the University of Texas at Austin. Initial test results in a control hardware-in-the-loop (CHIL) simulation environment suggest the effectiveness of the developed method.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Non-Stationary Power System Forced Oscillation Analysis using Synchrosqueezing Transform

Non-stationary forced oscillations (FOs) have been observed in power system operations. However, most detection methods assume that the frequency of FOs is stationary. In this paper, we present a methodology for the analysis of nonstationary FOs. Firstly, Fourier synchrosqueezing transform (FSST) is used to provide a concentrated time-frequency representation of the signals that allows identification and retrieval of non-stationary signal components. To continue, the Dissipating Energy Flow (DEF) method is applied to the extracted components to locate the source of forced oscillations. The methodology is tested using simulated as well as real PMU data. In conclusion, the results show that the proposed FSST-based signal decomposition provides a systematic framework for the application of DEF Method to non-stationary FOs.

42 ENGINEERING↗

Evaluating Methods for Measuring Grid Frequency in Low-Inertia Power Systems: Preprint

Accurate measurement of grid frequency is a critical component of reliable grid control. Traditionally, methods such as phase locked loops (PLLs) and discrete Fourier transforms (DFTs) have been used in inverters and phasor measurement units (PMUs) to measure frequency. However, as the percentage of inverter-based resources (IBRs) such as solar and wind has increased, these conventional frequency measurement methods are proving unable to guarantee reliable control in some cases. One challenge is measuring frequency during transient events, where there is a disruption in the steady state sinusoidal voltage. During these events, the underlying frequency of the grid may barely change, but measurement methods report a large spike in frequency due to the disrupted waveform. New methods must balance between suppressing spikes in frequency during faults, and providing fast, accurate, measurements in all other grid operation conditions, especially during events with high rate-of-change-of frequency (ROCOF), which are more prevalent in high-IBR power systems. This paper first surveys frequency measurement methods that have been proposed to reduce measurement errors during transient events. Then, both conventional and more novel frequency measurement methods are tested against an IEEE standard and industry recommendations, and their performance is evaluated for events simulated in PSCAD. Results quantify the trade-offs in performance during different grid conditions and lead to suggestions for the most appropriate frequency and ROCOF measurement methods for low inertia grids.

frequency↗

Novel Data Driven Noise Emulation Framework using Deep Neural Network for Generating Synthetic PMU Measurements

Sensors play a critical role in supporting day-to-day grid operations and they are essential to operator’s decision-making process. Furthermore, sensors and sensor behaviors need to be emulated with grid simulations to perform modeling studies and to design cutting edge power systems applications. Ensuring the accurate behavior of these applications requires accurate emulation of sensors and pertinent signals. However, most grid simulators and modeling tools assume either zero error scenarios or simplistic noise models that may not always correlate to real-world sensors. To address the above issue, this work presents an initial study on the noise characteristics of phasor measurement units (PMUs), along with models for recreating their unique noise signatures. The proposed methods (both analytical and machine-learning-based) provide a substantial increase in a sensor’s model fidelity, a feature that can be leveraged by an end-user application to yield more accurate system representations. The proposed methods were then applied to micro PMU data from the EPFL microgrid campus to extract sensor noise profiles. This data was used to train a deep learning model, which was tested to emulate the noise characteristics present in actual signals. Based on the observed results and the employed data-driven methodology, the proposed methods may be adapted to replicate the behavior of other grid sensors and power new applications capable of detecting sensor degradation and eventual device failures in near real-time.

PMU, noise emulation, synthetic measurements, deep↗

Dynamic Equivalence of Large-Scale Power Systems Based on Boundary Measurements

Parallel computing helped speed up many tasks that can be done independently. The advance in gaming industry did not produce a technology that helps the power industry to reduce the computation time for dynamic simulation in individual cases. To perform faster than real-time simulation for the purpose of predicting power system dynamic trajectory, power industry continues to struggle to reduce the system size and simulation time of large-scale power systems while keeping its dynamic behavior under various disturbances. There is also an acute need for real-time dynamic model reduction as more renewables enter the generation mix with dramatic changes in the generation outputs. All existing model reduction solutions are based on having access to a detailed dynamic model of the system. The system changes by the minutes, dynamic models are only updated annually. To solve this problem, wide-area measurements obtained by the phasor measurement unit (PMU) at the boundaries between the reduced system and the study system is used to represent the external area. An artificial neuro-fuzzy inference system (ANFIS) is established to perform the mapping of the measurement to the external equivalent model. Here the external area is regarded as a black-box. Model reduction studies are conducted on the Northeast Power Coordinating Council (NPCC) under various types of contingencies, by using a co-simulation approach between PSS/E and MATLAB. The results look very promising and will be discussed in this paper.

Tong, Ning↗

Simulation and Postmortem Analysis of Angeles Forest Disturbance Event

Multiple unexpected solar photovoltaic (PV) plant responses in the California region following contingencies in recent years warrant postmortem analysis leveraging digital fault recorder (DFR) data for a better understanding of such events and preventing similar events in the future. Most utilities in US, in general, possess transient stability (TS) phasor-domain models of the power grid. Since traditional phasor-based transient stability planning models cannot perform such analysis, this paper presents an approach to extract a region of such models and convert it to Electromagnetic transient (EMT) models. The approach is based on the determination of the minimum impedance-weighted spanning tree between the fault location and affected PV plants in a Western Electricity Coordinating Council (WECC) planning model followed by conversion of this region into an EMT model. The accuracy of the proposed approach is validated against DFR records obtained from the 2018 Angeles Forest disturbance event.

Samanta, Sayan↗

Online Output-Based Inertia Estimation of Modern Power Systems

The overall inertia of modern power systems is drastically impacted by the penetration level of converter-based resources (CBRs). The intermittent output of CBRs and their dependence on the weather conditions affirm the need for a realtime inertia estimation approach. This can help the transmission system operators(TSOs) to be continuously aware of the changes in the system inertia and to take suitable control actions. This paper is a step forward to a totally data-driven framework for power system inertia estimation using the available measurements from the phasor measurement units (PMUs). This inertia estimation is done based on the spectral analysis of the so-called Koopman linear operator. Koopman operator considers the relationship between the system's inertia and its dynamical response to slight disturbances in the load. Simulation results show that Koopman operator can approximate the system behavior in a reconstructed linear space hence inertia constant is estimated accurately.

data-driven↗

A New Impedance-Based Modeling and Stability Analysis Approach for Power Oscillations Between Grid-Forming Inverters

This paper presents a new modeling and analysis approach to address the small-signal stability issues among interconnected grid-forming (GFM) inverters. A novel phasor domain “power impedance” model is developed to capture the terminal characteristics of GFM inverters. Based on the developed models, a sum-type impedance stability criterion is proposed to analyze the power oscillations between GFM Inverters. The developed models are validated with EMT simulations and the stability analysis results using the proposed stability criterion can match both EMT simulations and eigenvalue analysis. In addition, the application of the developed model can be extended to the stability analysis of large-scale power system with high penetration of GFM inverters.

Liu, Hanchao↗

A Scalable PDC Placement Technique for Fast and Resilient Monitoring of Large Power Grids

The wide-area measurement system (WAMS) is a key enabler of real-time monitoring of power grids. The essential goals of WAMS design are fast and resilient data transfer from phasor measurement units (PMU) to phasor data concentrators (PDC). We propose a scalable two-stage PDC placement technique for minimizing the end-to-end delay while maintaining resiliency. In the prescreening stage, the plausible candidates of PDC configurations are identified based on a graph theory-based multi-median function (MMF). Here, in this article, a computationally efficient meta-heuristic algorithm is used to address scalability. In the candidate selection stage, two different algorithms, namely, Suurballe's and Dijkstra's, are employed to identify the best of those plausible PDC configurations as the final design. This technique not only minimizes the hop paths between PMUs and PDCs, but also ensures network resiliency against single PMU, PDC, or communication link failure by incorporating the roles of PMUs in power grid observability into routing policy. Simulation results on the IEEE 57-bus test power system and the 2000-bus test power system demonstrate the effectiveness and scalability of the proposed technique.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Control Oriented Models for Co-Design: Technical Overview of MT HVDC, MVDC, and Solid State Transformer Building Blocks

The electric power system is shifting toward a power electronics–enabled grid, where converter based “building blocks” (e.g., high voltage direct current (HVDC) links, multi terminal HVDC (MT HVDC) networks, medium voltage DC (MVDC) links, and solid state transformers (SSTs)) provide fast, precise control of power flows, voltage, and frequency. This report develops and applies publicly shareable electromagnetic transient (EMT) and phasor models to examine how such building blocks can be composed and coordinated to support offshore wind integration, inter area transfers, feeder support, and resilience. Section 2 documents a modular multilevel converter (MMC)–based MT HVDC modeling framework and two use cases: a compact WSCC/IEEE 9 bus test system and a 240 bus “mini WECC” case with five offshore wind plants (OWFs). Phasor to EMT transfer, initialization, and sanity checks are summarized, and neutral demonstrations of normal and contingency operation are reported. Section 3 frames the problem of wind plant inertial frequency response (IFR): shaping energy release and recovery to improve nadir while avoiding aerodynamic stall; representative simulations illustrate the issues without disclosing proprietary control. Section 4 develops MVDC concepts through an IEEE 16 bus loop and an Olympic Peninsula case study that compares AC vs. MVDC corridors and shows how feeder headroom can be pooled via DC couplers. Section 5 surveys SST architectures and identifies a gap: scalable, communication free coordination of multiple SSTs for islanded feeder networks. Across the report, novel methods and configurations under separate publication and IP review are not disclosed; only topic oriented, replicable setups and non proprietary results are shown. These models and use cases are intended as foundations for future publications and co design studies on architecture, control, and coordination of PE enabled grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Proactive Frequency Stability Scheme via Bayesian Filters and Synchrophasors

Underfrequency (UF) load shedding schemes are traditionally implemented in two ways: One approach is based on manual load shedding, with system operators requesting loads to be shed ahead of anticipated stressful operating conditions. Manual load shedding is usually done through phone calls. The second method is automatic load shedding via underfrequency relays. Using static static settings, these schemes can be designed to operate in stages and drop previously identified loads. The main limitation of traditional load shedding schemes is that they are reactive and leave little room for optimized corrective actions. This work presents a proactive and automatic underfrequency load shedding solution for power systems. Measurements are captured via phasor measurement units (PMUs) at relatively low sampling rates of 30 Hz. These measurements are then processed by particle filters who predict the future state of the system's frequency. Based on these predictions excess load is determined and shed. Comparative case studies are performed in simulated environments. Easy-to-implement models, without hard-to-derive parameters, highlight potential aspects for real-life implementation.

Paramo, Gian↗

Decentralized Data-Driven Estimation of Generator Rotor Speed and Inertia Constant Based on Adaptive Unscented Kalman Filter

This paper proposes an online decentralized and data-driven method for synchronous generator rotor speed and inertia estimation. First, an analytical relationship between the generator terminal voltage/current phasors and its internal rotor speed is derived using the Thevenin equivalent. The parameters of the latter are obtained via a recursive estimator, which allows us to estimate the generator's internal rotor speed from voltage/current phasors without the need for any generator information. Second, we reformulate the equivalent swing equation into the Kalman filter form, which enables us to use a priori-estimated internal rotor speed along with measured real and reactive power injections to obtain an estimate of the inertia for each online synchronous generator. This is achieved through an adaptive unscented Kalman filter. We demonstrate that the use of terminal bus frequency to approximate the rotor speed for inertia estimation by existing methods leads to large estimation biases/errors. Numerical simulations carried out on the IEEE 39-bus and Texas 2000-bus systems reveal that our proposed method is consistently more accurate than existing methods. Moreover, our proposed method is insensitive to both the type and location of system disturbances, and it is robust to different levels of measurement noise.

bus frequency↗

Data-Driven Adaptive Damping Controller for Wind Power Plants with Doubly-Fed Induction Generators

This paper presents an adaptive damping controller for wind power plants in which the turbines are equipped with doubly-fed induction generators. The controller is designed to respond to an input control signal that is triggered according to the system operating conditions. A processing unit continuously estimates the electromechanical modes of oscillation based on real-time streaming data acquired from a phasor measurement unit that is strategically positioned on the grid. The decision to trigger (or not trigger) the control signal is automatic, based on the relative damping of the dominant mode. The modes are estimated using the dynamic mode decomposition algorithm with time-delay embedding. Numerical simulations performed on the two-area system demonstrate that the proposed controller enhances the rotor angle stability for both small-signal and large disturbances, and is adaptive to changing grid conditions.

damping controller↗