Steady-State Comparison of GS-IHP Field Data to Modeled Performance
Field tests were conducted over the winter and summer of 2011 on a prototype (ground-source integrated heat pump (GS-IHP) in Oak Ridge, TN. The extensive field test data was filtered to provide a subset of near-steady-state operation data suitable for comparison to modeled steadystate performance. On-site power use characteristics of the compressor, blower, and pumps and other operational measurements were used to calibrate the system model. Comparisons were made for four modes of operation: space heating, dedicated water heating, space cooling, and combined space cooling and water heating. Analysis results suggest that the field unit was undercharged, especially in the combined space cooling and water heating mode. The fully calibrated model agreed on average to within 2% on capacity, power, and COP/EER for the space heating and cooling modes. Average differences were larger for the water heating modes, ranging from 3 to 11%.