DOE OSTI2026
Thermal energy storage (TES) using phase change materials (PCMs) enables load shifting and reduces mismatches between the building's thermal demand and the heat pump (HP) system's thermal capacity. While most TES studies have focused on single-phase heat transfer fluids, PCM-to-refrigerant heat exchangers (PRHX), in which the refrigerant undergoes liquid-vapor phase change, remain largely underexplored. Here, to address this gap, this study systematically investigates a shell-and-tube PRHX operating as the condenser in an HP through experiments and simulations. A two-dimensional enthalpy-based finite-volume PRHX model was developed and validated against experimental data, including refrigerant and PCM temperature profiles, PRHX capacity, and system-level performance. Results show three characteristic stages: Stage I, the condenser temperature rapidly increases with PCM in the solid state absorbing sensible heat; Stage II, stable operation during PCM phase change; and Stage III, performance decline once part of the PCM becomes fully melted. Heat transfer analysis revealed that uneven PCM melting along the condenser length was driven primarily by variations in the refrigerant-side heat transfer coefficient, rather than local approach temperature differences. Further study demonstrated that minimizing refrigerant outlet subcooling led to more uniform PCM melting and extended Stages I and II by up to 89%. This paper provides a validated PRHX model, clarifies the mechanisms of uneven PCM melting, and highlights subcooling control as an effective strategy to improve TES performance in HP systems without requiring secondary loops.