Search NASA⌕ Search

SEARCH · Search NASA

Results for “Inverter Based Resources”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 91 records · Page 5

Demonstration of Grid Services Using Mixed Grid-Forming and Grid-Following Technologies at the Wheatridge Renewable Energy Facility (Final Technical Report)

This Final Technical Report summarizes the analytical, modeling, and engineering work performed to evaluate grid-forming (GFM) inverter capabilities within a large hybrid renewable energy facility. The project focused on assessing the ability of advanced inverter-based resources to provide essential reliability services through coordinated operation of grid-forming (GFM) and grid-following (GFL) technologies. During Budget Period 1, the project developed a comprehensive framework of GFM performance metrics, including angle support, voltage regulation, frequency response, damping behavior, and current-limiting performance. Extensive electromagnetic transient (EMT) studies and hardware-in-the-loop (HIL) testing were conducted to validate GFM behavior under a range of operating conditions, including weak-grid scenarios, voltage disturbances, and multi-resource interactions. The project also established validated modeling approaches, plant-level control integration strategies, commissioning frameworks, and high-speed measurement infrastructure to support future field demonstration. Although the project concluded prior to field demonstration, the results provide a utility-scale foundation for evaluating, modeling, and deploying grid-forming technologies. The methodologies and tools developed contribute to industry understanding of inverter-based resource behavior and support future power system reliability under increasing renewable penetration.

14 SOLAR ENERGY↗

EMT-TS Hybrid Simulation for Large Power Grids Considering IBR-Driven Dynamics

The escalating integration of inverter-based resources (IBRs) poses new challenges to power systems by introducing fast dynamics with higher frequencies, which may need to be simulated by an electromagnetic transient (EMT) program. As an alternative to conducting EMT simulations for the entire system, which is typically time consuming, hybrid simulation between EMT and phasor-domain transient stability (TS) can greatly reduce the computational burden while preserving the detailed fast dynamics in the EMT zone. This paper establishes an EMT-TS hybrid simulation platform using open-source tools, specifically ParaEMT, GridPACK, and HELICS, which are the EMT simulator, TS simulator, and interface framework, respectively. Case studies on the 240-bus Western Electricity Coordinating Council (WECC) system demonstrate that the developed ParaEMT-HELICS-GridPACK hybrid simulator can accurately capture both slow electromechanical and fast IBR-driven dynamics with a 2.4x speedup.

electromagnetic transient↗

Large Scale Field Demonstration Evaluation Plan

This Evaluation Plan defines practical, commissioning-oriented test protocols for in-field assessment of grid-forming (GFM) inverter-based resources (IBRs) deployed under the UNIFI Consortium Field Demonstration. The demonstration’s overarching objective is to validate multi vendor GFM technologies at impactful unit/plant scale, assess interoperability and grid-service performance, and evaluate the applicability of the UNIFI Specifications for Grid-forming Inverter-based Resources in real utility environments, including integration with operational systems and protection schemes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Summary of GFL Inverter Capability and Performance: Malawi [Slides]

This presentation provides a comprehensive comparison of inverter-based resource (IBR) technical requirements across multiple international grid codes - including IEEE 2800, ESO, EirGrid, and Malawi's evolving regulatory framework - to support capacity building for electricity-sector institutions in Malawi. It highlights key performance expectations for grid-following (GFL) inverters across critical domains such as primary and fast frequency response, ramping behavior, frequency and voltage ride-through capabilities, reactive power and voltage control, ROCOF withstand, phase jump tolerance, system strength considerations, protection schemes, and dynamic modeling requirements. Emphasizing a "Do no harm, do something, do more" philosophy, the document synthesizes best practices and operational benchmarks to guide the integration and stability of inverter-based resources within Malawi's power system. The presentation forms part of the SABESS Center of Excellence initiative supported by the Global Energy Alliance for People and the Planet.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Feedback and Oscillations: Constructing Feedback Systems for Root Cause Analysis of Oscillations in Power Grids

Dynamic phenomena linked to inverter-based resources (IBRs) have gained global attention. Several IBR-induced dynamics have caused bulk power system-connected wind or solar power plants to trip, and some have even led to widespread outages. In addition, many oscillations have been observed involving IBR power plants. In 2023, the IEEE Power & Energy Society (PES) IBR Subsynchronous Oscillations (SSO) task force published a journal article, “Real-World Subsynchronous Oscillation Events in Power Grids With High Penetrations of Inverter-Based Resources,” in which 19 IBR oscillation events were examined for their causation. Earlier in 2020, another PES task force article, “Definition and Classification of Power System Stability-Revisited & Extended,” authored by prominent academics, introduced converter-driven stability as a new category of stability. The international power grid industry community also took action by publishing the CIGRE Green Book, Power System Dynamic Modelling and Analysis in Evolving Networks (led by Babak Badrzadeh and Zia Emin) in 2024. In August 2024, the Energy Systems Integration Group (ESIG) released a practical guide led by Nick Miller, “Diagnosis and Mitigation of Observed Oscillations in IBR-Dominant Power System: A Practical Guide.” The goal of the guide is to assist practicing engineers in making initial judgments and conducting detailed analyses about oscillations. Finally, when addressing the classification of stability and oscillations, the guide emphasizes a causality-based taxonomy for grouping, such as voltage control-induced oscillations, synchronization-induced oscillations, and frequency or active power control-induced oscillations.

Fan, Lingling [Univ. of South Florida, Tampa, FL (↗

Verification of Adaptive Protection in Hardware in the Loop for Coordination with Solar Variability

As inverter-based resources continue to be installed at all levels of the electric grid, the fixed protection schemes used at the distribution level will continue to be stressed until they no longer ensure the protection of the grid. Adaptive protection has been proposed as a solution with the ability to update the protection schemes in near real-time to ensure reliability and increase the resilience of the grid. However, weather variability poses a significant challenge to the ability of these methods to keep the selectivity and reliability of these schemes coordinated. If the ramp rates, due to solar variability, of the inverter-based resources change faster than the adaptive protection can issue new settings, the protection system could be uncoordinated, with the wrong device responding to a system fault. The proposed adaptive protection method ensures that due to solar variability, communication, and protection calculation latency, it can issu e coordinated protection settings promptly, in one minute or less. The hardware-in-the-loop results show the protection settings being issued and maintaining system coordination in under a minute.

Summers, Adam↗

Deep Learning-Based Dynamic Modeling of Three-Phase Voltage Source Inverters

Inverter-based resource (IBR) models are necessary to analyze modern power system stability and create effective control strategies. Modeling IBRs in converter-rich power systems is crucial, yet challenging due to the lack of commercial information on converter topologies and control parameters. This paper proposes novel convolutional neural network (CNN)–based data-driven techniques for modeling IBRs, addressing adaptability and proprietary concerns without requiring internal system physics knowledge. The proposed method is tested using real grid-tied commercial IBR transient data and demonstrates effectiveness and accuracy. Furthermore, the developed modeling approach is integrated and implemented in the open-source power distribution simulation and analysis tool, GridLAB-D, to illustrate the potentiality of dynamic analysis of large-scale power systems with high IBRs.

deep learning, artificial intelligence↗

Anomaly Identification of Synchronized Voltage Waveform for Situational Awareness of Low Inertia Systems

Inverter-based resources (IBRs) such as photovoltaics (PVs), wind turbines, and battery energy storage systems (BESSs) are widely deployed in low-carbon power systems. However, these resources typically do not provide the inertia needed for grid stability, resulting in a low-inertia power system. IBRs and lack of inertia have been known to cause anomalies such as waveform distortions and wideband oscillations in power systems due to the limited inertia level, leading to increased generation trips and load shedding. Here, to achieve effective anomaly identification, this paper proposes a synchro-waveform-based algorithm utilizing real-time synchronized voltage waveform measurements from waveform measurement units (WMUs). In the proposed method, different physical characteristics, as well as statistical features, are extracted from synchronized voltage waveform measurements to filter anomalies. Then, the anomaly identification approach based on the random forest is developed and deployed into the FNET/GridEye system considering trade-offs among accuracy, computational burden, and deployment cost. Moreover, four WMUs are specially designed and deployed on Kauai Island to receive instantaneous synchronized voltage waveform measurements. To verify the performance of the proposed algorithm, different experiments are carried out with collected field test data. The result demonstrates that the performance of the proposed synchro-waveform-based anomaly categorization algorithm can accurately identify anomalies 95.35% of the time, which has comparable performance among benchmarking algorithms.

Situational awareness↗

Utility Perspective on Protection Challenges with High Penetration of IBRs

Utilities have seen rapid increase in Solar, Wind, and Battery Energy Storage Resources that interconnect to their electric system through Inverters. Inverter-Based Resources (IBRs) have fault current characteristics that are unlike the fault current response of traditional rotating-machine-based generators, which is well known and repeatable. IBR’s non-traditional fault current behavior is due to the IBR control scheme, which is configured to provide a clean AC output but also protect the inverter’s sensitive power electronics devices from damage, one source of which is overcurrent. This results in low fault current magnitude, low or no negative sequence current injection, the variability of sequence component currents, the variability of voltage with respect to current angles, and the lack of inertia. The control scheme also results in a fault current response that can vary between manufactures and between models of the same manufacturer. High penetration of IBRs can adversely affect the protection schemes applied in areas with high penetration of IBRs. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems. This is mainly because the existing protection elements and practices have been designed based on the fault current response of conventional rotating machines. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This report / presentation identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. Instead of facing on one issue, this report looks broadly on all the challenges that system protection has experienced with high penetration of IBRs. Based on the IBR response from various utilities during real fault events and gathering perspective from different utility SMEs via questionnaire, the report summarizes on gathered data and internal experiences.

14 SOLAR ENERGY↗

Stability Analysis of Power Systems with High Penetration of State-of-the-Art Inverter Technologies

With the increasing level of inverter-based resources (IBRs) in modern power systems, this paper presents a small-signal stability analysis for power systems comprising synchronous generators (SGs) and IBRs. Four types of inverter controls are considered: two grid-following (GFL) controls, with or without grid support functions; droop-based grid-forming (GFM) controls; and virtual oscillator control-based GFM. We also analyze the impact of STATCOM and synchronous condensers on system stability to assess their role in the energy mix transition. With the small-signal dynamic behavior of the major technologies modeled, this paper provides stringent stability assessments using the IEEE 39-bus benchmark system modified to simulate future power systems. The exhaustive test cases allow for (a) assessing the impacts of different types and controls of generation and supplementary grid assets, as well as system inertia and line impedance on grid stability, and (b) elucidating pathways for the stabilization of IBR-dominated power systems. The analysis also indicates that future power systems can be stabilized with only a fraction of the total generation as voltage sources without SGs or significant system inertia if they are well distributed. This study provides insights into future power system operations with a high level of IBRs that can also be used for planning and operation studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Quantifying System Strength From Grid-Forming Resources Using Frequency Scan Approach: Preprint

Current industry practices for quantifying the system strength contribution from grid-forming (GFM) resources to ensure stability of power systems dominated by inverter-based resources (IBRs) are primarily based on iterative electromagnetic transient (EMT) time-domain simulation studies. While feasible, these approaches are resource-intensive, lack scalability and intuition, and might not evaluate the system strength contribution over the entire frequency range of interest. This paper introduces a novel, frequency-domain approach to quantify system strength support provided by a GFM resource using frequency scans. The proposed method uses transfer functions from the grid voltage magnitude (V) and phase (?), respectively, to the reactive (Q) and active power (P) output of a GFM resource for quantifying its contribution to system strength. These transfer functions provide a direct measure of the ability of a GFM resource to behave as a stiff voltage source behind a reactance over a specified frequency range, enabling robust quantification of its system strength contribution. The key innovation of this work is the development of a frequency domain system strength metric called the dynamic short-circuit ratio (dSCR) that is suitable for IBR-dominated power systems and is directly related with the familiar short circuit ratio (SCR) metric. The new metric, dSCR, enables the assessment of system strength contributions from both synchronous machines and converter-based GFM resources using a unified benchmark, which is not possible with the traditional SCR metric. The paper also demonstrates how impedance scans could identify if an unstable condition observed during weak grid conditions is a result of the lack active or reactive power support or both. By leveraging the proposed frequency-domain dSCR metric for quantifying system strength contribution from GFM IBRs, the paper demonstrates targeted mitigation strategies for weak grid instabilities without resorting to repeated, time-consuming time-domain simulations. The result is a scalable and efficient approach to remediate stability challenges in power systems with high shares of IBRs and accelerating the integration of GFM technologies for system strength support in power systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Robust Restoration From Cyber-Physical Attacks in Active Distribution Grids With Grid-Edge IBRs

The inverter-based resources (IBRs) have enabled the integration of renewable energy at the grid edge with enhanced control capabilities to support the reliable operation of power grids. Different control frameworks, such as hierarchical or distributed architecture, have been proposed with the expansion of cyber networks for real-time monitoring and control. This evolution of critical infrastructure into cyber-physical systems also brings more vulnerabilities for the broadened attack surfaces, and significantly increases the possibility of physical system failures or outages caused by cyberattacks. Among tremendous efforts in the defense-in-depth approach, it remains challenging to provide prompt detection and accurate location of attack entry points or paths. Therefore, the prevailing restoration framework may struggle to fully consider the cyber-physical interdependence, successfully isolate the compromised cyber and physical components, and safely recover the systems without the potential risks leading to secondary outages. This paper is motivated to develop a cyber-physical restoration framework for distribution grids to recover from cyber attacks by harnessing grid-edge IBRs. The framework is first built on the operational guidelines of IBRs considering the compromised cyber layer. Then, an ambiguity set is established to represent the uncertainty of attack scenarios and their possibility levels. Next, a distributionally robust optimization model is developed to provide the optimal load restoration strategy across all scenarios. The effectiveness of the proposed model is demonstrated through various use cases on the modified IEEE 13-node and 123-node test systems. Finally, simulation results demonstrate the effectiveness and advancement of developed post-attack restoration strategies.

Cybersecurity↗

Interoperable, Inverter - Based Distributed Energy Resources Enable 100% Renewable and Resilient Utility Microgrids

As microgrids transition away from use of conventional generating resources and increasingly rely on renewable resources towards decarbonization goals, it is crucial to evaluate the capability inverter-based resources to provide microgrid stability and resilience. Particularly, microgrids with a high contribution of intermittent solar photo voltaic generation and higher load variability present unique challenges requiring fast voltage and frequency support. At the San Diego Gas & Electric Company(R) (SDG&E(R)) Borrego Springs Microgrid, a battery inverter was upgraded with grid-forming (GFM) capability to serve as island leader, transitioning responsibility away from diesel generators. An interoperable microgrid control scheme was developed, coordinating GFM and grid-following (GFL) inverters. Hardware-in-the-loop (HIL) simulations using relevant power and controller HIL interfaces between real-time simulators and field equipment are being conducted to de-risk field deployment.

battery energy storage↗

Secure and Resilient Operations Using Open-Source Distributed Systems Platform (OpenDSP)

The goal of this project is to identify and address cybersecurity gaps by developing a multi-layer multi-channel cyber-physical defense and survival mechanism for operating distribution networks with high penetration of solar / inverter-based resource (IBR) / distributed energy resource (DER). The proposed security enhancements are built upon the distributed framework and solution architecture for both information technology (IT) and operational technology (OT) systems. The technical solutions consist of two composite functionalities and six layers: proactive defense (vulnerability assessment, communication protection, and attack detection, as layers 1-3), and adaptive self-healing (attack-resilient control, adaptive recovery, and resilient survival, as layers 4-6). These layers, built on and extended from DHS CISA Cyber Framework, establish an integrated and robust cybersecurity framework for operating large-scale distribution networks.

14 SOLAR ENERGY↗

Advanced grid-forming (GFM) inverter controls, modeling and system impact study for inverter dominated grids

Our main goals in this project are to understand: 1) the stability of the power system with very high penetration of PV or other inverter-based resources (IBR), 2) the interactions among IBRs and traditional generators, and 3) the impact of the GFM inverters on bulk power system. To achieve these goals, we took a holistic research and development approach. First, an impedance-based large system modeling and stability analysis tool was developed to aid the large IBR system small-signal stability analysis. Second, consensus-based control and transient overload ride through were developed to control and coordinate multiple GFM inverters in a large system to maintain transient stability during big grid events. Third, high fidelity electromagnetic transient (EMT) IBR models were developed and integrated into a large reduced WECC model to study the system impact from IBRs. Lastly, extensive validation tests of the GFM control which was developed in this project and implemented in two 1MW commercial solar inverters were performed using different validation platforms, e.g., control hardware-in-the-loop (CHIL) platform, power hardware- in-the-loop (PHIL) platform, and a real PV plant.

14 SOLAR ENERGY↗

Black-Starting Microgrids Using Inverter-Based Distributed Energy Resources

Recent trends in power systems show increasing deployment of inverter-based distributed energy resources (DERs) at the distribution level. Efforts have also been made to use inverter-based DERs for system restoration of critical sections of distribution feeders. In the past few years, there has been active consideration of using local grid-forming (GFM) DERs, which can form their own voltage and frequency, to black-start microgrids instead of waiting for the bulk system for supply restoration. However, using current-limited inverter-based DERs for black-start operations with high inrush currents can pose some technical challenges. This paper presents detailed electromagnetic transient studies on a digital real-time simulator to assess the operational feasibility of using local inverter-based GFM DERs for microgrid black-start operations as a bottom-up approach instead of a top-down approach where the substation is used to restore critical sections of the feeder. The paper presents key modeling details for distribution system components for studying GFM DER-based microgrid black-start operations. The paper presents simulation results comparing different black-start approaches using GFM DERs for two test systems: i) a simple test microgrid and ii) a real-world utility microgrid currently being designed and deployed by Holy Cross Energy in Colorado.

black start↗

Power-Hardware-in-the-Loop Experiments of a Microgrid with a Grid-Forming Battery Inverter

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power-Hardware-in-the-Loop Experiments of a Microgrid With a Grid-Forming Battery Inverter: Preprint

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗