Test Report: Glovebox Test Fire for Evaluation of Effects on Containers and Windows
This test report describes a designed Glovebox (GB) fire to identify target environmental conditions that GB containers and windows are subject to such fires. The fire was designed by representatives from the Los Alamos National Laboratory (LANL) to replicate a realistic worst-case fire scenario at LANL. Key results of these experiments include: • The GB fire was active for more than 30 minutes. • Thermocouples were placed at multiple points in the GB were measured, including one on top of the container. Temperatures at varied widely as a function of location during the fires, as might be expected and as a function of proximity to fire, elevation in the GB, and in relation airflow present during the test, which constantly introduces room-temperature air into the GB. The maximum temperature recorded by a thermocouple was slightly less than 500°F at the elevation of the highest gloveports and near, but not in contact with the GB wall. • A thermographic camera imaged the region of the GB container during the fire. These data report container temperatures of up to approximately 900°F (482°C) over a period of several minutes. • Four kilograms of lead shot were held in the container. The majority of the shot melted during the course of the fire (lead melting point: 621°F/327°C). • Multiple windows fractured during the test. In some cases, the polymer interlayer of the laminated GB window glass appears to have sustained damage due to thermal breakdown of the polymer, though the interlayer of the laminated GB window glass appears to have remained intact in all cases. • The one window with an attached thermocouple was less affected by the fire. The attached thermocouple measured up to approximately 150°F. • Other thermocouples along (but not in contact with) the GB wall and closer to the fire (and cracked windows) reported up to approximately 200°C (392° F). These finding suggest that subjecting containers to 500°C for 45 minutes is bounding and representative for fires of this type. It should also be noted that 500°C (932°F) has been previously used as a test criterion for related work. Similarly, 200°C may be a reasonable target temperature for GB windows subjected to fires of this type.