Modeling Zone-3 Protection with Generic Relay Models for Dynamic Contingency Analysis
This paper presents a cohesive approach for calculating and coordinating the settings of multiple zone-3 protections for dynamic contingency analysis. The zone-3 protections are represented by generic distance relay models. A two-step approach for determining zone-3 relay settings is proposed. The first step is to calculate settings, particularly, the reach, of each zone-3 relay individually by iteratively running line open-end fault short circuit analysis; the blinder is also employed and properly set to meet the industry standard under extreme loading conditions. The second step is to systematically coordinate the protection settings of the zone-3 relays. The main objective of this coordination step is to address the over-reaching issues. We have developed a tool to automate the proposed approach and generate the settings of all distance relays in a PSS/E dyr format file. The calculated zone-3 settings have been tested on a modified IEEE 300 system using a dynamic contingency analysis tool (DCAT).