Search NASA⌕ Search

SEARCH · Search NASA

Results for “Inverters”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 109 records · Page 6

A Trade-Off Study Between the Primary and Transient Responses of Grid-Forming Inverters

The control parameters of the grid-forming (GFM) inverter-based resources (IBRs) directly impact power system dynamics. The primary control requires the GFM inverter to balance generation and load. It is also preferred that a GFM inverter maintain the terminal frequency after a power system fault. In this paper, we investigate the trade-off between the primary control objective and the transient response. To quantify the transient performance of the GFM inverter, we introduce a new real-time transient stability index (TSI). This index plays a crucial role in our investigation, as it allows us to compare the performance trade-offs of different sets of GFM control parameters.

Lin, Xuheng↗

Use of Power Hardware-in-the-Loop and Controller Hardware-in-the-Loop to De-Risk the Use Of Grid-Forming Fuel Cell Inverters in Microgrids

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such interfaces are particularly challenging when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This presentation shows the use of PHIL interfaces for such microgrids and the preliminary experimental results.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Interoperable, Inverter - Based Distributed Energy Resources Enable 100% Renewable and Resilient Utility Microgrids

As microgrids transition away from use of conventional generating resources and increasingly rely on renewable resources towards decarbonization goals, it is crucial to evaluate the capability inverter-based resources to provide microgrid stability and resilience. Particularly, microgrids with a high contribution of intermittent solar photo voltaic generation and higher load variability present unique challenges requiring fast voltage and frequency support. At the San Diego Gas & Electric Company(R) (SDG&E(R)) Borrego Springs Microgrid, a battery inverter was upgraded with grid-forming (GFM) capability to serve as island leader, transitioning responsibility away from diesel generators. An interoperable microgrid control scheme was developed, coordinating GFM and grid-following (GFL) inverters. Hardware-in-the-loop (HIL) simulations using relevant power and controller HIL interfaces between real-time simulators and field equipment are being conducted to de-risk field deployment.

battery energy storage↗

Dynamic Validation of CNN-Based Surrogate Models for Inverter-Based Resources in Open-Source Solvers

Traditionally, distribution system planning has focused on steady-state analyses, with limited consideration of dynamic behavior. However, as large or medium-scale inverter-based resources (IBRs), particularly grid-following (GFL) inverters in commercial or industry buildings, become more prevalent, understanding their dynamic impact is essential for grid planning and operation. This article presents an innovative deep-learning (DL)-approach using convolutional neural networks technique to model the GFL inverters. Developed from real grid-tied commercial IBR transient data, these dynamic DL models overcome proprietary constraints by requiring minimal knowledge of internal converter physics while maintaining high accuracy and flexibility. To demonstrate their applicability, the models were incorporated into GridLAB-D, an open-source, three-phase distribution analysis tool. This integration enables dynamic simulations of large-scale distribution networks with high IBR penetration stability analysis. Rigorous testing and validation, aligned with industry standards, confirmed the reliability and efficiency of this approach, paving the way for enhanced planning and operational assessments of modern power systems.

Deep-learning↗

Experiences and Lessons from Field Demonstration of Grid-forming Inverter in An AC Microgrid

The validation of GFM control strategies through simulation and hardware demonstration is important before their large-scale deployments in the real grid. Considering the importance of testing and validation, several works have explored the GFM inverter’s capability to blackstart a microgrid, synchronize and share loads, and interact with various types of generation sources and loads present in the grid. Herein, this paper complements the existing works by presenting the results and analysis of a field demonstration in an actual AC microgrid. The capability of a three-level neutral point clamped (NPC) GFM inverter equipped with a recursive feedback type of non-linear device level control to operate with PV source on its DC input and off-the-shelf PVGFL inverters and EV chargers of different kinds on the AC side is explored. The analysis and conclusions drawn would inform the readers to make better decisions during the field demonstration process.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Virtual Self-Excited Induction Generator-Based Grid-Forming Inverter Control for Robust Voltage Regulation Under Nonideal Loading

This paper presents a generator-inspired control methodology for grid-forming (GFM) inverters that deliberately emulates a self-excited induction generator so that the inverter can hold its voltage and frequency under difficult loading and severe terminal disturbances across wide voltage and frequency ranges. The design integrates a Lyapunov energy function-based inner loop to provide high bandwidth and strong disturbance rejection, and it complements this with a passivity-based argument that furnishes a coherent large-signal stability guarantee beyond small-signal limits. Analytical insights are developed via the Krylov-Bogoliubov-Mitropolsky averaging method, which reveals an intrinsic resistive droop characteristic; these closed-form relations both explain the observed dynamics and yield simple, decentralized tuning rules. The methodology is validated on a controller-hardware-in-the-loop platform and exercised in real time across balanced, unbalanced, and nonlinear loads, as well as during parallel operation. Across these scenarios, the inverter maintains balanced three-phase voltages, limits harmonic content, settles quickly with well-damped transients, and remains resilient when multiple units operate in parallel. The contributions are a self-excited-machine-inspired GFM controller with enhanced dynamic performance and robustness, a single stability rationale grounded in passivity, closed-form expressions that guide tuning, and comprehensive hardware-in-the-loop validations demonstrating effectiveness and superiority under challenging operating conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Two-Phase Cooling for High Packaging Density Planar Inverter: Cooperative Research and Development Final Report, CRADA Number CRD-15-00592

The project objective was to utilize two-phase heat transfer to enable compact and power-dense inverters. The high heat transfer capacity and near isothermal characteristics of two-phase cooling can enable higher power densities, reducing the size and cost of the power electronics system. This project focused on developing efficient, passive (no pump or compressor) two-phase cooling strategies that consist of an air-cooled condenser and evaporator. This report describes the modeling work conducted to design the evaporator and air-cooled condenser for a prototype inverter development work underway in the John Deere. Prototypes of the final evaporator and condenser designs were then fabricated via 3D printing for testing. Experiments on the evaporator confirmed that this component can meet the heat load and junction temperatures requirements for Si IGBT (insulated-gate bipolar transistor) inverter. Experiments with the air-cooled condenser were not possible due to leaks through the condenser walls.

33 ADVANCED PROPULSION SYSTEMS↗

Autonomous Inverter Controls for Resilient and Secure Grid Operation: Vector Control Design for Grid Forming

The project addresses both fundamental and practical challenges of GFM/GFL inverter control for the power grids with high inverter based resources (IBRs) penetration. A data- driven modeling technique is applied to accurately model dynamics of PWM inverters, including electromagnetic-transient (EMT). Systematic and integrative designs of grid- forming (GFM) and grid-following (GFL) primary controls are developed to guarantee system performance under either normal or abnormal operating conditions without violating constraints. This modeling and control framework provides black-start capability in case of an outage without relying on rotating generators, and its secondary control is also shown to enhance resilience against cyber-physical attacks.

14 SOLAR ENERGY↗

How Inverter-Based Resources (IBRs) Affect Protection Relay Elements

Inverter-based resources (IBRs) exhibit fault responses that differ significantly from those of synchronous generators, which can challenge the reliable operation of many commonly used power system protection elements. The fault response of IBRs is primarily influenced by their control algorithms and configurations, but the impact of these controls on protection relays is not yet fully understood. This presentation provides a comprehensive study of how IBR modeling and controls affect transmission line protection. Key modeling and control aspects include the DC source, inverter model, power level control, current control, and current limiting. The study reveals that certain aspects - such as the type of DC source (battery, PV, or hybrid), inverter model (average vs. switching), and power level control methods (PQ dispatch vs. Vdc-Vac control for grid-following IBRs, and droop vs. VSM for grid-forming IBRs) - do not significantly affect relay response. However, faster control loops, such as current control and current limiting, do influence the relay behavior. Additionally, the study explores the effects of other factors, including momentary cessation, operating points, fast/slow current responses, and grid strength on relay performance. Finally, the study offers recommendations for both IBR and protection engineers to improve IBR fault response and enhance the reliability of protection systems.

14 SOLAR ENERGY↗

UNIFI 1-MW Multi-Vendor Grid-Forming Inverter Test Updates

This presentation gives an update on UNIFI 1MW multi-vendor GFM inverter testing. The 1MW demo enters the last stage of the test, which is the integration test. And the main objectives of the integration tests include: 1) explore the interoperability of dispatching a future grid with energy mix (GFM inverters, GFL inverters and synchronous machine). The presentation highlights one example test, ROCOF, and summarizes all the key learning.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Cryogenically-Cooled MW Inverter for Electric Aircraft Propulsion

Power electronic converter will be a key enabler for future electrified aircraft propulsion system. In aircraft applications, superconducting technologies such as superconducting motors and generators along with supporting power systems will grow in importance. Utilizing cryogenic cooling for power converter potentially can significantly improve the inverter system efficiency and specific power. This paper presents the cooling, hardware,and testing of a cryogenically-cooled MW inverter developed for electrified aircraft propulsion system. The 1 MVA full load testing with cryogenic cooling is demonstrated. The developed inverter system achieves 18 kVA/kg specific power and 99% efficiency, which provides a promising solution to achieve high power density and efficiency for future electrified aircraft propulsion system.

cryogenically-cooled inverter↗

Real-Time Testbed for Studying Cyberattacks and Defense in DER-integrated Smart Inverter Systems

In this paper, we propose a Hardware-in-the-Loop (HIL) simulation testbed suitable for the implementation and testing of realistic cyberattacks on grid-tied smart inverter systems integrated with Distributed Energy Resources (DER) that use the Distributed Network Protocol-3 (DNP3) protocol for communications between grid components. Specifically, our testbed combines a Real-Time Digital Simulator (RTDS) NovaCor device, outfitted with GNETx2 network interface cards, a gridtied DER topology implemented via the RTDS software package RSCAD, and a custom virtual network that emulates a man in the middle attacker. The Man-in-the-Middle (MITM) attacker captures DNP3 traffic and falsifies telemetry data in DNP3 packets to trigger unwarranted commands from a DNP3 controller that exploit smart inverter grid support functions. We choose DNP3 and implement grid support functions according to the IEEE Std. 1547-2018 mandated for the interconnection and interoperability of DER power systems with associated power components. Furthermore, we develop a protocol payload agnostic attack detection framework that leverages the round-trip time (RTT) anomalies between DNP3 requests and responses and can detect the presence of attacks without having to analyze the payload’s contents, while balancing trade-offs between false alarm counts, missed detections, and time to detection. To facilitate further research, we publicly release benign and attack network traffic exchanged between various sensors, controllers, and actuators in our grid-tied inverter testbed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Cyber Threat Landscape and Engineering Mitigations for Grid Forming Inverters

This talk will cover the cyber threat landscape and engineering mitigations for grid forming (GFM) inverters. It will discuss the penetration of inverter-based resources (IBRs) in the United States and expected growth. It will then discuss the threat landscape for IBRs based on current and expected penetration. Real-world examples of cyber incidents affecting IBRs will be presented, concluding with an introduction to Cyber-Informed Engineering (CIE) and a guide on applying it to GFM inverters.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Stability Analysis of Power Systems with High Penetration of State-of-the-Art Inverter Technologies

With the increasing level of inverter-based resources (IBRs) in modern power systems, this paper presents a small-signal stability analysis for power systems comprising synchronous generators (SGs) and IBRs. Four types of inverter controls are considered: two grid-following (GFL) controls, with or without grid support functions; droop-based grid-forming (GFM) controls; and virtual oscillator control-based GFM. We also analyze the impact of STATCOM and synchronous condensers on system stability to assess their role in the energy mix transition. With the small-signal dynamic behavior of the major technologies modeled, this paper provides stringent stability assessments using the IEEE 39-bus benchmark system modified to simulate future power systems. The exhaustive test cases allow for (a) assessing the impacts of different types and controls of generation and supplementary grid assets, as well as system inertia and line impedance on grid stability, and (b) elucidating pathways for the stabilization of IBR-dominated power systems. The analysis also indicates that future power systems can be stabilized with only a fraction of the total generation as voltage sources without SGs or significant system inertia if they are well distributed. This study provides insights into future power system operations with a high level of IBRs that can also be used for planning and operation studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Out-of-time-ordered-correlators for the pure inverted quartic oscillator: classical chaos meets quantum stability

Out-of-time-ordered-correlators (OTOCs) have been suggested as a means to diagnose chaotic behavior in quantum mechanical systems. Recently, it was found that OTOCs display exponential growth for the inverted quantum harmonic oscillator, mirroring the fact that this system is classically and quantum mechanically unstable. In this work, I study OTOCs for the inverted anharmonic (pure quartic) oscillator in quantum mechanics, finding only oscillatory behavior despite the classically unstable nature of the system. For higher temperature, OTOCs seem to exhibit saturation consistent with a value of –2< x 2 > T < p 2 > T at late times. I provide analytic evidence from the spectral zeta-function and the WKB method as well as direct numerical solutions of the Schrödinger equation that the inverted quartic oscillator possesses a real and positive energy eigenspectrum, and normalizable wave-functions.

72 PHYSICS OF ELEMENTARY PARTICLES AND FIELDS↗

Nanoscale Amorphization of Poly(Triarylamine) for Efficient and Stable Inverted Perovskite Photovoltaics

Perovskite solar modules require hole-selective layers that combine efficient charge extraction, interfacial uniformity and scalable processing. Poly(triarylamine) (PTAA) is widely used in high-performance inverted perovskite photovoltaics, but its nanoscale crystallization and aggregation on indium tin oxide can disrupt film continuity, increase interfacial recombination and limit module stability. Here we show that 4-fluorobenzylphosphonic acid (4FBPA) modifies the surface of indium tin oxide to induce nanoscale amorphization of PTAA, forming a uniform sub-10-nm hole-selective layer. The molecule binds to indium tin oxide through a dehydration reaction, tunes the work function and surface free energy of the photoanode, and improves energy-level alignment with PTAA. The resulting amorphous PTAA film shows enhanced conductivity and hole extraction, suppresses non-radiative recombination at the buried interface and promotes more uniform perovskite growth. Inverted perovskite solar cells reach a power conversion efficiency of 26.63%, while blade-coated modules achieve a certified quasi-steady-state efficiency of 23.01%. The modules retain 95.9% of their initial efficiency after 2,600 hours of maximum-power-point operation under 1-sun illumination at 65 +- 5 degrees C in nitrogen. These results identify nanoscale amorphization of polymeric hole-selective layers as a route to efficient and stable inverted perovskite photovoltaics.

14 SOLAR ENERGY↗

Comprehensive AI-based System for Control, Sensor Estimation, and Fault Detection of Cascaded Multilevel Inverters

In this paper, an Artificial Intelligence-based (AI) system is proposed for an 11-level cascaded H-bridge multilevel inverter (MLI) with the aims of harmonic suppression and reliability enhancement. The system consists of three seamlessly integrated Neural Networks (NNs). First, a multilayer perceptron is used to generalize the optimal switching angles for selective harmonic elimination under non-equal DC voltages. Next, an autoencoder NN estimates the voltage sensor readings to address potential drifting. Finally, a perceptron NN detects inverter faults based solely on the output voltage of the MLI. Simulation scenarios were evaluated, and the results show that the proposed system provides a comprehensive solution for the robust operation of the MLI. The proposed solution is capable of minimizing the targeted harmonics orders with minimal impact on the fundamental voltage, even when the voltage sensor drifts. Furthermore, the inverter under fault conditions was successfully identified.

Rezende da Costa Reis Kimpara, Renata↗

Inverter Intensive Hybrid Power Plant Modeling with Small-Signal Stability Augmentation through Flexible Operation Mode Transition

Hybrid power plants (HPPs) prompt the penetration of inverter-based renewable energy sources (RES) in transmission systems; however, given their low-inertia nature, HPPs are dominated by power electronic inverters, so there are inevitable challenges in system stability when increasing numbers of HPPs are integrated into the modern power grids. To boost the penetration level of HPPs without jeopardizing system stability, it is desirable to equip them with operational characteristics (i.e., grid-forming capabilities) that are comparable to those of conventional power plants dominated by synchronous generators (SGs). In this paper, a holistic model of inverter intensive HPP is derived and a bi-level hierarchical control is developed to allow HPPs to flexibly switch among the designed operation modes (i.e., P-Q, P-V, and isochronous modes). Compared to SGs, which have limited controllability, the operation mode of each HPP could vary as requested. Such flexible mode transitions could be integrated into the secondary plant-level control and be leveraged as an additional control degree to further augment system stability. Further, the system small-signal stability margin is quantified with varying HPP operation modes. More importantly, modal analysis is thereby conducted to quantify the impacts of mode transition on the system oscillatory modes. The effectiveness of the proposed HPP bi-level hierarchical control is verified using extensive case studies based on the simplified real-world island power grid, and the results validate that the system small-signal stability margin can be enhanced with the additional degree of control flexibility enabled by HPP operation mode transition. The real-time hardware-in-the-loop (HIL) results are also provided to verify the proposed method.

grid-forming control↗