White Paper on Case Study of Safe Installation of Second-Life Energy Storage System
This technical report provides for a case study for the safe installation of a second-life, or repurposed, battery, that has been reconfigured for use as a stationary energy storage systems (ESS). Driven by legislative requirements such as California Senate Bill 615 and projections that retired EV batteries could meet a substantial portion of U.S. grid ESS needs beginning in 2035, the repurposing of EV batteries is anticipated to grow significantly. However, safety concerns arise from the effects of aging, unknown prior usage history, and changes in thermal runaway behavior, which may increase failure risks compared to new batteries. NFPA 855, the predominant U.S. standard for ESS installation, mandates that second-life batteries meet all requirements for new batteries, with repurposers complying with UL 1974 in addition to obtaining UL 9540 and UL 1973 listings. These are certifications that few repurposers have achieved and represent a regulatory barrier to entry for the market as a whole.