At least 109 records · Page 6

Model-based interface design for smart field-device integration

Operational complexity is ever-increasing for electric utilities that face challenges including integration of DERs, customer expectation of energy choices, the proliferation of non-utility-owned resources, new business models with energy service providers, and new technology with IT/OT convergence. To maintain and improve the quality of operations, planning, and decision-making in general, utilities need to manage and navigate the complexity. Managing complexity requires a modular, scalable, and flexible solution. Connecting large amounts of DERs and introducing new services requires increased grid control and evolving applications. In this paper, we show an approach utilizing model-based standardized interfaces that simplifies integration and deployment of new algorithms and smart field devices for interoperability across legacy or new systems. A modular design is presented for a reference implementation of widely used DNP3 and IEEE 2030.5 interfaces within an open-source, standards-based data integration platform for integration of smart field devices with independently developed, best-of-breed applications.

Model-driven development, system integration, smar↗

Interoperable, Inverter - Based Distributed Energy Resources Enable 100% Renewable and Resilient Utility Microgrids

As microgrids transition away from use of conventional generating resources and increasingly rely on renewable resources towards decarbonization goals, it is crucial to evaluate the capability inverter-based resources to provide microgrid stability and resilience. Particularly, microgrids with a high contribution of intermittent solar photo voltaic generation and higher load variability present unique challenges requiring fast voltage and frequency support. At the San Diego Gas & Electric Company(R) (SDG&E(R)) Borrego Springs Microgrid, a battery inverter was upgraded with grid-forming (GFM) capability to serve as island leader, transitioning responsibility away from diesel generators. An interoperable microgrid control scheme was developed, coordinating GFM and grid-following (GFL) inverters. Hardware-in-the-loop (HIL) simulations using relevant power and controller HIL interfaces between real-time simulators and field equipment are being conducted to de-risk field deployment.

battery energy storage↗

Communication enabled – fast acting imbalance reserve (CE-FAIR)

This letter presents a new frequency control strategy that takes advantage of communications and fast responding resources like PV generation, energy storage, wind generation, and demand response, termed collectively as converter interfaced generators (CIGs). The proposed approach uses an active monitoring of power imbalances to rapidly redispatch CIGs. This approach differs from previously proposed frequency control schemes in that it employs feed-forward control based on a measured power imbalance rather that relying on a frequency measurement. As a result, time-domain simulations of the full Western Electricity Coordinating Council (WECC) system are conducted to demonstrate the effectiveness of the proposed method, showing improved performance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modelling a single phase voltage controlled rectifier using Laplace transforms

The development of a 20 kHz, AC power system by NASA for large space projects has spurred a need to develop models for the equipment which will be used on these single phase systems. To date, models for the AC source (i.e., inverters) have been developed. It is the intent of this paper to develop a method to model the single phase voltage controlled rectifiers which will be attached to the AC power grid as an interface for connected loads. A modified version of EPRI's HARMFLO program is used as the shell for these models. The results obtained from the model developed in this paper are quite adequate for the analysis of problems such as voltage resonance. The unique technique presented in this paper uses the Laplace transforms to determine the harmonic content of the load current of the rectifier rather than a curve fitting technique. Laplace transforms yield the coefficient of the differential equations which model the line current to the rectifier directly.

Kraft, L. Alan↗

DERMS-RT (Distributed Energy Resource Management Solution using Real-Time Optimization) [SWR-20-46]

DERMS-RT provides a distributed energy resource management solution using real-time optimization to control different types of distributed energy resources (DERs) — such as rooftop PVs, battery energy storage systems, HVAC loads, electric water heater loads, and EV charging loads, and use these DERs to provide distribution voltage regulation and peak demand management services. The control approach implemented by DERM-RT is developed based on the real-time optimal power flow and distributed control previously developed by NREL researchers. The software codes are designed to provide modular DER management solution that can be easily applied to control heterogeneous DERs in distribution grids in coordination with centralized utility management systems. Also, DERMS-RT provides application programming interface (API) to extract useful grid model information from an open-source power system simulation software, use the information to solve the optimization problem, and apply the optimal set-points to the controlled DERs. In this way, DERMS-RT provides a plug-and-play function for implementing the real-time DER control on different utility system models, and it can be used as a simulation testbed to demonstrate the impact of real-time DER optimization on improving grid operations.

Ding, Fei↗

Hybrid active vibration control of rotorbearing systems using piezoelectric actuators

The vibrations of a flexible rotor are controlled using piezoelectric actuators. The controller includes active analog components and a hybrid interface with a digital computer. The computer utilizes a grid search algorithm to select feedback gains that minimize a vibration norm at a specific operating speed. These gains are then downloaded as active stillnesses and dampings with a linear fit throughout the operating speed range to obtain a very effective vibration control.

Palazzolo, A. B.↗

Using a Grid-Forming Inverter to Stabilize a Low-Inertia Power System - Maui Hawaiian Island

As power systems around the world integrate greater amounts of wind and solar photovoltaic power, periods of very high instantaneous power shares of inverters, the primary interfacing technology for these generation sources, are complicating system stability and control. The contemporary, primary mode of inverter operation, grid-following, which explicitly assumes the presence of a local, stable voltage waveform, yields operational inadequacy at high instantaneous power shares potentially leading to instability due to the low-inertia conditions, as well as the correlated reduced voltage forming capacity on the respective system. Parallel connected grid-forming inverters, which directly regulate the local voltage, are a solution that is expected to bolster system stability and mitigate the shortcomings of the grid-following technology. In this paper, grid-following and two types of grid-forming inverter control, the traditional linear droop and the recently introduced nonlinear exponential droop (Droop-e), are simulated on a low-inertia, H = 0.48s, high inverter-based resource scenario, 97%, with a validated electromagentic transient domain model of the Hawaiian island of Maui power system. The benefit of a single grid-forming device over its grid-following counterpart is significant, both in terms frequency deviation and voltage stability. Further, the superiority of the Droop-e and the associated secondary power sharing control over both grid-following and linear droop grid-forming technologies is displayed, with improved nadir and rate of change of frequency over the linear droop control.

droop control↗

A study of the diffusional behavior of a two-phase metal matrix composite exposed to a high temperature environment

The progress of diffusion-controlled filament-matrix interaction in a metal matrix composite where the filaments and matrix comprise a two-phase binary alloy system was studied by mathematically modeling compositional changes resulting from prolonged elevated temperature exposure. The analysis treats a finite, diffusion-controlled, two-phase moving-interface problem by means of a variable-grid finite-difference technique. The Ni-W system was selected as an example system. Modeling was carried out for the 1000 to 1200 C temperature range for unidirectional composites containing from 6 to 40 volume percent tungsten filaments in a Ni matrix. The results are displayed to show both the change in filament diameter and matrix composition as a function of exposure time. Compositional profiles produced between first and second nearest neighbor filaments were calculated by superposition of finite-difference solutions of the diffusion equations.

Tenney, D. R.↗

Securing Inverter Communication: Proactive Intrusion Detection and Mitigation System to Tap, Analyze, and Act

The electric grid has undergone rapid, revolutionary changes in recent years; from the addition of advanced smart technologies to the growing penetration of distributed energy resources (DERs) to increased interconnectivity and communications. However, these added communications, access interfaces, and third-party software to enable autonomous control schemes and interconnectivity also expand the attack surface of the grid. To address the gap of DER cybersecurity and secure the grid-edge to motivate a holistic, defense-in-depth approach, a proactive intrusion detection and mitigation system (PIDMS) device was developed to secure PV smart inverter communications. The PIDMS was developed as a distributed, flexible bump-in-the-wire (BITW) solution for protecting PV smart inverter communications. Both cyber (network traffic) and physical (power system measurements) are processed using network intrusion monitoring tools and custom machinelearning algorithms for deep packet analysis and cyber-physical event correlation. The PIDMS not only detects abnormal events but also deploys mitigations to limit or eliminate system impact; the PIDMS communicates with peer PIDMSs at different locations using the MQTT protocol for increased situational awareness and alerting. The details of the PIDMS methodology and prototype development are detailed in this report as well as the evaluation results within a cyber-physical emulation environment and subsequent industry feedback.

14 SOLAR ENERGY↗

Energy Northwest — Advanced Grid Interactive Load Efficiency (AGILE) : A Techno-economic Assessment

The Advanced Grid Interactive Load Efficiency project team, led by Energy Northwest, was awarded funding as part of the fourth round of the Clean Energy Fund program to investigate, co-create, and complete a preliminary design for grid-interactive efficient buildings (GEBs) for a number of schools served by Grays Harbor PUD. The project team has evaluated different combinations of systems at selected school buildings and the potential to respond to grid and customer needs, and develop a preliminary system technical design, including specifying desired GEB technology options, determining communication and electrical interface requirements, assessing control software sensor requirements, and interfacing with building management systems. PNNL led the techno-economic assessment efforts, leveraging its advanced modeling and analytical methods and tools developed for building-to-grid integration. This report documents the economic assessment for different GEB design options, encompassing an in-depth examination of use cases and value propositions, assumptions and inputs, models, methods, case studies, as well as key findings.

24 POWER TRANSMISSION AND DISTRIBUTION↗

IFCPT S-Duct Grid-Adapted FUN3D Computations for the Third Propulsion Aerodynamics Works

Contributions of the unstructured Reynolds-averaged Navier-Stokes code, FUN3D, to the 3rd AIAA Propulsion Aerodynamics Workshop are described for the diffusing IFCPT S-Duct. Using workshop-supplied grids, results for the baseline S-Duct, baseline S-Duct with Aerodynamic Interface Plane (AIP) rake hardware, and baseline S-Duct with flow control devices are compared with experimental data and results computed with output-based, off-body grid adaptation in FUN3D. Due to the absence of influential geometry components, total pressure recovery is overpredicted on the baseline S-Duct and S-Duct with flow control vanes when compared to experimental values. An estimate for the exact value of total pressure recovery is derived for these cases given an infinitely refined mesh. When results from output-based mesh adaptation are compared with those computed on workshop-supplied grids, a considerable improvement in predicting total pressure recovery is observed. By including more representative geometry, output-based mesh adaptation compares very favorably with experimental data in terms of predicting the total pressure recovery cost-function; whereas, results computed using the workshop-supplied grids are underpredicted.

Davis, Zach S.↗

Reconfigurable and Dynamic Distribution Systems Enabled Using Self-Sustainable Minimal-Microgrids with Region Based Stability Guarantees

In this paper, a reconfigurable and dynamic distribution system is designed using self-sustainable minimal-microgrids (min-MGs). Particularly, multiple dynamic microgrids are implemented by aggregating local min-MGs in a controllable way to facilitate service restoration at critical grid infrastructures, especially during severe power outages (e.g., those induced by natural disasters). These dynamic microgrids are implemented surrounding inverter interfaced distributed energy resources (DERs) to pick up local critical loads. Stable transient process during neighboring microgrid disconnection and resynchronization is realized by involving additional control terms in the secondary control level. Meanwhile, in order to ensure a stable operation with dynamic topology change, a computationally efficient region-based stability assessment approach is developed to ensure stability guarantees of each inverter dominated min-MG with potential changes of external grids modeled as disturbances. In contrast to conventional point-by-point stability evaluation approaches, the proposed region-based stability analysis can intuitively exhibit the feasible region comprised of stable operating points and identify sufficient stability margin to tolerate disturbances of dynamic system topology variations. Theoretical analysis is verified using simulation in MATLAB/Simulink.

distribution systems↗

Investigating Short Circuit Models for Wind Turbine Generators

Short circuit study needs to be performed at the planning stage before connecting large gen erators with the electric grid. This study will reveal the impact of new generation on the fault levels of the grid. The fault levels will determine the rating of nearby equipment and setting of relays. However, a short circuit model of the new generation is required for this study. This report investigates and quantifies the short circuit models of different wind turbine generators (WTGs) and of wind farms, and using these models, explores the effects of the wind farms on the nearby switchgear. WTGs, commonly classified as Type 1, Type 2, Type 3, and Type 4, exhibit different short circuit behavior depending upon their architecture and controls. The short circuit model (synonymous to Thevenin model) of Type 1 WTG is well known; it comprises of a voltage source behind a transient reactance, X'. The transient reactance X' is derived using the reactance of stator, rotor and the magnetizing reactance. In case of Type 2 WTG, an external rotor resistance is used to increase the range of operating slips. The value of the external rotor resistance increases at higher operating slips. The effect of the external rotor resistance on the fault current response is analyzed by simulating a validated model of Type 2 WTG. The validation is performed using the field data from an actual 67-machine Type 2 wind farm located in Wyoming, USA. The results shows that the external rotor resistance should be considered in its Thevenin impedance for better accuracy. A wind farm contains a large number of WTGs, pad mounted transformers, and cables typically connected in a ‘daisy chain” configuration. The effect of these cable impedances on the short circuit model of Type 2 wind farm is examined using the validated models. It is found that the collector circuit cables inside the farm do not have a significant effect on the short circuit model of the farm. Based on this finding, a simple equivalencing procedure for the wind farm is proposed and validated. Faults inside and outside the wind farm are analyzed and recommendations to select main circuit breakers and generator circuit breakers are made. Type 3 WTG, also known as Doubly Fed Asynchronous Generator (DFAG), uses back to back converters in the rotor circuit to inject slip frequency voltage into the rotor circuit. Until recently, these machines used crowbar to short the rotor circuit during faults to protect the converter com ponents form high rotor currents resulting from faults. This type of WTG is simulated and the model is validated using field data from a 66-machine Type 3 wind farm in Wyoming, USA. The simulation study reveals that the crowbar feature is activated almost immediately after the fault takes place, and remains activated throughout the fault-period. This confirms that the short circuit model for Type 3 WTG with crowbar is similar to the model for Type 2 WTG. In the past, wind farms were allowed to disconnect during faults. However, recent grid codes around the world and in the United States demand that the wind farms be kept connected to the grid during faults, and provide certain reactive power quantified based on the voltage dip at the point of interconnection. This requirement, also called low voltage ride through (LVRT), can be accomplished by using Type 4 WTGs that employ full back to back converter interface between generators (permanent magnet synchronous generators are typically used) and the grid. However, the controls are proprietary, and hence the short circuit models are not well defined. This report proposes controls that enable the WTG to comply with the strictest grid codes, and based on this model, proposes a short circuit model of the Type 4 WTG. This model is not validated due to lack of validation data, but the use of grid code requirements as control objectives lends good credibility to the model. PSCAD/EMTDC ® , a powerful and time-tested time-domain simulation software is used to implement all models. This software is capable of modeling in detail all components of wind farms, and all components and controls of converters in time domain.

17 WIND ENERGY↗

Gridtrust: Electricity Grid Root-of-Trust Decentralized Supply Chain Cyber-Security (Final Scientific/Technical Report)

GridTrust represents a departure from reliance on a single organization or a single person to multiple organizations and therefore multiple people across organizational structures. The motivating idea behind involving multiple organizations is the increase in security due to human factors. More specifically, the requirement that distinct people in different organizations sign off on a change or an update makes a cyberattack much less likely due to the inherent requirement that both organizations be penetrated and fooled. GridTrust focuses on the software update process as the primary exemplar for the research and development work. A novel hardware-based technology referred to as a Physical Unclonable Function (PUF) provides a microchip Root-of-Trust (RoT), i.e., a starting point for verifying that the hardware being communicated with is the hardware the control center believes the hardware to be. As a result, staff at power grid control centers can ensure the accurate and reliable identification of hardware devices from the outset. The GridTrust protocol introduces two key innovations, as detailed in this report. Firstly, the utilization of a PUF as a root-of-trust in the initial phase of a software or firmware update. Secondly, the application of multiple cryptographic signatures from two or more organizations to the update binary. These signatures are verified before implementing the update on a power grid device in the field. In terms of GridTrust hardware design, this report outlines two main components. The first is the GridTrust Native Device, integrating PUF technology intrinsically into the hardware device itself. The second is the GridTrust Interfacing Device, which incorporates PUF technology and multiple cryptographic signatures. These signatures are cross-checked within a separate hardware positioned between the power grid control center and the legacy power grid device, functioning as an intermediary. While the GridTrust Interfacing Device offers the advantage of being applicable to existing power grid equipment, it may have reduced security if the intermediary component is targeted. On the other hand, the GridTrust Native Device boasts increased security due to protocol integration within a unified form factor. The effectiveness of GridTrust technology has been extensively demonstrated, with multiple external red-team attackers unable to breach GridTrust's security measures. This was observed both in controlled laboratory settings during Phase 1 of the project and in real-world conditions within a City of Marietta substation during Phase 2 of the project.

24 POWER TRANSMISSION AND DISTRIBUTION↗

G-PST Inertia Monitoring Tool [SWR-23-54]

This tool provides interfaces for ingesting real-time unit commitment data (e.g., from a grid operator's control room energy management system) and calculating system inertia estimates based on the H-constant method, before relaying those estimates to customizable visualization or logging outputs.

Stephen, Gordon↗

Data distribution service-based interoperability framework for smart grid testbed infrastructure

This study presents the design and implementation of a communication and control infrastructure for smart grid operation. The proposed infrastructure enhances the reliability of the measurements and control network. The advantages of utilizing the data-centric over message-centric communication approach are discussed in the context of smart grid applications. The data distribution service (DDS) is used to implement a data-centric common data bus for the smart grid. This common data bus improves the communication reliability, enabling distributed control and smart load management. These enhancements are achieved by avoiding a single point of failure while enabling peer-to-peer communication and an automatic discovery feature for dynamic participating nodes. The infrastructure and ideas presented in this paper were implemented and tested on the smart grid testbed. A toolbox and application programing interface for the testbed infrastructure are developed in order to facilitate interoperability and remote access to the testbed. This interface allows control, monitoring, and performing of experiments remotely. Furthermore, it could be used to integrate multidisciplinary testbeds to study complex cyber-physical systems (CPS).

97 MATHEMATICS AND COMPUTING↗

Algorithm and code development for unsteady three-dimensional Navier-Stokes equations

In the last two decades, there have been extensive developments in computational aerodynamics, which constitutes a major part of the general area of computational fluid dynamics. Such developments are essential to advance the understanding of the physics of complex flows, to complement expensive wind-tunnel tests, and to reduce the overall design cost of an aircraft, particularly in the area of aeroelasticity. Aeroelasticity plays an important role in the design and development of aircraft, particularly modern aircraft, which tend to be more flexible. Several phenomena that can be dangerous and limit the performance of an aircraft occur because of the interaction of the flow with flexible components. For example, an aircraft with highly swept wings may experience vortex-induced aeroelastic oscillations. Also, undesirable aeroelastic phenomena due to the presence and movement of shock waves occur in the transonic range. Aeroelastically critical phenomena, such as a low transonic flutter speed, have been known to occur through limited wind-tunnel tests and flight tests. Aeroelastic tests require extensive cost and risk. An aeroelastic wind-tunnel experiment is an order of magnitude more expensive than a parallel experiment involving only aerodynamics. By complementing the wind-tunnel experiments with numerical simulations the overall cost of the development of aircraft can be considerably reduced. In order to accurately compute aeroelastic phenomenon it is necessary to solve the unsteady Euler/Navier-Stokes equations simultaneously with the structural equations of motion. These equations accurately describe the flow phenomena for aeroelastic applications. At Ames a code, ENSAERO, is being developed for computing the unsteady aerodynamics and aeroelasticity of aircraft and it solves the Euler/Navier-Stokes equations. The purpose of this contract is to continue the algorithm enhancements of ENSAERO and to apply the code to complicated geometries. During the last year, the geometric capability of the code was extended to simulate transonic flows, a wing with oscillating control surface. Single-grid and zonal approaches were tested. For the zonal approach, a new interpolation technique was introduced. The key development of the algorithm was an interface treatment between moving zones for a control surface using the virtual-zone concept. The work performed during the period, 1 Apr. 1992 through 31 Mar. 1993 is summarized. Additional details on the various aspects of the study are given in the Appendices.

Obayashi, Shigeru↗

Secure Communications Concept and API Concept for Integrating XENDEE Positronix with TESLA PowerPack System at Site 300 (Final Deliverable)

The CleanStart DERMS project focuses on the management of Distributed Energy Resources (DER) for enhanced distribution grid resilience. The demonstration site has changed from Riverside Public Utility to the LLNS Site 300 DERS demonstration site. This project has so far focused only on device level controllers and local area controllers. These controllers potentially lack the ability to perform supervisory control and grid interactive control functions, essential for grid-level optimal DER management. This project seeks to close that gap in development of secure communication concept and appropriate Application Programming Interfaces (API) to enable integration with DERs, device level and local area controllers, such as Distributed Energy Resources Management System (DERMS).

24 POWER TRANSMISSION AND DISTRIBUTION↗