Fault Contribution of Grid-Following and Grid-Forming Inverters Considering Generic Inverter Controls and Ride-through Requirements

Gradual transformation of the synchronous generator (SG)-dominated power systems to inverter-based resource (IBR)-dominated power systems is bringing new challenges regarding power system protection. Increasing IBR’s penetration will reduce the reliability of protection coordination, originally developed for SG-dominated power systems, potentially leading to less accurate calculation or even mis-operation. Thus, new protection schemes compatible with IBR-dominated power systems should be established. Prior to establishing the protection schemes, research on the fault contribution of generic IBR models should be conducted considering interconnection requirements. This paper conducts fault current contribution analysis of generic grid-following (GFL) and grid-forming (GFM) inverters considering interconnection requirements using an electromagnetic transient (EMT) simulation tool. To do this, EMT-based generic GFL models have been developed with the ride-through requirements from IEEE-1547 standards. In addition, the major functions of the generic models are explained. Then, the fault current analysis was conducted using GFL and GFM inverters in a single-inverter-infinite-bus system and a modified IEEE 34-node system considering different grid, fault, inverter control parameters.

Kim, Jinho [BATTELLE (PACIFIC NW LAB)]↗

Testbed Demonstration of a Microgrid Building Block Prototype

With the adoption of ambitious climate action goals, the penetration level of distributed energy resources (DERs) is rapidly increasing. Microgrids are an efficient way to integrate these DERs, facilitating their operation and control. Additionally, microgrids enhance the overall resilience of the distribution system by serving critical loads both within and outside their boundaries. However, the need for substantial customized engineering leads to a high cost of development, installation and maintenance of microgrids. To address this challenge, Microgrid Building Blocks (MBB) are proposed to reduce the deployment cost of microgrids through modular, standardized design and implementation. This work presents a testbed demonstrating the integrated power conversion, control, and communication functionalities of an MBB. The testbed is formed by a real-time electromagnetic transient (EMT) simulation combined with a hardware and software prototype of MBB. The use cases supported by the MBB testbed are enumerated. The islanded operation, voltage regulation, and optimal dispatch capabilities of an MBB-based microgrid controller are validated through a case study.

Somda, Baza [Virginia Tech]↗

Resilient Inverter-Driven Black Start with Collective Parallel Grid-Forming Operation

As modern power systems are experiencing exceptional changes with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has received attention. Using local grid-forming (GFM) assets near consumers, engineered to establish grid voltages in the absence of a stiff grid, i.e., bottom-up restoration, a distribution system could obtain high system resilience by not relying on the bulk power system restoration, which requires significant human intervention and procedure. This paper studies the technical feasibility of the novel approach with detailed electromagnetic transient (EMT) simulations. To thoroughly evaluate the potential of GFM inverters and the technical challenges in IBR-driven black start, a detailed three-phase inverter model is developed, including negative-sequence control for voltage balance and a phase-by- phase current limiter to sustain momentary overloading during the black start. To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics to emulate their inrush and startup behaviors as well as network dynamics. In addition, active involvement of grid- following distributed energy resources is also studied to facilitate the black-start process. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, we demonstrate that a system can achieve high resilience even with a fraction of assets lost. Two test cases of inverter-driven black start, using two and one GFM inverters, respectively, for a heavily unbalanced 2-MVA distribution feeder are demonstrated. Takeaways for further study and field deployment are provided.

grid-forming inverter↗

Interactive Power to Frequency Dynamics Between Grid-Forming Inverters and Synchronous Generators in Power Electronics-Dominated Power Systems

With increased attention on grid-forming inverters as a power system stabilizing device during high shares of inverter-based resource operations, there is a present need for a transparent and methodical investigation of the inverted and direct power to frequency control capabilities and impacts of these devices on emerging power systems. Here, analysis of the frequency dynamics of the droop-controlled grid-forming inverter and the synchronous generator illuminates the inverted active power-frequency relationship and the frequency response order reduction, forming the basis for novel, nonlinear frequency control approaches. Device-level electromagnetic transient domain simulations corroborate the order-reduction findings, establish that a properly designed dc-side system has a negligible impact on power transfer and will not impede frequency regulation, and confirm the primary frequency response improvement with nonlinear control. Simulations of the 9- and 39-bus test systems validate the order reduction and associated decoupling of the nadir and rate of change of frequency in larger networks. Oscillatory mode analysis confirms the grid-forming benefit of increased damping; decreased damping is observed at shares above 80%, but not at 100%. Finally, simulations on a validated Maui power system model with a 96% of inverter-based resources model yield a trend toward a first-order response.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Hardware Demonstration of Weak Grid Oscillations in Grid-Following Converters

The increasing penetration of inverter-based resources (IBRs) introduces some unexpected dynamic issues, including low-frequency oscillations. In this paper, a laboratory-scale grid-following voltage-source converter (VSC) system is implemented to demonstrate weak grid oscillations. Grid-following control is applied in VSC to provide active power, reactive power or ac voltage control. The test bed is also replicated in electromagnetic transient (EMT) simulation environment (MAT-LAB/SimPowerSystems) for benchmark purpose. Case studies are carried out to demonstrate low-frequency oscillations under real power/ac voltage or real power/reactive power control. The excellent agreement between the simulation and experimental results ensures that the two test beds are exchangeable and can be used for testing oscillation mitigation strategies in future research.

Bao, Li↗

Linear Solvers for Collector Systems of Generalized Large-scale Inverter-Based Resources

Collector systems for inverter-based resources (IBRs) are typically represented by equivalent circuits for electromagnetic transient (EMT) simulations. Recent studies have revealed that modeling a detailed collector system is essential to accurately represent the behavior of IBRs, especially when dealing with partial tripping during external disturbances. However, there are several challenges in simulating a detailed EMT model of a collector system due to the time required to simulate such systems. Thus, this paper investigates the modeling of a detailed collector system, taking into account its configuration and components as defined in IEEE standard 2800. The configurations include the collector systems of generalized large-scale IBR plants. The components include the main IBR transformer, collector bus, and feeders with lines and/or cables. The EMT model of the collector system is represented by differential algebraic equations (DAEs) that are discretized to form linear equations that are solved using linear solvers. In this paper, linear solvers are proposed based on the Schur complement method, which are utilized for simulation of the EMT model of collector systems of generalized large-scale IBRs to accelerate simulation speed while maintaining the accuracy of the results. The proposed solvers are verified by comparing the performance to that of linear solvers provided in MATLAB.

Choi, Jongchan↗

Optimal Droop Setting for Congestion Reduction in a 100% Grid-Forming Inverter-based Power System

he high penetration of inverter-based resources (IBRs) introduces new challenges to power systems due to the complex inverter control. However, IBRs can be configured to maximize their benefits to improve system resilience and reliability. This paper proposes a steady-state optimization model that aims to mitigate transmission congestion in a 100% grid- forming (GFM) IBR-based power system. This goal is achieved by determining the optimal droop settings for the GFM IBRs under different congestion conditions due to renewable energy and load variations. The numerical solution is rigorously verified by a high-fidelity model of the IEEE 39-bus test system with detailed GFM IBR control in the time-domain electromagnetic transient (EMT) simulation tool PSCAD. The numerical solution and simulation results show a significant congestion reduction while meeting all other operating requirements. It is also observed that the numerical solving time is substantially less compared to the EMT simulation time.

Nguyen, Quan H.↗

Reinforcement Learning-Based Approach for EMT Automation of Large-Scale PV Plants

In the pursuit of efficient and precise modeling of large-scale power systems, particularly utility-scale photovoltaic (PV) plants, Electromagnetic Transient (EMT) simulations play a crucial role. As utility-scale PV plants increase in size and complexity, traditional computational methods become inadequate, necessitating more advanced techniques. This paper highlights the progressive efforts made to accelerate EMT simulations. A novel continuous reinforcement learning (RL) strategy is explored to automate the differentiation and categorization of stiff and non-stiff differential algebraic equations (DAEs). The use of stiff and non-stiff integration methods applied to relevant parts of the DAEs assists with the speed-up of the simulations. The paper details the data acquisition, development and offline training of the RL model, leading to its validation that demonstrates a high precision in optimizing simulation methods. The proposed RL promises to significantly enhance the efficacy of EMT simulations, offering a robust framework for the future of power system analysis.

Xia, Qianxue↗

Assessing the Feasibility of Bordered Block Diagonal Reordering in Power System Matrices using Fully Convolutional Network

In electromagnetic transient (EMT) simulations for power systems and inverter-based resources (IBRs), the arrangement of states within the system's linear equations, represented by matrix A in Ax=b, is critical. The state ordering in matrix A can highlight distinct characteristics of the system's graph, and identifying an optimal state ordering is crucial for efficient computation. The choice of state ordering, however, is dependent on the solver used, as each solver may perform optimally with different matrix patterns. With a wide array of matrix reordering algorithms available, selecting the most suitable one becomes challenging without insights into the matrix's ideal configuration. To address this, the paper proposes a fully convolutional network (FCN) to evaluate the reordering potential of the A matrix into a bordered block diagonal (BBD) pattern, which is commonly observed in power system and IBR modeling. The FCN's assessment aims to streamline the solver's operation, which in turn could substantially reduce the computational time required to find a solution.

Xia, Qianxue↗

Transient Stability Analysis of Direct Droop-Controlled Grid-Forming Inverter with Current Clipping as Current Limiting Control

This paper investigates the transient stability of the direct droop-controlled grid-forming (GFM) inverter which employs the current clipping-based approach for overcurrent limitation. An equivalent circuit model of the direct-droop GFM inverter with current clipping is developed for this purpose. It is shown that during overcurrent conditions, the GFM inverter with current clipping acts as a voltage source with a virtual resistance behind the inverter filters. To compute the parameters of this virtual resistance an analytical expression is given in the paper. Then utilizing the developed circuit, a criteria to exit current limiting during post-fault conditions is given. The developed analytical approaches are then validated through electromagnetic transient (EMT) simulation results in PSCAD software and finally concluding remarks are drawn.

Mohiuddin, Sheik Mohammad↗

Black Start of Unbalanced Microgrids Harmonizing Single- and Three-Phase Grid-Forming Inverters

As power systems are transforming with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has drawn attention. Using distributed grid-forming (GFM) assets located near critical loads, either three-phase or single-phase, to establish microgrid voltages in the absence of a bulk grid, a distribution system could obtain high system survivability. For swift and secure recovery of a critical load in a single-phase lateral, local single-phase GFM inverters can form a microgrid, and then it can be combined with a neighbouring grid with the inverters remaining in GFM mode for voltage and frequency regulation until the bulk grid comes online. It leads to dynamic interoperation of single-phase GFM inverters with three-phase ones in the black start process. This paper studies the novel approach with electromagnetic transient (EMT) simulations. To evaluate the potential and the technical challenges of the heterogeneous IBR-driven black start, three-phase and single-phase GFM inverter models are developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter (three-phase) and current magnitude limiter (single-phase). To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics emulating their inrush and startup behavior as well as network dynamics. Involvement of grid-following assets to facilitate the black-start process is also modeled. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, regardless of phases, a system can achieve extreme resilience. An inverter-driven black start of a heavily unbalanced 2-MVA distribution feeder using 1 three-phase and 3 single-phase GFM inverters is demonstrated. The simulation shows the heterogeneous system can maintain stability with the single-phase GFM dynamics coupled with the three-phase one.

grid-forming inverter↗

The Cause of Insufficient Damping in Phase-Locked-Loop and Its Influence

Phase-locked loop (PLL) is a critical component that synchronizes grid-following (GFL) inverter-based resources (IBR) to the grid. Insufficient damping in PLL has been identified as a cause associated with real-world weak grid stability issues. This paper reveals that the second-order low-pass filter deployed in a sophisticated PLL structure can have negative influence on damping performance and lead to system instability when the grid is weak and power generation is low. Improving the PLL damping is illustrated as one of the mitigation approaches. The dynamic study is carried out in electromagnetic transient (EMT) simulation environment. In addition to EMT demonstration, a simplified analytical model of PLL is developed to represent a PLL with the sophisticated structure. The resulting overall analytical model of the entire system is then used for eigenvalue- based analysis to illustrate the influence of PLL on dynamic modes.

Wang, Zhengyu↗

Provably-Stable Overload Ride-Through Control for Grid-Forming Inverters Using System-Wide Lyapunov Function Analysis

A key challenge associated with a grid-forming (GFM) inverter based resource (IBR) is its behavior during severe grid disturbances: since a GFM inverter regulates voltage in the fast timescale instead of current or power, it may experience a transient overload of current, power and/or energy during a severe grid disturbance. While many promising control strategies for overload ride-through have been proposed over the past two decades, transient stability of the system during and after the transition to an overload ride-through control mode remains difficult to guarantee. In this work, a novel overload ride-through control strategy is proposed for a system of grid-forming inverters that takes both self-protection and system-wide transient stability into account. A proposed system-level supervisory control uses slow communication to pre-emptively assign a set of local ride through control parameters to individual GFM IBR, including a current-limiting virtual reactance, that guarantees that synchronism is still preserved for any set of anticipated grid disturbances. At the core of the supervisory control lies a Lyapunov-function-based routine capable of establishing a strong, albeit conservative, transient stability guarantee for the system. Here, the proposed overload ride-through control strategy is validated via numerical integration of a reduced-order model, as well as through detailed electromagnetic transient (EMT) simulation.

30 DIRECT ENERGY CONVERSION↗

Large Angle Deviation in Grid-Following IBRs Upon Grid Voltage Dip

In the 2021 Texas Odessa large-scale solar PV tripping events, phase-locked-loop (PLL) loss of synchronism is identified as a major cause of solar PV tripping. When solar PVs detected a large phase angle deviation (e.g., 10 degrees), tripping commands were initiated. Here, the large phase angle deviation was triggered by a transmission line fault 200 miles away, which in turn led to approximately 30% voltage drop in the 345-kV system. This paper offers a plausible reason why grid-following inverter-based resources (IBRs) may experience a large angle deviation upon grid voltage dip. Critical operating conditions contributing to such phenomena are identified via analysis and their effects are demonstrated using electromagnetic transient (EMT) simulation. Furthermore, the effect of converter control, e.g., grid-following control vs. grid-forming control, is examined. It is found from EMT simulation results that frequency and voltage control are helpful in mitigating angle deviation. Furthermore, linear block diagrams are derived to examine why frequency control can effectively suppress large angle deviation.

14 SOLAR ENERGY↗

A Two-Stage Current Limiting Control Strategy for Direct-Droop-Controlled Grid-Forming Inverters

This paper presents a two-stage current limiting control strategy with fault ride-through capability for the direct-droop-controlled grid-forming (GFM) inverters. The proposed approach comprises Stage 1 and Stage 2 current limiting controls. During faults, Stage 1 current limiting control instantly clamps the inverter output current magnitude to its maximum transient limit by blocking the switching pulses to the insulated-gate bipolar transistors (IGBTs) with the help of a hysteresis loop control, and Stage 2 current limiting control limits the inverter output current magnitude to its steady-state limit by regulating the amplitude and frequency of the modulating waveform utilizing the active and reactive current limiting control loops. By implementing the current limiting actions in two stages, this approach can effectively limit the over-current within a few cycles after the fault occurrence and ensure synchronism to the grid after long-term fault events. The efficacy of the proposed control approach is validated through electromagnetic transient (EMT) simulation results conducted on a single GFM inverter-based test system and the IEEE 39-bus test system with multiple GFM inverters in the PSCAD platform.

Mohiuddin, Sheik Mohammad↗

Virtual Dynamic Grid Impedance and Its Impacts on Harmonics and Stability of Inverter Based Resources Plant

Nowadays, a large number of inverter-based resources (IBRs) are integrated into the grid at a single connection point as an IBR plant. In this article, a virtual dynamic grid impedance concept is introduced to evaluate the harmonics and stability for grid integration of an IBR plant containing multiple IBRs. First, a detailed theoretical study is conducted to build a foundation of the virtual grid impedance concept, which is a dynamic impedance that changes with the number of IBRs added into an IBR plant. Then, based on the new virtual dynamic grid impedance concept, frequency spectrum analysis is performed to explore harmonic impact at the interconnection point for an IBR plant with IBRs having L, LC, and LCL filters, respectively. An electromagnetic transient (EMT) simulation model of a grid-connected IBR plant is developed to explore the harmonics and stability of the IBR plant connected to the grid as well as the reliable operation of IBRs within the plant from the novel virtual equivalent dynamic grid impedance point of view. Hardware experiments are conducted to validate the EMT simulation evaluation. The results show that the number of IBRs added into an IBR plant influences the grid impedance, i.e., grid strength, and the grid impedance variation has multiple impacts on the IBR plant and IBRs within the plant depending on the grid-connected filters of the IBRs.

grid impedance↗

Wideband Impedance Passivation of MMCs for Suppressing Harmonic Oscillations

Harmonic instability and associated oscillation events have become one of the main concerns in MMC-based HVdc systems. These oscillations can appear in the range from a few hundred hertz to several kilohertz, and the root cause is identified as delay-induced negative damping of MMC impedance appearing at the system resonance frequency. Here, this paper introduces a wideband impedance reshaping method through MMC control to eliminate such negative damping for both grid-following (GFL) and grid-forming (GFM) MMCs, which makes the MMC impedance completely passive from the second harmonic frequency upward, thus preventing all harmonic oscillations. First, simplified impedance models of MMCs are derived for the harmonic stability analysis and the impedance reshaping control design. Next, a passivity-based impedance reshaping method is presented, as well as practical considerations for its implementation. In addition, to maintain the MMC's disturbance ride-through capability, an adaptive activation scheme is developed, which enables the wideband impedance reshaping control only in the presence of harmonic oscillation events. The effectiveness of the proposed method is validated by frequency domain analysis and by electromagnetic transient (EMT) simulations of two typical MMC-based power systems.

17 WIND ENERGY↗

Oscillation Risks of Grid-Following and Grid-Forming Inverter-Based Resources in Series-Compensated Networks

Here, this paper investigates the dynamic behavior of a grid-connected inverter-based resource (IBR) when connected radially to a series compensated line. Potential interactions between the series compensation and the IBR have been identified for both types: grid-following (GFL) or grid-forming (GFM). The study begins with electromagnetic transient (EMT) simulations to demonstrate stability issues. Subsequently, nonlinear analytical models are formulated in the dq frame, validated against the EMT simulation, and leveraged to assess eigenvalues and participation factors. Influencing factors of the dominant oscillation modes have been identified. The analysis results show that series compensation may make a mode associated with the synchronization unit unstable. Furthermore, customized feedback systems are built for the synchronizing loop. Series compensation can increase the sensitivity of the voltage phase angle towards the synchronizing angle, and introduce phase lag in the real power response towards the synchronizing angle. These factors may cause interactions with the phase-locked loop in GFL-IBR systems and with power-based synchronization in GFM-IBR systems, potentially leading to instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗