A High-Fidelity Electromagnetic Transient Model of Inverter-based Resources Integrated to an IEEE-9 Bus System for Benchmarking Studies

An inverter-based resource (IBR) is a source of electricity that is asynchronously connected to the electrical grid via an electronic power converter. These power sources lack the intrinsic behaviors of the standard power plants, presenting specific challenges to system stability. These power sources lack the intrinsic behaviors of the standards power plants and their features are almost entirely defined by the control strategy used on them, presenting specific challenges to system stability as their penetration increases into the already fragile Bulk Power System (BPS). Utilizing renewable energy has a great upside but the electrical industry needs to understand the requirements like performing electromagnetic transient (EMT) simulation studies in planning and/or in interconnection studies. This paper presents the development of a high-fidelity EMT model based on commercial equipment and field parameters, which at the same time aims to study the increasing penetration of IBRs and their impact on the actual BPS. The open-source EMT model developed will be a benchmarking example that can be used to evaluate algorithms in the power grid (including evaluating grid-forming controls, power system monitoring and operation, etc.).

Martinez Montejano, Misael↗

Leveraging National Laboratory Assets to Address Stability Challenges due to Declining Grid Inertia Using Geographically Distributed Electrical–Thermal Co-Emulation

Due to increased penetration of low-inertia resources into the electric grid, challenges are increasing for maintaining wide-area system stability. Grid stability assessment requires a faithful representation of the multiple-physics interaction at the system level, and timescales of interaction varying in orders of magnitude, from microseconds to seconds to several minutes. Along with the simulation-based techniques, hardware-in-the-loop (HIL), controller HIL, and power HIL techniques have been developed to better understand the emergent behavior of the system with emerging technologies. US National Laboratories have played a vital role in research and development to understand the behavior of individual technologies and devices integrated to the electric grid. Each national laboratory forwards a technological and strategic initiative tied core and enabling capabilities. Due to strategic, efficiency, and economic reasons, not all the labs have assets to conduct research on all technologies concomitantly, so it becomes crucial to integrate the labs across geographies to understand the interplay of different technologies together at the system level. This approach avoids duplication of the assets at different lab facilities and helps understand the integrated system behavior of various technologies representative of actual grid conditions by connecting multiple national labs. This article talks about techniques of connecting three national laboratories to enable co-emulation of electrical–mechanical–thermal characteristics of devices and systems. Such an approach can be used to understand the dynamic and transient interaction of multi-physics in a system level, at-scale emulation using real-time simulation tools and techniques.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Robust Yule-Walker Method for Online Monitoring of Power System Electromechanical Modes of Oscillation

Reliable power system operation requires that system operators maintain a satisfactory small-signal stability margin at all times. Mode meters allow system operators to continuously monitor the stability margin by analyzing synchrophasor measurements. Experience with mode meters at the Bonneville Power Administration (BPA) has revealed that mode meters sometimes suffer severe bias following transient disturbances. In this paper, a robust version of the Yule-Walker mode meter algorithm is proposed to mitigate this bias. The robust capability is introduced by modifying the estimator of the autocovariance sequence (ACS) on which the algorithm depends. Tests with field-measured data demonstrate that the robust Yule-Walker (RYW) algorithm significantly outperforms its conventional counterpart and is better able to provide system operators with accurate information about the system's stability margin.

Follum, James D.↗

Performance Analysis and Simulaion of the Hydraulic Scram System in TREAT Reactor

The Transient Reactor Test Facility (TREAT) at Idaho National Laboratory (INL) serves a vital role in nuclear fuel safety research, enabling transient experiments that simulate reactivity excursions and accident scenarios. Central to these operations is the transient control rod drive system (TCRDS), which drives rapid motion of the transient control rods such that TREAT can simulate rapid power changes typical of reactor accidents. The reliability and performance of this system are critical for protecting both fuel specimens and reactor infrastructure. This study presents the initial phase of a two-year investigation into the dynamics and reliability of the TREAT hydraulic TCRDS. Conducted in collaboration with INL, the research employs a combined computational and experimental approach to analyze the system's response time, pressure transients, and potential failure modes. Emphasis is placed on understanding how fluid characteristics influence the TCRDS’s ability to achieve both rapid power changes and mechanical stability. The TRDS and the skid that powers it will be analyzed throughout this investigation. Computational modeling using computational fluid dynamics (CFD) will simulate the hydraulic response under varying conditions. In parallel, experimental testing planned at INL will validate these models and capture key performance metrics. This paper outlines the system design, analytical framework, and modeling strategies that form the foundation for later testing. Ultimately, this work aims to support improvements to the TCRDS’s design and reliability, contributing to the broader goal of enhancing nuclear fuel safety and sustaining TREAT’s mission as a premier nuclear fuel test facility.

21 - SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLAN↗

The Monolithic Heat Pipe Microreactor Reference Plant Model

This work introduces a reference plant model for a generic monolithic heat-pipe-cooled microreactor. The model will serve as a springboard to develop future evaluation models in the licensing process of similar microreactor designs at the U.S. Nuclear Regulatory Commission. This model has been developed with the Comprehensive Reactor Analysis Bundle and its specifications are based on open literature publications for the eVinci TM design. BlueCRAB is the U.S. Nu- clear Regulatory Commission non-light-water reactor analysis system based on the Multiphysics Object-Oriented Simulation Environment framework, which can couple the Griffin, BISON, and Sockeye applications to resolve the various physics that are essential for the safety analysis of this type of reactor system. The core specifications includes tristructural isotropic fuel, graphite monolith, graphite reflectors, and drums composed of graphite and B 4 C. No moderator or burnable poison pins are used in the design. The fuel enrichment is reduced to control excess reactivity in the core. This core design is not optimized and only serves for testing purposes, since the primary objective of this work is to exercise the multiphysics coupling for this type of reactor system. A three dimensional (3D) core heterogeneous Griffin discrete ordinates (SN) transport model allows the precise calculation of the flux distribution and pin powers. Griffin transfers the power density distribution and obtains a temperature distribution to and from BISON. The BISON model com- putes the 3D core temperature distribution and is coupled to 876 Sockeye subapplications running a heat pipe model. This 3D conduction model is coupled to the various heat pipes via heat flux boundary conditions. The model includes a small gap between the heat pipe and the monolith. Convective heat transfer boundaries with either ambient temperature or condenser temperature as heat sinks are imposed at the model boundaries. The 2D Sockeye heat pipe model uses a vapor- only methodology, which provides the needed resolution for transient calculations and allows the determination of various heat pipe limits. This approach is superior to the superconductor model traditionally used in steady-state calculations. BlueCRAB computes steady-state power and temperature distributions that serve as the initial condition for a loss-of-heat-sink transient simulation. The steady-state results show significant peaking due to the position of the control drum, but this is a characteristic of the particular design used, which is not optimized at this stage. The transient results show the reactor power slowly stabilizing towards a 3% power level after the partial loss of secondary heat removal. Several recriticalities are observed due to cooling through the secondary system but the reactor is self-stabilizing and behaves as expected.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Developing a PSCAD Model of the Reduced 240-Bus WECC Test System: Preprint

Fast-acting controls of inverter-based resources (IBR) introduce unprecedented dynamics to bulk power systems and island power grids, especially the high-frequency dynamics ranging from $>5$ Hz to hundreds of Hz. These oscillatory stability problems cannot be captured by the phasor domain simulations, e.g., in PSS/E, Powerworld and TSAT, due to insufficient modeling. Instead, they should be studied by electromagnetic transient (EMT) simulations by using proper EMT dynamic models. This paper develops and validates the PSCAD model of the reduced 240-bus Western Electricity Coordinating Council (WECC) test system. The PSCAD model will be released to the public, which can be used by both academia and power industry practitioners for studying the fast dynamic problems without any Critical Energy/Electric Infrastructure Information (CEII).

240-bus WECC test system↗

Introduction to Grid Forming Inverters: A Key to Transforming our Power Grid [Slides]

A grid-forming (GFM) inverter-based resource (IBR) controls maintain an internal voltage phasor that is constant or nearly constant in the sub-transient to transient time frame. This definition means that the GFM IBR will nearly immediately respond to changes in the external system and attempt to maintain IBR control during challenging network conditions to maintain grid stability. In GFM IBR, the voltage phasor is controlled to maintain synchronism with other devices in the grid while regulating the active and reactive power appropriately to support the grid. This contrasts with conventional GFL IBR controls wherein immediately after a disturbance (0-5 cycles), within the normal operating range of voltage, the output current phasor magnitude and angle remain unchanged, and the current phasor begins changing only within the transient time frame (tens of cycles) to strictly control the active and reactive power being injected into the network. This presentation gives an introduction to GFM IBR and presents the current state of the art in this area.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Advanced grid-forming (GFM) inverter controls, modeling and system impact study for inverter dominated grids

Our main goals in this project are to understand: 1) the stability of the power system with very high penetration of PV or other inverter-based resources (IBR), 2) the interactions among IBRs and traditional generators, and 3) the impact of the GFM inverters on bulk power system. To achieve these goals, we took a holistic research and development approach. First, an impedance-based large system modeling and stability analysis tool was developed to aid the large IBR system small-signal stability analysis. Second, consensus-based control and transient overload ride through were developed to control and coordinate multiple GFM inverters in a large system to maintain transient stability during big grid events. Third, high fidelity electromagnetic transient (EMT) IBR models were developed and integrated into a large reduced WECC model to study the system impact from IBRs. Lastly, extensive validation tests of the GFM control which was developed in this project and implemented in two 1MW commercial solar inverters were performed using different validation platforms, e.g., control hardware-in-the-loop (CHIL) platform, power hardware- in-the-loop (PHIL) platform, and a real PV plant.

14 SOLAR ENERGY↗

Critical values of cyber parameters in a dynamic microgrid system

An islanded microgrid can be used to serve critcal load as a resiliency source when a severe outage occurs. In an islanded mode, control of a microgrid relies on the communication system significantly. Hence, microgrids are cyberphysical systems and, therefore, the cyber system plays a crucial role in the performance of the cyber-power system. A microgrid control scheme is proposed for power dispatch and regulation based on the droop and proportional-integral (PI) feedback control. The proposed control strategy is validated for transient stability following dynamic events. To evaluate the impact of a networked control system on control performance, a cyber model is developed to represent data acquisition periods and communication delays. An analytical method is proposed to determine the critical values for the data reporting periods and communication delays. The analytical method based on a state space model of a networked control system is applicable for large-scale systems. A 2-dimensional stability region of a microgrid in the space of cyber parameters can be obtained by the proposed method, and the critical values of cyber parameters are determined based on the stability region. Simulation results validate that the design of a microgrid as a cyber-physical system needs to be guided by critical values for the data reporting period and communication delay to prevent system instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Sparse Control Synthesis for Uncertain Responsive Loads With Stochastic Stability Guarantees

In this report, recent studies have demonstrated the potential of flexible loads in providing frequency response services, predominantly due to their availability and cost-effectiveness. However, uncertainty and variability in various weather-related and end-use behavioral factors often impact the reliability of demand-side control performance. This work addresses this problem with the design of a demand-side control to achieve frequency response under load uncertainties. Our approach involves modeling the load uncertainties via stochastic processes that appear as both multiplicative and additive in the power system dynamics. Recently developed mean square exponential stability (MSES) results for continuous-time linear stochastic systems are applied to pose the control synthesis problem which results in an LMI-based optimization problem. Additional costs and constraints are added to the LMI-based controller synthesis to ensure MSES, improve closed-loop transient performance, maximize tolerable uncertainties, and promote sparsity in the controller. Additionally, the fundamental limitations between the tolerable uncertainties and control efforts while ensuring MSES are discussed. Further, the control synthesis problem for the case of the full-state measurement is generalized to the case of partial-state measurements. The proposed control synthesis is illustrated on an IEEE 39 bus system with rigorous studies to demonstrate the role of sparsity, closed-loop transient performance, tolerable uncertainties, and control efforts while ensuring MSES and achieving frequency response.

42 ENGINEERING↗

Power HIL Validation of a MW-Scale Grid-Forming Inverter's Stabilization of Otherwise Unstable Cases of the Maui Transmission System

This presentation summarizes MW-scale power hardware-in-the-loop experiments using a 2.2 MW grid-forming inverter connected to a real-time electromagnetic transient simulation of the Maui transmission system. The hardware inverter used is a commercially available "off-the-shelf" inverter from a major manufacturer that is capable of operating in grid-forming mode or grid-following mode. The hardware inverter was connected via power hardware-in-the-loop to a real-time model of the year-2023 Maui power system, which consists of a networked transmission system with diverse generation sources. The results of the simulations indicate that with sufficient synchronous machines online, the system is stable without grid-forming inverters, but that as the amount of synchronous machines is reduced, the system becomes unstable. Changing the hardware inverter (scaled up to represent a 30 MW plant) into grid-forming mode mitigates the instability in various low-inertia cases, including a zero-inertia scenario with 100% of generation from PV and wind. This result broadly agrees with pure simulation results.

battery energy storage system↗

High-fidelity multiphysics load following and accidental transient modeling of microreactors using NEAMS tools: Application of NEAMS codes to perform multiphysics modeling analyses of micro-reactor concepts

The feasibility of modeling microreactors using high-fidelity models with the Nuclear Energy Advanced Modeling and Simulation (NEAMS) tools is investigated in this report. Three overarching questions guided this research: can NEAMS tools readily be applied for high-fidelity multiphysics modeling of different types of transients in microreactor designs; how accurate are the results obtained; and are improvements needed in accuracy or user experience of NEAMS tools, especially considering newly developed capabilities? This work builds upon FY-2022 work, and two microreactor concepts considering heat pipe (HP-MR) and gas-cooled (GC-MR) technologies were further analyzed using high-fidelity multiphysics simulations. The NEAMS tools considered and coupled within the MultiApp environment are Griffin for neutronics, BISON for thermo-mechanics, Sockeye for heat pipe modeling (in HP-MR), SAM for 1D Fluid – 3D solid modeling of coolant channels and system modeling of balance of plant components (in GC-MR), and the SWIFT code for hydrogen redistribution in hydride moderator. The Heat Pipe MicroReactor (HP-MR) concept was further analyzed in FY-2023 to demonstrate the stochastic TRISO failure modeling capability in BISON to check operational limits of the TRISO fuel. A new full-core Gas-Cooled MicroReactor (GC-MR) model was developed based on the initial assembly-model used in Y-2022 and used for steady-state and accidental depressurization transient simulations. Accuracy of the simulations performed was assessed through 1) verification analyses completed on the different physics with code-to-code comparison, and 2) validation of the multiphysics simulations based on modeling of the Kilopower Reactor Using Stirling Technology (KRUSTY) experiment. In FY-2023, the mesh and model of KRUSTY was updated to closely match publicly available data, and the neutronic model was verified and validated against experimental control rod worth measurements. The multiphysics model of KRUSTY was developed and used for steady-state analysis and for modeling reactivity insertion transient. The calculated power increase and stabilization agrees well with experimental data following adjustment in fuel thermal expansion coefficient. As an important component of this project, the ANL team gathered experience with a wide range of NEAMS tools: the MOOSE Mesh System, Griffin, BISON, SWIFT, Sockeye, SAM, Workbench, and the MOOSE MultiApp System, and provided assessment of new capabilities. Noteworthy are the user assessment of the “vapor-only” flow model in Sockeye and development of a multiphysics startup transient in HP-MR unit cell for use as tutorial in Sockeye. The full-core GC-MR model was used for assessment of SAM for balance of plant modeling and for demonstrating the SWIFT code capability for hydrogen redistribution modeling in multiphysics transient analyses. In this process, several bugs/issues were identified and reported to developers. Finally, the assembly GC-MR model developed in FY-2022 coupling Griffin, BISON and SAM through flow blockage and rod ejection transients was published to the National Reactor Innovation Center (NRIC) Virtual Test Bed (VTB). The Heat Pipe MicroReactor (HP-MR) concept high-fidelity multiphysics coupling of Griffin/BISON/Sockeye in load-following and heat pipe failure transients was also published on the VTB. Those submissions are enabling thorough review of these models as well as wide distribution to industry, regulator, and university users. In this analysis, several new research questions were uncovered, and follow-up analyses are recommended to further improve some models, consider additional transients, and continue development of VTB models.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Aggregate data‐driven dynamic modeling of active distribution networks with DERs for voltage stability studies

Abstract Electric distribution networks increasingly host distributed energy resources based on power electronic converter (PEC) toward active distribution networks (ADN). Despite advances in computational capabilities, electromagnetic transient models are limited in scalability because of their reliance on exact data about the distribution system and each of its components. Similarly, the use of the DER_A model, which is intended to examine the combined dynamic behavior of many DERs, is limited by the difficulty in parameterization. There is a need for improved dynamic models of DERs for use in large power system simulations for stability analysis. This paper proposes an aggregate model‐free, data‐driven approach for deriving a dynamic partitioned model (DPM) of ADNs. Detailed residential distribution feeders were first developed, including PEC‐based DERs and composite load models (CMLDs), from which the aggregated DPM was derived. The performance was evaluated through various case studies and validated against the detailed ADN model and state‐of‐the‐art DER_A model with CMLD. The data‐driven DPM achieved a of over 90%, accurately representing the aggregated dynamic behavior of ADNs. Furthermore, the DPM significantly accelerated the simulation process with a computational speedup of 68 times compared to the detailed ADN and a 3.5 times speedup compared to the DER_A CMLD model.

42 ENGINEERING↗

Using Energy Storage-Based Grid Forming Inverters for Operational Reserve in Hybrid Diesel Microgrids

In remote arctic communities, where access to a bulk electrical grid interconnection is not available, the implementation of islanded microgrids has been the most viable way to produce and distribute electricity services to their inhabitants. Historically, these islanded grids have relied primarily on diesel generators or hydropower resources to supply the baseload. However, this practice can result in increased expense due to the high costs associated with fuel transportation and the significant amounts of on-site storage necessary when fuel transportation is unavailable during winter months. In order to mitigate this problem, arctic microgrids have started to transition to a hybrid-source operational mode by incorporating renewable energy sources that are inherently variable in nature, such as wind or solar. Due to their highly stochastic behavior, these hybrid-source islanded microgrids can pose potential issues related to power quality due to introduction of rapid net load fluctuations and inability of diesel generators to respond rapidly. In addition, non-firm stochastic sources can require significant idling diesel generator resources to serve as spinning reserves, which is inefficient and wasteful. This work studies the problems that may arise in the transient dynamics of a real-world hybrid diesel microgrid when subjected to a loss of wind generation. Moreover, this work proposes a transition from a diesel spinning reserve to a battery energy-storage system (BESS) operating reserve scheme. The study of the proposed transition is important in establishing the fundamental implication of transient dynamics and the potential benefits of integrating a BESS as a spinning reserve in terms of stability, frequency nadir, and transient voltage deviation. The methods to investigate and validate the transient dynamics relied on both electromagnetic simulation models of GFMIs and a commercially available GFMI in an experimental power hardware-in-the-loop setup. The simulation results showed that the proposed operating reserve scheme improves the power quality of the system in terms of voltage deviation and frequency nadir when the microgrid is subjected to a loss of wind generation scenario. Depending on the simulation cases, adding a GFMI reduced the frequency nadir between 65.3% and 86.7%. Moreover, the reductions in the voltage deviations improved between 3.6% and 23.0%. From these results it can be concluded that the integration of a GFMI can reduce the frequency nadir in a hybrid diesel microgrid, and in turn, reduce diesel consumption, which improves system reliability while reducing fuel expenses. Furthermore, the novelty of this work relies on the fact that the offline simulation results were validated using a power hardware-in-the-loop platform that incorporated a 100 kVA commercially available GFMI as the device under test.

Hernandez-Alvidrez, Javier↗

Analysis of Grid-Forming Inverter Controls for Grid-Connected and Islanded Microgrid Integration

Autonomous grid-forming (GFM) inverter testbeds with scalable platforms have attracted interest recently. In this study, a self-synchronized universal droop controller (SUDC) was adopted, tested, and scaled in a small network and a test feeder using a real-time simulation tool to operate microgrids without synchronous generators. We presented a novel GFM inverter control adoption to better understand the dynamic behavior of the inverters and their scalability, which can impact the distribution system (DS). This paper provides a steady-state and transient analysis of the GFM power inverter controller via simulation to better understand voltage and frequency stabilization and ensure that the critical electric loads are not affected during a prolonged power outage. The controllers of the GFM inverter are simulated in HYPERSIM to examine voltage and frequency fluctuations. This analysis includes assessing the black start capability for photovoltaic microgrids, both grid-connected and islanded, during transient fault conditions. The high photovoltaic PV penetration levels open exciting opportunities and challenges for the DS. The GFM inverter control demonstrated appropriate response times for synchronization, connection, and disconnection to the grid. The DS has become more resilient and independent of fossil fuels by increasing the penetration of inverter-based distributed energy resources (DERs).

Ward, Laura (ORCID:0000000345501581)↗