Search NASA⌕ Search

SEARCH · Search NASA

Results for “Synchronous machines”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 127 records · Page 7

Recovery Act: Strategies for Voltage Control and Transient Stability Assessment

As wind generation grows, its influence on power system performance will becoming increasingly noticeable. Wind generation differs from traditional forms of generation in numerous ways though, motivating the need to reconsider the usual approaches to power system assessment and performance enhancement. The project has investigated the impact of wind generation on transient stability and voltage control, identifying and addressing issues at three distinct levels of the power system: 1) at the device level, the physical characteristics of wind turbine generators (WTGs) are quite unlike those of synchronous machines, 2) at the wind-farm level, the provision of reactive support is achieved through coordination of numerous dissimilar devices, rather than straightforward generator control, and 3) from a systems perspective, the location of wind-farms on the sub-transmission network, coupled with the variability inherent in their power output, can cause complex voltage control issues. The project has sought to develop a thorough understanding of the dynamic behaviour of type-3 WTGs, and in particular the WECC generic model. The behaviour of such models is governed by interactions between the continuous dynamics of state variables and discrete events associated with limits. It was shown that these interactions can be quite complex, and may lead to switching deadlock that prevents continuation of the trajectory. Switching hysteresis was proposed for eliminating deadlock situations. Various type-3 WTG models include control blocks that duplicate integrators. It was shown that this leads to non-uniqueness in the conditions governing steady-state, and may result in pre- and post-disturbance equilibria not coinciding. It also gives rise to a zero eigenvalue in the linearized WTG model. In order to eliminate the anomalous behaviour revealed through this investigation, WECC has now released a new generic model for type-3 WTGs.

17 WIND ENERGY↗

How a Large-Scale Deployment of Grid-Forming Inverters May Impact Inter-Area Oscillation Modes: An Investigation in the US Western Interconnection

This report describes work performed to evaluate the impact of high grid-forming (GFM) inverter penetration on the inter-area oscillation mode characteristics of the Western Interconnection. Using simulations, this work analyzes how: a) replacing fossil-fuel-based synchronous generators by GFM inverters will impact properties of the North-South mode, and b) replacing the Colstrip power plant by grid-following (GFL) and GFM inverters will change the characteristics of the Montana mode. Results obtained indicate that high penetration of GFM inverters will significantly alter inter-area oscillation characteristics in interconnections. Low frequency oscillations in the 0.11 Hz range will be predominantly driven by remaining synchronous machines, and hence their relative distribution in the interconnection will impact mode characteristics and observability.

20 FOSSIL-FUELED POWER PLANTS↗

An Overview of Inverter-based Resource Interconnection Standards

For the past century, electric power systems have primarily been bulk power systems consisting of generation, transmission, and distribution networks. Now the rapid expansion of distributed renewable power sources (RESs) and the shift from large, conventional synchronous machine resources to smaller-sized resources with diverse generation characteristics become the most significant change in modern power systems. With the increasing penetration of RESs, which are inverter-based resources (IBRs), it is important to develop interconnection standards that define performance and capability criteria for these IBRs. This is necessary to ensure the stable and reliable operation of power systems. This report summarizes the standards for IBRs interconnection in North America.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Reliable, High Power Density Inverters for Heavy Equipment Applications

With this final report, the combined team of the University of Arkansas (UA), University of Illinois, Urbana-Champaign (UIUC), Wolfspeed, Caterpillar, and Ampaire have successfully met all of their project objectives. Noteworthy for the heavy equipment portion of the project with Caterpillar is that the team made its project milestones two years into the project by designing a power dense motor drive for a permanent magnet synchronous machine. Upon finding out that Caterpillar had pivoted to switched-reluctance machines (SRMs), the team subsequently redesigned and implemented the SRM drive with a coolant temperature of 105°C! The other major task that the UA, UIUC, and Wolfspeed teams took on was the design of a PMSM drive for a hybrid aircraft that was flown on Feb. 20, 2023 by Ampaire after extensive testing and evaluation. While there were also technical objectives in thermal management, integrated gate drivers, reliability studies, and high temperature capacitors with integrated bussing, each of these have been fully reported on in quarterly reports. In brief, advances in thermal management and high temperature capacitors were utilized in order to achieve a 105°C motor drive. The integrated gate driver work resulted in a higher density drive with no loss of efficiency. Most of the last year, during a no-cost extension, was spent waiting for the Ampaire motor drive to be tested (outside of our project). Many months passed with the device just sitting in California while the company dealt with battery-related issues. This delayed the integration and testing activities until Fall 2022. Once those began, then the process took about 4-5 months to complete culminating in the test flight in Feb. 2023. By providing technical advances and integration into final platforms, the barrier to economic impact has been lowered. This project benefits the public by overcoming key technical barriers to electrified and hybrid electric heavy equipment and aircraft. This, in turn, leads to lower greenhouse gas emissions and a cleaner environment. This final report summarizes the integrated gate driver work and the Ampaire hybrid electric aircraft integration and test flight efforts. All other information has been previously reported in quarterly reports. A summary of the motor drives created during this project is provided along with a listing of publications.

42 ENGINEERING↗

A Real-Time Testbed for Smart Inverter Cyber Security Studies

Distributed energy resources (DER) have become a popular solution to modern-day issues surrounding the efficiency and reliability of power generation, as well as climate change concerns. Energy centers are shifting towards incorporating smart inverters with embedded functionalities such as high voltage ride through (HVRT), low voltage ride through (LVRT), active and reactive power compensation. However, the integration of smart inverters leave DER systems highly vulnerable to cybersecurity threats. The distributed network protocol 3 (DNP3) is a common method of communication between grid-tied hardware. Despite its popularity, the level of security leaves all hardware connected to the grid at risk of severe cyber-attacks. Thus, it is important to study any potential cybersecurity threats towards grid-tied smart inverters to mitigate cybersecurity vulnerabilities and refine existing cyber-security protections. This report describes the proposed testbed design to study cybersecurity threats to smart inverters. The testbed utilizes a real-time simulation case in RSCAD that includes a grid-tied wind turbine (WT) topology featuring two back-to-back two-level voltage source converters (BTB,2L-VSCs) and a permanent magnet synchronous machine (PMSM). The simulated case runs within the NovaCor real time digital simulator (RTDS). This report focuses on the design and implementation of a single module of the GTNETx2 card as a distributed network protocol and the configuration of an IEEE 1518 DNP database file that includes input and output variables mapped to different connection points in the grid that transmit and receive discrete, analog, and binary signals on command. This allows realistic emulation of the communication between the smart inverter and the grid for cybersecurity studies.

97 MATHEMATICS AND COMPUTING↗

Study of the Protection Improvements for a Weak Grid Area With High Inverter-Based Resources (IBRs)

This project designs enhanced protection scheme for the real-world weak grid area with a high penetration of IBRs. As the existing protection schemes are originally designed for traditional synchronous machines, we first evaluate if the protection scheme will continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with IBR original equipment manufacturer black-box models is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. Enhanced protection is designed to address the challenge of lack of negative sequence current from IBRs, including increased restraining factors a2 and k2 to block 32Q or using V instead QV ORDER for ground faults, enhanced mho distance element with voltage and phase angle supervision for L-L faults. The efficacy of enhanced protection logic is validated and proven to work reliably. Additionally, IEEE Std. 2800-2022 negative sequence current compliant GFL and GFM IBRs from another vendor are tested and proven to work reliably without need for enhanced logic. Therefore, this work provides valuable decision-making for utilities facing protection system challenges due to IBRs, either designing enhanced protection scheme or requesting their IBRs being IEEE Std. 2800-2022 compliant to produce regulated negative sequence current for protection relay to make correct decision.

24 POWER TRANSMISSION AND DISTRIBUTION↗

UNIFI 1-MW Multi-Vendor Grid-Forming Inverter Test Updates

This presentation gives an update on UNIFI 1MW multi-vendor GFM inverter testing. The 1MW demo enters the last stage of the test, which is the integration test. And the main objectives of the integration tests include: 1) explore the interoperability of dispatching a future grid with energy mix (GFM inverters, GFL inverters and synchronous machine). The presentation highlights one example test, ROCOF, and summarizes all the key learning.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a realtime digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBRonly scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Advanced Motor Control Test Facility for NASA GRC Flywheel Energy Storage System Technology Development Unit

This paper describes the flywheel test facility developed at the NASA Glenn Research Center with particular emphasis on the motor drive components and control. A four-pole permanent magnet synchronous machine, suspended on magnetic bearings, is controlled with a field orientation algorithm. A discussion of the estimation of the rotor position and speed from a "once around signal" is given. The elimination of small dc currents by using a concurrent stationary frame current regulator is discussed and demonstrated. Initial experimental results are presented showing the successful operation and control of the unit at speeds up to 20,000 rpm.

Kenny, Barbara H.↗

Investigation of Combined Motor/Magnetic Bearings for Flywheel Energy Storage Systems

Dr. Hofmann's work in the summer of 2003 consisted of two separate projects. In the first part of the summer, Dr. Hofmann prepared and collected information regarding rotor losses in synchronous machines; in particular, machines with low rotor losses operating in vacuum and supported by magnetic bearings, such as the motor/generator for flywheel energy storage systems. This work culminated in a presentation at NASA Glenn Research Center on this topic. In the second part, Dr. Hofmann investigated an approach to flywheel energy storage where the phases of the flywheel motor/generator are connected in parallel with the phases of an induction machine driving a mechanical actuator. With this approach, additional power electronics for driving the flywheel unit are not required. Simulations of the connection of a flywheel energy storage system to a model of an electromechanical actuator testbed at NASA Glenn were performed that validated the proposed approach. A proof-of-concept experiment using the D1 flywheel unit at NASA Glenn and a Sundstrand induction machine connected to a dynamometer was successfully conducted.

Hofmann, Heath↗

AC/DC Power Systems with Applications for future Lunar/Mars base and Crew Exploration Vehicle

ABSTRACT The Power Systems branch at JSC faces a number of complex issues as it readies itself for the President's initiative on future space exploration beyond low earth orbit. Some of these preliminary issues - those dealing with electric power generation and distribution on board Mars-bound vehicle and that on Lunar and Martian surface may be summarized as follows: Type of prime mover - Because solar power may not be readily available on parts of the Lunar/Mars surface and also during the long duration flight to Mars, the primary source of power will most likely be nuclear power (Uranium fuel rods) with a secondary source of fuel cell (Hydrogen supply). The electric power generation source - With nuclear power being the main prime mover, the electric power generation source will most likely be an ac generator at a yet to be determined frequency. Thus, a critical issue is whether the generator should generate at constant or variable frequency. This will decide what type of generator to use - whether it is a synchronous machine, an asynchronous induction machine or a switched reluctance machine. The type of power distribution system - the distribution frequency, number of wires (3- wire, 4-wire or higher), and ac/dc hybridization. Building redundancy and fault tolerance in the generation and distribution sub-systems so that the system is safe; provides 100% availability to critical loads; continues to operate even with faulted sub-systems; and requires minimal maintenance. This report descril_es results of a summer faculty fellowship spent in the Power Systems Branch with the specific aim of investigating some of the lessons learned in electric power generation and usage from the terrestrial power systems industry, the aerospace industry as well as NASA's on-going missions so as to recommend novel surface and vehicle-based power systems architectures in support of future space exploration initiatives. A hybrid ac/dc architecture with source side and load side redundancies and including emergency generators on both ac and dc sides is proposed. The generation frequency is 400 Hz mostly because of the technology maturity at this frequency in the aerospace industry. Power will be distributed to several ac load distribution buses through solid state variable speed, constant frequency converters on the ac side. A segmented dc ring bus supplied from ac/dc converters and with the capability of connecting/disconnecting the segments will supply power to multiple de load distribution buses. The system will have the capability of reverse flow from dc to ac side in the case of an extreme emergency on the main ac generation side.

Chowdhury, Badrul H.↗

A Novel Current Angle Control Scheme in a Current Source Inverter Fed Permanent Magnet Synchronous Motor Drive for Automotive Applications

This paper describes a novel speed control scheme to operate a current source inverter (CSI) driven surface-mounted permanent magnet synchronous machine (SPMSM) for hybrid electric vehicles (HEVs) applications. The idea is to use the angle of the current vector to regulate the rotor speed while keeping the two dc-dc converter power switches on all the time to boost system efficiency. The effectiveness of the proposed scheme was verified with a 3 kW CSI-SPMSM drive prototype.

33 ADVANCED PROPULSION SYSTEMS↗

Robust Adaptive Decentralized Dynamic State Estimation with Unknown Control Inputs using Field PMU Measurements

This paper proposes a robust adaptive decentralized dynamic state estimation method for power system with unknown inputs of the highly detailed synchronous machine model. The temporal and spatial correlations among the unknown inputs are used to derive a vector auto-regressive model. The latter is further integrated together with state transition and measurement models for joint state and unknown inputs estimation. Thanks to the consideration of implicit cross-correlations between the states and the unknown inputs, only generator terminal voltage and current phasors are needed. Test results on the US WECC system using the field PMU measurements show that the proposed method is able to track both the system dynamic states and unknown controller inputs. These information could significantly benefit the validation and calibration of generator controller parameters.

Zhao, Junbo↗

Model Gap Quantification and Evaluation

In the real world, model gaps always exist because models cannot perfectly match the objective physical plants. Model gaps reflect the integrity of models, which is vital for model validation and calibration. This letter proposes a novel approach for model gap quantification and evaluation. First, a comprehensive metric is developed to quantify dynamic model gaps. Next, the model gaps are evaluated from a panoramic view of the probability distribution of the comprehensive metric for multiple scenarios. Finally, we demonstrate the proposed quantification and evaluation approach through synchronous machine models.

Wang, Shaobu↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations: Preprint

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: droop, virtual synchronous machine (VSM), and dispatchable virtual oscillator control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy with up to 150x lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

circuit-equivalent model↗

Probing Signal-Based Inertia and Frequency Response Estimation for Power Systems with High Penetration of Inverter-Based Resources: Preprint

Power system inertia is the inherent capability of a power system to resist changes in its frequency during disturbances. Real-time inertia estimation technology has become more important due to the low-inertia issues caused by the increasing integration levels of inverter-based resources (IBRs) from renewable energy; however, existing inertia estimation methods hardly consider multiple frequency response controls that act within the same time frame as conventional inertial response, thus making measured inertia values vary under different testing conditions. To resolve this issue, this paper proposes a novel real-time estimation method to simultaneously estimate a power system's inertia constant and frequency response droop constant using a well-designed probing signal. First, we formulate the inertia and frequency response model of a power system with IBRs. Second, through the integration and manipulation of the developed model, we propose a multivariate linear regression- based estimation method that is resilient to measurement noise. Third, we design a probing signal that can be injected by IBRs to incite the required transients for estimation. Finally, we validate the proposed estimation method through comprehensive power- hardware-in-the-loop experiments using inverter hardware and a realistic island power system model. The results demonstrate that the proposed method can accurately estimate the inertia and droop value of the power system with grid-following IBRs and grid-forming IBRs with virtual synchronous machine control.

frequency response↗

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources: Preprint

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION↗