Search NASA⌕ Search

SEARCH · Search NASA

Results for “Variable Generation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 127 records · Page 7

The Grid Value of Ocean Current Energy in Florida

Ocean current energy technology has been proposed as a potential contributor to Florida's energy portfolio. There has been limited investigation of how this energy would be valued when integrated into the Florida electrical grid. This study assesses three future grid scenarios to evaluate the impact of adding zero-cost ocean current energy to each. The Resource Planning Model, a tool developed by the National Renewable Energy Laboratory, is used to identify the least-cost generation mix through 2050, with and without ocean current energy. The first scenario is a base case and assumes existing policies in which the addition of ocean current energy does not retire fossil-based technologies but variable generation technologies. In the second scenario, solar and storage technologies are lower cost, and the addition of ocean current generation enables those technologies along with wind to retire existing natural gas units earlier. In the third scenario, which requires a 95% reduction in carbon emissions from 2020 levels by 2050, ocean current energy can play a role in decarbonization along with other variable generation technologies. This analysis is intended to inform stakeholders on the opportunity, potential challenges, and overall value to the grid of ocean current technology from a reliability and availability focused perspective.

capacity expansion model↗

A Novel Framework for Optimizing Ramping Capability of Hybrid Energy Storage Systems

Hybrid Energy Storage System has been widely applied in aerospace, electric vehicle, and microgrid applications. The advantages are that they include complimentary technologies with both high power and energy capabilities. HESS have the potential to be useful to the bulk power systems, for example to increase the value of energy produced by variable generation resource through enabling participation in ancillary service markets. Actualizing the benefits of HESSs requires optimizing the combined ramping capability of aggregated HESS resources. To provide quality ancillary service, source of HESSs locating at multiple sites of variable generation resource must be optimally sized and cohesively controlled. Optimizing aggregated resources can be formulated as an optimization problem. Successfully solving this problem not only requires using effective solution methods but also depends on accurately and rapidly setting the necessary parameters in the problem formula. This article proposes a novel framework with double-layer structure to solve the optimization problem of aggregating ramping capability. Program developed on the upper layer focuses on solving the optimization of aggregating ramping capability among multiple HESSs and is compatible with most existing optimization algorithms. Program on lower layer of the framework targets at optimizing the local control of a single HESS based on a thorough analytics of HESS operation strategy presented in this article. Result of local optimization is also provided to upper layer program for updating the parameters in formula of optimization problem. Real time hardware-in-the-loop test is conducted to verify the performance of the optimization framework developed. The work presented is expected to provide guidance for implementing this framework in practical operation.

Luo, Yushen↗

Annual Performance of the Second-Generation Variable-Geometry Oscillating Surge Wave Energy Converter

Recent studies in wave energy have highlighted the need for a structured innovation approach in wave energy converter (WEC) design because cost-of-energy estimates have remained high. One specific innovation being investigated by the National Renewable Energy Laboratory is WEC geometry control, which uses control surfaces in combination with an oscillating surge WEC (OSWEC) to increase device availability and power generation while limiting structural costs. This study performs the first analysis of annual performance for a novel OSWEC with geometry control to understand how the geometry control affects availability, annual power generation, and structural loadings like the power-take-off (PTO) torque or surge foundation force. Device hydrodynamic coefficients are calculated using linear potential theory for six geometry configurations. A nonideal PTO system is assumed and quadratic viscous damping losses are considered. Annual performance is evaluated and compared for three U.S. wave energy sites. The WEC geometry and PTO system are controlled on a sea-state basis to optimize for power capture while remaining under limits set on motion amplitude and structural loads. Results indicate that geometry control can increase availability up to 25 days in an average year depending on design limits, increase average power generation, and significantly reduce peak structural loads.

30 DIRECT ENERGY CONVERSION↗

CTGAN-TVAE

SAND2026-18914O CTGAN-TVAE (Conditional Tabular Generative Adversarial Networks-Tabular Variational Autoencoders) generates extensive sets of variable generation data through a hybrid framework. It enhances latent space representation by combining TVAE's robust feature-embedding with CTGAN's ability to condition categorical variables such as time. CTGAN-TVAE employs a fully connected neural network within a conditional generative adversarial network framework to manage continuous and categorical data effectively, capturing complex feature interactions without needing sequential modeling. This was developed as part of NNSA-MSIPP: Minority Serving Institution Partnership Program, Grant Number DE-NA0004016. Sandia National Laboratories is a multimission laboratory managed and operated by National Technology & Engineering Solutions of Sandia, LLC, a wholly owned subsidiary of Honeywell International Inc., for the U.S. Department of Energy's National Nuclear Security Administration under contract DE-NA0003525.

Newlun, Cody [Sandia National Lab. (SNL-CA), Liver↗

Western Wind Strategy: Addressing Critical Issues for Wind Deployment

The goal of the Western Wind Strategy project was to help remove critical barriers to wind development in the Western Interconnection. The four stated objectives of this project were to: (1) identify the barriers, particularly barriers to the operational integration of renewables and barriers identified by load-serving entities (LSEs) that will be buying wind generation, (2) communicate the barriers to state officials, (3) create a collaborative process to address those barriers with the Western states, utilities and the renewable industry, and (4) provide a role model for other regions. The project has been on the forefront of identifying and informing state policy makers and utility regulators of critical issues related to wind energy and the integration of variable generation. The project has been a critical component in the efforts of states to push forward important reforms and innovations that will enable states to meet their renewable energy goals and lower the cost to consumers of integrating variable generation.

17 WIND ENERGY↗

Coordination and Control of Flexible Building Loads for Renewable Integration; Demonstrations using VOLTTRON

Renewable energy resources such as wind and solar power have a high degree of uncertainty. Large-scale integration of these variable generation sources into the grid is a big challenge for power system operators. Buildings, in which we live and work, consume about 75% of the total electricity in the United States. They also have a large capacity of power flexibility due to their massive thermal capacitance. Therefore, they present a great opportunity to help the grid to manage power balance. In this report, we study coordination and control of flexible building loads for renewable integration. We first present the motivation and background, and conduct a literature review on building-to-grid integration. We also compile a catalog of flexible building loads that have great potential for renewable integration, and discuss their characteristics. We next collect solar generation data from a photovoltaic panel on Pacific Northwest National Laboratory campus, and conduct data analysis to study their characteristics. We find that solar generation output has a strong uncertainty, and the uncertainty occurs at almost all time scales. Additional data from other sources are also used to verify our study. We propose two transactive coordination strategies to manage flexible building loads for renewable integration. We prove the theories that support the two transactive coordination strategies and discuss their pros and cons. In this report, we select three types of flexible building loads—air-handling unit, rooftop unit, and a population of WHs—for which we demonstrate control of the flexible load to track a dispatch signal (e.g., renewable generation fluctuation) using experiment, simulation, or hardware-in-the-loop study. More specifically, we present the system description, model identification, controller design, test bed setup, and experiment results for each demonstration. We show that coordination and control of flexible loads has a great potential to integrate variable generation sources. The flexible loads can successfully track a power dispatch signal from the coordinator, while having little impact on the quality of service to the end-users.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A Comparison of Forecast Error Generators for Modeling Wind and Load Uncertainty

This paper presents four algorithms to generate random forecast error time series, including a truncated-normal distribution model, a state-space based Markov model, a seasonal autoregressive moving average (ARMA) model, and a stochastic-optimization based model. The error time series are used to create real-time (RT), hour-ahead (HA), and day-ahead (DA) wind and load forecast time series that statistically match historically observed forecasting data sets, used for variable generation integration studies. A comparison is made using historical DA load forecast and actual load values to generate new sets of DA forecasts with similar stoical forecast error characteristics. This paper discusses and compares the capabilities of each algorithm to preserve the characteristics of the historical forecast data sets.

Lu, Ning↗

Impact of Transmission on Resource Adequacy in Systems with Wind and Solar Power: Preprint

Variable generation is on track to become a significant contributor to electric power systems worldwide. Thus, it is important to analyze the effect that renewables will have on the reliability of systems. In this paper we present a new tool being implemented at the National Renewable Energy Laboratory, which allows the inclusion of variable generation in the power system resource adequacy. Thetool is used to quantify the potential contribution of transmission to reliability in highly interconnected systems and an example is provided using the Western Interconnection footprint.

14 SOLAR ENERGY↗

Final Scientific/Technical Report for Building Transmission Capacity in the Western Interconnection to Support a Low Carbon Future

The Building Transmission Capacity grant activities focused on educating both policy makers (primarily at Public Utility Commissions) and utilities across the West. Western Grid Group (WGG), the grant recipient, chose three methods to reach these audiences - direct outreach, a website that contains information on policies and strategies to integrate more variable generation resources, and a report - The Best of the West, Policies and Practices to Support Transition to a Lower-Carbon Electric Sector in the Western Interconnection and that highlights what is working in the West. While all avenues for education are effective the Best of the West report is the first west-wide assessment of its kind. The report details incremental changes that are working to integrate variable generation but it also expounds on what fundamental or transformative changes are needed to get to the 20% wind penetration and beyond.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Nuclear-renewable hybrid energy systems: Opportunities, interconnections, and needs

As the U.S. energy system evolves, the amount of electricity from variable-generation sources is likely to increase, which could result in additional times when electricity demand is lower than available production. Thus, purveyors of technologies that traditionally have provided base-load electricity—such as nuclear power plants—can explore new operating procedures to deal with the associated market signals. Concurrently, innovations in nuclear reactor design coupled with sophisticated control systems now allow for more complex apportionment of heat within an integrated system such as one linked to energy-intensive chemical processes. This paper explores one opportunity – nuclear-renewable hybrid energy systems. These are defined as integrated facilities comprised of nuclear reactors, renewable energy generation, and industrial processes that can simultaneously address the need for grid flexibility, greenhouse gas emission reductions, and optimal use of investment capital. Six aspects of interaction (interconnections) between elements of nuclear-renewable hybrid energy systems are identified: Thermal, electrical, chemical, hydrogen, mechanical, and information. Additionally, system-level aspects affect selection, design, and operation of this hybrid system type. Throughout the paper, gaps and research needs are identified to promote further exploration of the topic.

30 DIRECT ENERGY CONVERSION↗

Photovoltaic frequency–watt curve design for frequency regulation and fast contingency reserves

When renewable energy resources are installed in electricity grids, they typically increase generation variability and displace thermal generator control action and inertia. Grid operators combat these emerging challenges with advanced distributed energy resource (DER) functions to support frequency and provide voltage regulation and protection mechanisms. This paper focuses on providing frequency reserves using autonomous IEC TR 61850-90-7 pointwise frequency-watt (FW) functions that adjust DER active power as a function of measured grid frequency. The importance of incorporating FW functions into a fleet of photovoltaic (PV) systems is demonstrated in simulation. Effects of FW curve design, including curtailment, deadband, and droop, were analyzed against performance metrics using Latin hypercube sampling for 20%, 70%, and 120% PV penetration scenarios on the Hawaiian island of Lanai. Finally, to understand the financial implications of FW functions to utilities, a performance function was defined based on monetary costs attributable to curtailed PV production, load shedding, and generator wear. An optimization wrapper was then created to find the best FW function curve for each penetration level. Lastly, it was found that in all cases, the utility would save money by implementing appropriate FW functions.

14 SOLAR ENERGY↗

Variable-speed Generators with Flux Weakening

A cost-competitive, permanent-magnet 20 kW generator is designed such that the following criteria are satisfied: an (over) load capability of at least 30 kW over the entire speed range of 60-120 rpm, generator weight of about 550 lbs with a maximum radial stator flux density of 0.82 T at low speed, unity power factor operation, acceptably small synchronous reactances and operation without a gear box. To justify this final design four different generator designs are investigated: the first two designs are studied to obtain a speed range from 20 to 200 rpm employing rotor field weakening, and the latter two are investigated to obtain a maximum speed range of 40 to 160 rpm based on field weakening via the stator excitation. The generator reactances and induced voltages are computed using finite element/difference solutions. Generator losses and efficiencies are presented for all four designs at rated temperature of Tr=120C.

Fardoun, A. A.↗