Search NASA⌕ Search

SEARCH · Search NASA

Results for “electromagnetic transient simulations”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 127 records · Page 7

A New Type of Weak Grid IBR Oscillations

This letter presents the discovery of a new type oscillations associated with inverter-based resources (IBRs) in weak grids. While typical weak grid oscillations become worse when the grid strength decreases and the power exporting level increases, this new type of oscillations appear when the grid becomes weaker and the power exporting level decreases. Electromagnetic transient (EMT) simulation results are presented, along with eigenvalue loci for a varying power. The notable signatures of such oscillations are also remarked. In further analysis, a feedback system consisting of two blocks is derived with one block associated with the phase-locked-loop (PLL) and the other associated with the rest of the system. Here, this feedback system quantitatively demonstrates why insufficient damping in the PLL may be an issue for stability. Open-loop analysis shows that a larger phase lag in angle tracking in the low-frequency range due to high power exporting level at the weak grid condition is beneficial to the open-loop poles introduced by the PLL. And this is the reason why such oscillations may appear when power is ramping down.

24 POWER TRANSMISSION AND DISTRIBUTION↗

DQ Admittance Model Extraction for IBRs via Gaussian Pulse Excitation

While $dq$ admittance models have shown to be very useful for stability analysis, extracting admittance models of inverter-based resources (IBRs) from the electromagnetic transient (EMT) simulation environment using frequency scans takes time. In this letter, a new perturbation method based on Gaussian pulses in combination with the system identification algorithms shows great promise for parametric $dq$ admittance model extraction. We present the $dq$ admittance model extracting method for a type-4 wind turbine. Challenges in implementing Gaussian pulse excitation are also pointed out. In conclusion, the extracted $dq$ admittance model via the new method shows to have a high matching degree with the measurements obtained from frequency scans.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Analytical Models of Frequency and Voltage in Large-Scale All-Inverter Power Systems

Low-order frequency response models for power systems have a decades-long history in optimization and control problems such as unit commitment, economic dispatch, and wide-area control. With a few exceptions, these models are built upon the Newtonian mechanics of synchronous generators, assuming that the frequency dynamics across a system are approximately homogeneous, and assume the dynamics of nodal voltages for most operating conditions are negligible, and thus are not directly computed at all buses. As a result, the use of system frequency models results in the systematic underestimation of frequency minimum nadir and maximum RoCoF, and provides no insight into the reactive power-voltage dynamics. This paper proposes a low-order model of both frequency and voltage response in grid-forming inverter-dominated power systems. The proposed model accounts for spatial-temporal variations in frequency and voltage behavior across a system and as a result, demonstrates the heterogeneity of frequency response in future renewable power systems. Electromagnetic transient (EMT) simulations are used to validate the utility, accuracy, and computational efficiency of these models, setting the basis for them to serve as fast, scalable alternatives to EMT simulation, especially when dealing with very large-scale systems, for both planning and operational studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

pnnl/pecblocks

ConverterBlocks uses the output of detailed electromagnetic transient (EMT) simulations to produce generalized block diagram models of power electronic systems. The process uses deep learning with customized block architectures. The outputs are reduced-order models that meet specified accuracy requirements, while providing important advantages over the original EMT models: ConverterBlock models have fewer nodes and can take longer time steps, resulting in shorter simulation times ConverterBlock models are continuously differentiable, making them compatible with control design methodsGeneralized block diagram modeling of power electronic converters for grid solar and storage applications.

McDermott, Tom↗

Impact of Inverter Based Resource Negative Sequence Current Injection on Transmission System Protection

This report documents the results of analysis performed to investigate the impact of inverter-based resource (IBR) response to unbalanced faults on transmission system protective relay dependability and security. Electromagnetic transient (EMT) simulations were performed to simulate IBR response to these faults using existing manufacturer-developed EMT models for four separate IBRs. The study team was composed of IBR manufacturers, relay manufacturers, transmission providers, reliability coordinators and industry consultants with experience in EMT simulation and system protection. The results indicate that under certain conditions, IBR response can result in protective relay misoperations if current protection practices, which were developed based on conventional power sources, are not adapted to the characteristics of IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Studying the Impact of Momentary Cessation of IBRs Compliant With IEEE Std. 2800-2022 on Transmission Line Protection Elements

This paper examines the impact of inverter-based resource (IBR) momentary cessation timing on transmission system protection relays. IEEE Std. 2800 mandates voltage ride-through, requiring IBRs to remain online during voltage disturbances. However, for severe voltage dips (|V| = 0.1 p.u.), the standard permits current blocking. In practice, vendors implement momentary cessation with varying delays, potentially affecting relay operation if IBRs cease too early. This article studies the impact of the time IBRs enter momentary cessation on transmission line protective relays. Using an electromagnetic transient (EMT) simulation, this study models IBR momentary cessation with tunable delays in a realistic transmission network. COMTRADE files generated from EMT simulations are analyzed in MATLAB using detailed protective relay models. Results indicate that IBRs must sustain operation for at least one cycle to ensure proper relay response; otherwise, relays may fail to oper- ate. These findings guide IBR vendors in optimizing momentary cessation settings to enhance transmission line protection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Investigation on Tuning Power–Frequency Droop for Improved Grid–Forming Inverter and Synchronous Generator Transient Load Sharing

Poor transient load sharing has been observed during the parallel operation of synchronous generators (SGs) and droop-controlled grid-forming (GFM) inverter-based resources (IBRs) in islanded microgrids. This can result in overcurrent protections, causing the inverters to trip, which leads to the collapse of voltage and frequency. In this article, small-signal analysis supported by electromagnetic transients (EMTs) simulation is performed on a detailed model of a microgrid containing IBRs and an SG to identify underdamped modes and their sensitivities to the power–frequency (P-F) droop parameter. Further EMT simulation of a more complex microgrid model with multiple GFM IBRs and SGs is performed to determine whether trends identified from the modal analysis extend to cases where the number of SGs in operation may vary. The objective is to investigate the effectiveness of tuning this parameter to reduce the likelihood of overcurrents in response to load and generation disturbances. The work uncovers both fast and slow modes of concern. Primarily, the findings show that increasing the P-F droop value improves the damping of the slower mode while degrading the damping of the faster mode, leading to an upper limit on the damping improvement of the GFM IBR output current. In EMT simulations of the more complex microgrid, the greatest damping improvement still exhibits significant maximum overshoot. Furthermore, the optimal value of the P-F droop parameter is sensitive to the number of SGs in operation. The conclusion is that tuning the P-F droop parameter is not an effective means to avoid the overcurrent tripping of GFM IBRs during response to large load or generation disturbances when operating in parallel to SGs in islanded microgrids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Resilient Inverter-Driven Black Start with Collective Parallel Grid-Forming Operation: Preprint

As the modern power systems are experiencing exceptional changes with increasing penetration of inverter-based resources (IBRs), system restoration using IBRs has received attention. Using local grid-forming (GFM) assets near consumers, engineered to establish grid voltages in the absence of a stiff grid, i.e., bottom-up restoration, a distribution system would obtain high system resilience, by not relying on the bulk power system restoration requiring significant human intervention and procedure to restore. This paper studies the technical feasibility of the novel approach with detailed electromagnetic transient (EMT) simulations. To thoroughly evaluate the potential of GFM inverters and technical challenges in IBR-driven black start, a detailed three-phase inverter model is developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter to sustain momentary overloading during the black start. To examine dynamic aspects of the black start process, the EMT simulation also models transformer and motor dynamics to emulate their inrush and start-up behaviors as well as network dynamics. In addition, active involvement of grid-following distributed energy resources (DER) is also studied to facilitate the black start process. It is shown that, by allowing multiple GFM inverters to collectively black start without master-slave coordination, a system can achieve high resilience even with a fraction of assets lost. Two test cases of inverter-driven black start using two and one GFM inverters, respectively, for a heavily unbalanced 2-MVA distribution feeder are demonstrated. Takeaways for further study and field deployment are provided.

grid-forming inverter↗

Black Start of Unbalanced Microgrids Harmonizing Single- and Three-Phase Grid-Forming Inverters: Preprint

As power systems are transforming with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has drawn attention. Using distributed grid-forming (GFM) assets located near critical loads, either three-phase or single-phase, to establish microgrid voltages in the absence of a bulk grid, a distribution system could obtain high system survivability. For swift and secure recovery of a critical load in a single-phase lateral, local single-phase GFM inverters can form a microgrid, and then it can be combined with a neighbouring grid with the inverters remaining in GFM mode for voltage and frequency regulation until the bulk grid comes online. It leads to dynamic interoperation of single-phase GFM inverters with three-phase ones in the black start process. This paper studies the novel approach with electromagnetic transient (EMT) simulations. To evaluate the potential and the technical challenges of the heterogeneous IBR-driven black start, three-phase and single-phase GFM inverter models are developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter (three-phase) and current magnitude limiter (single-phase). To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics emulating their inrush and startup behavior as well as network dynamics. Involvement of grid-following assets to facilitate the black-start process is also modeled. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, regardless of phases, a system can achieve extreme resilience. An inverter-driven black start of a heavily unbalanced 2-MVA distribution feeder using 1 three-phase and 3 single-phase GFM inverters is demonstrated. The simulation shows the heterogeneous system can maintain stability with the single-phase GFM dynamics coupled with the three-phase one.

grid-forming inverter↗

A High-Fidelity Electromagnetic Transient Model of Inverter-based Resources Integrated to an IEEE-9 Bus System for Benchmarking Studies

An inverter-based resource (IBR) is a source of electricity that is asynchronously connected to the electrical grid via an electronic power converter. These power sources lack the intrinsic behaviors of the standard power plants, presenting specific challenges to system stability. These power sources lack the intrinsic behaviors of the standards power plants and their features are almost entirely defined by the control strategy used on them, presenting specific challenges to system stability as their penetration increases into the already fragile Bulk Power System (BPS). Utilizing renewable energy has a great upside but the electrical industry needs to understand the requirements like performing electromagnetic transient (EMT) simulation studies in planning and/or in interconnection studies. This paper presents the development of a high-fidelity EMT model based on commercial equipment and field parameters, which at the same time aims to study the increasing penetration of IBRs and their impact on the actual BPS. The open-source EMT model developed will be a benchmarking example that can be used to evaluate algorithms in the power grid (including evaluating grid-forming controls, power system monitoring and operation, etc.).

Martinez Montejano, Misael↗

Adaptive Narrowband Damping for Improving Harmonic Stability of Modular Multilevel Converter: Preprint

Harmonic instability events between modular multilevel converter (MMC) and ac systems have been widely reported in recent years. To resolve it, this paper proposes an adaptive narrowband damping control that automatically programs, adds and adjusts damping around the oscillation frequency when detect the oscillation. The paper first presents a low-pass filter design for MMC control loops, which pushes all negative damping of MMC impedance down to the medium frequency range (< approximately 1000 Hz). This makes narrowband damping can be more targeted and easier to design because multiple harmonic oscillations are avoided. An adaptive damping control that uses online oscillation detection is then proposed, which can automatically configure the narrowband damper to provide damping to the MMC at the detected oscillation frequency. In contrast to existing narrowband damping methods, the proposed adaptive narrowband damper adjusts the damping gain (e.g., to zero when system resonance disappears) and the width of the damping range automatically based on continuous monitoring of system resonance conditions. Electromagnetic transient (EMT) simulation results validate the efficacy of the proposed method in two typical MMC-based power systems.

active damping↗

Per-Phase Control for CHB Converters with Negative-Sequence Current and DC Voltage Balancing Control

This paper presents a per-phase controller for a grid-connected Cascaded H-Bridge (CHB) converter featuring negative sequence current regulation and DC bus voltage balancing capabilities. Unlike conventional three-phase controllers, each phase of the CHB can be separately and controlled to regulate the DC voltage and reactive power flow. per-phase negative sequence current control strategy is incorporated into the proposed controller to ensure compliance with IEEE Standard 2800-2022, which requires the absorption of negative-sequence reactive current during grid voltage disturbances. Furthermore, a feed-forward control-based DC bus voltage balancing method is employed, which eliminates the need for the integrator commonly used in traditional approaches. The performance of the proposed controller is validated under various unbalanced grid scenarios and DC bus voltage imbalances through electromagnetic transient (EMT) simulation using a three-phase, three-level grid-connected CHB–Dual Active Bridge (DAB) converter testbed developed on MATLAB/Simulink. Additionally, the performance of the negative-sequence current regulation is investigated through simulation under different unbalanced grid voltage scenarios.

negative sequence current↗

Real-World 20-Hz IBR Subsynchronous Oscillations: Signatures and Mechanism Analysis

This article provides analyses of subsynchronous oscillations associated with solar photovoltaics (PVs) observed in real world. All have oscillation frequencies at approximately 20 Hz in voltage and current magnitudes. On the other hand, in phase voltage and current, the oscillations show very different signatures. Through constructing simplified linear models and conducting sensitivity analysis, we are able to associate dynamic phenomena with the underlying mechanism and speculate the possible causes of the 20-Hz oscillations. The analysis results have all been validated via simulation results from electromagnetic transient (EMT) test beds constructed in MATLAB/Simscape.

inverter-based resources↗

Cause identification of electromagnetic transient events using spatiotemporal feature learning

This paper presents a spatiotemporal feature learning method for cause identification of electromagnetic transient events in power grids. The proposed method is formulated based on the availability of time-synchronized high-frequency measurements and using the convolutional neural network as the spatiotemporal feature representation along with softmax function for the classification. Despite the existing threshold-based, or energy-based events analysis methods, such as support vector machine autoencoder, and tapered multi-layer perceptron neural network, the proposed feature learning is carried out with respect to both time and space. The effectiveness of the proposed feature learning and the subsequent cause identification is validated through the Electromagnetic Transients Program (EMTP) simulation of different events such as line energization, capacitor bank energization, lightning, fault, and high-impedance fault in the IEEE 30-bus, and the real-time digital simulation of the Western System Coordinating Council (WSCC) 9-bus system.

42 ENGINEERING↗

Parallel Grid-Forming Inverter-Driven Black Start: Power-Hardware-in-the-Loop Validation: Preprint

With power systems encountering increasing deployment levels of inverter-based resources (IBRs), system restoration using grid-forming (GFM) IBRs has gained attention. Engineered to establish grid voltages in the absence of a stiff grid, black-start-capable GFM IBRs are expected to enhance power system resilience by playing a critical role in bottom-up system restoration. This paper experimentally studies the feasibility of the novel approach through power-hardware-in-the-loop (PHIL) testing and validation with a commercial GFM inverter. The PHIL test setup demonstrates an inverter-driven black start of a 5-MW unbalanced distribution feeder where two GFM inverters collectively black start the feeder: one is a commercial hardware GFM inverter interacting through the PHIL interface, and the other is a software GFM emulated by a real-time simulation with full electromagnetic transient (EMT) models. Both GFM inverters are equipped with negative-sequence voltage control to suppress the voltage imbalance resulting from the unbalanced loading, allowing us to study the dynamic interactions between the GFMs with their control parameters unknown. To evaluate the dynamic behavior of the GFM inverters under the entire black-start process, the EMT model of the distribution system details the transformer and motor dynamics to emulate their inrush and startup behaviors. It abstracts conventional grid-connected inverter dynamics, i.e., grid-following inverters. Oscilloscope measurements of the hardware GFM inverter are also presented for critical steps. Takeaways for further study and field deployment are provided.

grid-forming inverter↗

Novel Approach to PV Inverter Modeling and Simulation Leveraging Experiments, Learning Based Modeling and Co-Simulation

Photovoltaic (PV) inverter manufacturers use custom, proprietary control approaches and topologies in their inverter design. The proprietary nature of these approaches makes it challenging to share electromagnetic transients (EMT) domain models for system studies. This research work presents an approach to develop EMT models from experimental data. We use novel approach in experimental design, high fidelity data collection, use of learning-based modeling, and co-simulation to reduce the time taken to develop an EMT model for an inverter under test (IUT). We used a 20 kW off-the-shelf grid following PV inverter and subjected the inverter to controlled tests. The tests include voltage and frequency step changes, as well as solar irradiance variations. The recorded high frequency data were used to train a neural network model representing the dynamic behavior of the IUT. The model was subsequently imported into an EMT tool using co-simulation techniques, and thus completing the modeling effort.

black box inverter modeling↗

An Electromagnetic Transient and Three-Phase Phasor Co-Simulation Platform for Studying Distribution System Transients with High Pentration of DERs

Inverter vendors usually have electro-magnetic transient (EMT) models of distributed energy resources (DERs) for validation purposes and these types of models are usually black-boxed considering intellectual property (IP) protection. Limited by small simulation time step for the entire power system network, studying the system-level responses of DERs in EMT simulators is more time-consuming as the network size increases. Meanwhile, vendors usually do not have inverter models that can be used in three-phase phasor-domain simulators. This paper proposes a platform that can dynamically co-simulate the EMT inverter models and three-phase phasor-domain distribution networks considering high penetration of inverter-based DERs. This platform is very useful for evaluating the impacts of vendor-provided black-box DER model on distribution system dynamics. The co-simulation platform is validated against the full EMT model using a simple two-inverter test system and tested using IEEE 34-node test feeder.

Liu, Yuan↗