At least 145 records · Page 8

Guest Editorial Special Section on Advanced Medium-Voltage Power Electronics for Grid Interactive Applications

Medium-voltage power electronics (MVPE) plays essential roles in power grid modernization and links the MV distribution grid with low-voltage consumers and prosumers. Various MVPE devices, such as solid-state transformers or circuit breakers, inverter-based resources, power flow controllers, etc., bring the benefits of voltage conversion and power regulation in small footprint, power quality and efficiency improvements, and enhancements of grid controllability, flexibility, stability, and resilience. The MVPE also makes it possible for sustainable energy systems, such as solar/wind farms and energy storage generating facilities, to directly access to MV grids without multistage conversions. With their intrinsic intelligence and communications, MVPE enables many new smart grid functions and applications, e.g., dc interconnections and electric vehicle charging, which were not envisioned by traditional power grids otherwise. In addition, the integration of physical power processing units with cyber components forms a cyber-physical system, which is essential for long-term sustainability, development, and environmental preservation. Nonetheless, technical challenges on MVPE device reliability, scalable and efficient converter topologies, control stability, large-scale modeling and simulation, to name a few, need to be addressed and advanced to the next level. In conclusion, this Special Section on Advanced MV Power Electronics for Grid Interactive Applications in IEEE Transactions on Power Electronics (TPEL) provides an insight on some of the recent advances in MVPE and emerging challenges and potential solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A review of Geological Thermal Energy Storage for seasonal, grid-scale dispatching

Energy storage is essential for the decarbonization of the U.S. energy grid, especially with the increasing deployment of variable renewable energy sources like solar and wind. Geological thermal energy storage (GeoTES) has emerged as a promising long duration, grid scale solution, providing stability and security through flexible operations and valuable grid services. GeoTES utilizes subsurface reservoirs to store thermal energy for power generation and direct-use heating and cooling. This approach significantly enhances the use of low-temperature reservoirs, which would otherwise be unsuitable for geothermal power plants. It also aligns well with depleted oil and gas reservoirs, concentrating solar power, non-flexible renewables (photovoltaic and wind), and geothermal-related power cycles. Given the favorable marginal costs of GeoTES as storage duration increases, it becomes particularly competitive for seasonal, grid-scale dispatch, where few technologies are viable. This paper provides a comprehensive review of GeoTES systems and the research underpinning itsr development. This analysis begins by defining and categorizing the unique characteristics of thermal energy storage techniques, setting GeoTES apart from other technologies. The various components, configurations, subsurface characteristics, and modeling efforts that guide GeoTES development are then explored. Finally, challenges in GeoTES research, development, and deployment are discussed, along with mitigation strategies and lessons from related technologies. Beyond their economic benefits, GeoTES systems support grid resilience and decarbonize industrial processes. Their scalability, broad distribution, seasonal storage potential, and flexible dispatch capacity make GeoTES a valuable tool for expanding renewable energy deployment and addressing climate change.

15 - GEOTHERMAL ENERGY↗

South Asia Group for Energy-India

The South Asia Group for Energy (SAGE) is working with Grid India and the Central Electricity Authority (CEA) to determine the best methods to deploy more inverter-based resources (IBR) such as solar photovoltaic generators and utility-scale battery. To address grid strength and stability concerns, planners and operators are working with the National Renewable Energy Laboratory's (NREL) team, through SAGE, to identify potential solutions for strengthening the grid and fostering grid reliability.

ENERGY PLANNING, POLICY, AND ECONOMY↗

Thermal and electric multidomain dynamic model for integration of power grid distribution with behind-the-meter devices

As renewable energy sources like solar and wind power become more integrated into the grid, coordinated control of behind-the-meter devices is crucial for enhancing grid flexibility and reliability and for meeting cost targets, with standardized models being developed to support this transition. The increasing flexibility and uncertainty of integrated renewable energy grids, along with interactions between various subsystems, make traditional steady-state modeling insufficient to capture transient and dynamic behaviors. Current models (e.g., composite load and battery equivalent models) focus on thermodynamic or electrical characteristics but overlook critical electromechanical interactions. This limits the ability to share performance information for grid services and hampers fast dynamic simulations. In addition, motor stalling is usually triggered by a fault event and attributed to the characteristics of the mechanical torque of the motor, resulting in absorption of a large amount of reactive power during the stalling period. Further, this significant withdrawal of reactive power will deteriorate the dynamic voltage stability of power grids and cause delayed voltage recovery. Therefore, an in-depth modeling of the thermodynamics or mechanical torque is essential to study the impacts of the realistic torque characteristics of those behind-the-meter devices on power system voltage stability. This study developed a dynamic multidomain model for building HVAC systems, such as air-source heat pumps, to simulate their thermal and electrical responses to grid transients. The model can accurately predict power metrics with a mean absolute percentage error of 10%, by validating against with power system computer-aided design performance data. Case studies demonstrate the model capability of capturing the transient response to sudden voltage changes, rapid load fluctuations, and system shutdowns respectively. During a sudden voltage drop (30% for 0.1s), a fully loaded heat pump’s motor speed dropped, continued declining, and shut down after 3.6s, with severe power oscillations and a torque spike. A partially loaded unit experienced temporary oscillations but stabilized. Under higher building loads, compressor speed increased from 64% to 100%, with power and torque rising before stabilizing. In safety-triggered shutdowns, power decreased after minor fluctuations, and torque briefly spiked before dropping to zero.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Cybersecurity Challenges in Low-Inertia Power-Electronics-Dominated Grids

Here, the low inertia characteristics of the power electronics dominated grid (PEDG) introduces challenges while restoring voltage and frequency to their nominal values. These stability challenges create new cybersecurity vulnerabilities that are not thoroughly discussed in the literature. Cyber events such as false data injection (FDI), denial of service (DoS), man-in-the-middle attacks, stealthy attacks, and advanced persistent threats target PEDG to disrupt grid stability or gain financial benefits. The low inertia of PEDG (< 2s) compared to traditional grids (~10s) exacerbates these vulnerabilities. In response to stealthy attacks on state variables that supervisory layers cannot detect until significant harm occurs, the low inertia characteristics of PEDG offer substantial stealthy attack surfaces. To counteract such threats, PEDG must be equipped with ultra-fast real-time anomaly detection system and trajectory prediction mechanism to achieve effective cyberattack resiliency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid and Wind Transient Ride Through Assessment of Type-5 Synchronous Wind Turbine

The integration of the inverter-based renewable energy resources is increasing and replacing conventional synchronous generators in the evolving bulk power system (BPS), impacting the system inertia along the way. Also, the limited over-current capability of power electronic converters continues to deteriorate the grid strength of the evolving power systems. Type-5 wind turbines have the potential to mitigate these problems because this configuration interfaces with the grid through a synchronous generator; hence, its operation and consequent grid impacts might mimic the conventional synchronous generator. The drivetrain of this type of turbines, however, is different from the more common Type-3 and Type-4 turbines. A hydraulic torque converter and gearbox with torque limiting feature are integral parts of a Type-5 wind turbine drivetrain, to isolate the wind speed variations at the wind turbine rotor from the grid connected generator side. This supports the synchronous operation of the generator. However, high fidelity models of Type-5 wind turbine drivetrain including these core components are not openly and widely available for grid integration and transient stability studies. Moreover, Type-5 turbines are not commonly deployed and hence its power generation and frequency stability characteristics are not widely publicized. This hinders appropriate assessment of Type-5 wind power plant's contribution to bulk grid resilience. This work provides transient stability assessment of a standalone Type-5 wind turbine. Normal operation and grid transient studies are performed to see the step load change and wind speed disturbance impacts on the Type-5 drivetrain and generation dispatch. Preliminary results show that Type-5 wind turbines can support load changes of between 0.6 p.u to 1.15 p.u. Beyond this point, the synchronization of the generator starts to deviate from its set point.

17 - WIND ENERGY↗

Stability Analysis of Power Systems with High Penetration of State-of-the-Art Inverter Technologies

With the increasing level of inverter-based resources (IBRs) in modern power systems, this paper presents a small-signal stability analysis for power systems comprising synchronous generators (SGs) and IBRs. Four types of inverter controls are considered: two grid-following (GFL) controls, with or without grid support functions; droop-based grid-forming (GFM) controls; and virtual oscillator control-based GFM. We also analyze the impact of STATCOM and synchronous condensers on system stability to assess their role in the energy mix transition. With the small-signal dynamic behavior of the major technologies modeled, this paper provides stringent stability assessments using the IEEE 39-bus benchmark system modified to simulate future power systems. The exhaustive test cases allow for (a) assessing the impacts of different types and controls of generation and supplementary grid assets, as well as system inertia and line impedance on grid stability, and (b) elucidating pathways for the stabilization of IBR-dominated power systems. The analysis also indicates that future power systems can be stabilized with only a fraction of the total generation as voltage sources without SGs or significant system inertia if they are well distributed. This study provides insights into future power system operations with a high level of IBRs that can also be used for planning and operation studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Stability-Constrained Learning for Frequency Regulation in Power Grids With Variable Inertia

The increasing penetration of converter-based renewable generation has resulted in faster frequency dynamics, and low and variable inertia. As a result, there is a need for frequency control methods that are able to stabilize a disturbance in the power system at timescales comparable to the fast converter dynamics. This paper proposes a combined linear and neural network controller for inverter-based primary frequency control that is stable at time-varying levels of inertia. We model the time-variance in inertia via a switched affine hybrid system model. We derive stability certificates for the proposed controller via a quadratic candidate Lyapunov function. We test the proposed control on a 12-bus 3-area test network, and compare its performance with a base case linear controller, optimized linear controller, and finite-horizon Linear Quadratic Regulator (LQR). Our proposed controller achieves faster mean settling time and over 50% reduction in average control cost across 100 inertia scenarios compared to the optimized linear controller. Unlike LQR which requires complete knowledge of the inertia trajectories and system dynamics over the entire control time horizon, our proposed controller is real-time tractable, and achieves comparable performance to LQR.

data-driven control↗

Voltage Service Limits Smart Contract Using Distributed Ledger Technology for Electrical Utility Grid with Customer-Owned Generator

Modern electrical grids face growing stability risks from customer-owned generators, especially at points of common couplings (PCCs). Disruptive behavior from power-electronic sources can cause protective relays to isolate problematic generators, making measurement integrity critical. This article presents a distributed ledger technology (DLT) approach that uses smart contracts to evaluate PCC voltage measurements and trigger backup breaker operations. The approach is framed as a verifiable, multi-organization attestation and audit layer, not as a real-time control security mechanism. In the proposed architecture, voltage measurements from a hardware protective relay are anchored on a DLT through the Cyber Grid Guard (CGG) system for attestation by both the grid utility and customer-owned generator. A Voltage Service Limits (VSLs) smart contract evaluates the on-chain measurements against allowable phase-voltage limits derived from the ANSI C84.1 standard. The framework is validated in a hardware-relay-in-the-loop test bed under sustained-undervoltage, sustained-overvoltage, and transient line-to-line fault scenarios. The results show that the VSL smart contract can process these measurements and issue backup breaker actions consistent with the defined service-limit criteria, demonstrating the DLT potential as a verifiable audit layer at the PCC that complements primary protection.

cyber security↗

Stability Analysis of Parallel Connected Bidirectional WPT System

This paper presents a stability analysis of parallel-connected bi-directional series-series resonant network wireless power transfer (WPT), optimized for Electric Vehicle (EV) charging and vehicle-to-grid (V2G) applications. The study addresses critical stability challenges in systems integrated with diverse distributed energy resources (DERs), including photovoltaics, fuel cells, wind turbines, energy storage systems, and the AC grid. The stability of such integrated DC grid systems is paramount for ensuring reliable operation, particularly under varying power flow conditions and dynamic interactions between parallel WPT systems. The analysis included system impedance characterization, state-space modeling, and open and closed-loop stability evaluations. The results demonstrated that the integration of a robust control architecture effectively mitigates instability risks and supports scalable, efficient operation. This work underscores the converter's adaptability and its potential for large-scale deployment in wireless EV charging infrastructures and integrated DC grid systems.

Asa, Erdem [ORNL] (ORCID:0000000190884812)↗

TCF - Sustainable Well Cement for Geothermal, Thermal Recovery, and Carbon Storage wells

Primary cementing is the most important operation performed on a subterranean well. Cement, placed in the annulus between the casing and the formations, serves as a hydraulic seal preventing fluids and gas migrations, protecting steel casing from corrosion, and supporting the well structure. Poor cementing jobs can be directly responsible for wells not reaching their full capacity, casing corrosion, compromised well integrity and, in the worst-case scenarios, well collapse. Geothermal, thermal recovery, and carbon storage wells offer environments that are especially difficult for cements to survive while the required lifespan of these wells can be years. In these wells currently used cements cannot provide durable well integrity, and new solutions are necessary. The necessity of stabilizing the electric grid, increasing its flexibility, and providing energy on demand will further expand the market of durable cement solutions for applications in high-temperature underground reservoir thermal energy storage wells (HT RTES). The design challenges of special cement systems for such wells originate from chemistry limitations of currently used well cements, aggressive environments, temperature and repeated shock conditions associated with them, and very weak formations that are not uncommon in these wells. During the last 70 years the most common systems for thermal-well construction have been Ordinary Portland Cement (OPC) (absolute majority of the wells), silica-lime system, and high aluminum cement-containing formulations. The major issues of calcium-silicate hydrates, that form during the hydration of OPC resulting in hardened material, are their poor chemical resistance to acids due to the calcium interactions with acid anions followed by its eventual dissolution, even in mild acids, such as carbonic acid from CO 2 dissolution, and inadequate bonding to the steel causing serious casing corrosion problems (Sugama & Pyatina, 2019). Performance of OPC-based cement may be significantly improved with organic additives; however, those are limited by their temperature stability. An alternative to calcium-silicate cement was developed by BNL and commercialized by Halliburton as ThermaLock TM cement. Calcium-aluminate-phosphate-based chemistry of the material allowed overcoming acid-resistance problems of OPC, especially in CO 2 -rich geothermal environments. In 2012-2015, building upon this experience, BNL developed Thermal Shock Resistant Cement (TSRC) with the support of Geothermal Technology Office (GTO) of DOE. TSRC has high-temperature stable chemistry, superior properties of cement-metal casing bond and corrosion protection (4-times better than currently used OPC-based formulation), significantly outperforms common well-cements in thermal-shock tests, has self-healing properties, and like ThermaLock TM is CO 2 resistant incorporating carbonate ions into stable hydrates (Gill et al., 2012).

15 GEOTHERMAL ENERGY↗

Feasibility and strategic implications of deploying nuclear power reactors in Africa

This report assesses the feasibility and strategic implications of deploying nuclear power reactors, including large-scale plants, advanced small modular reactors (SMRs), and microreactors, in African countries. Case studies focus on South Africa, Egypt, Kenya, Ghana, and Nigeria, examining nuclear energy’s role in Africa’s rapidly evolving energy landscape, marked by fast-growing demand, significant electricity access gaps, increasing renewable penetration, and strong policy commitments to industrialization and energy security. Several U.S. reactor technologies and designs are considered based on their development status and readiness for deployment. The analysis finds that nuclear power can provide reliable, clean baseload and flexible generation, as well as high-temperature process heat for desalination, hydrogen production, and industrial applications. However, suitability is highly country-specific, depending on grid size and stability, transmission capacity, cooling water availability, regulatory readiness, and fuel supply chains. Near-term deployment opportunities are strongest for light-water reactors (such as NuScale, BWRX-300, AP300, and SMR-300) that use low-enriched uranium and build on proven technology. More advanced concepts, including gas-cooled, sodium-cooled, molten-salt cooled reactors, and microreactors, will likely be relevant for African deployment in the 2030s or later, contingent on demonstration projects, high-assay low-enriched uranium (HALEU) fuel availability, and mature international licensing frameworks. Economic analysis shows that SMRs are capital-intensive, with projected overnight costs for 300 MWe units in 2025 ranging from approximately 1.4 to 2.6 billion USD per module. The levelized cost of electricity (LCOE) is highly sensitive to the weighted average cost of capital (WACC). Given typically higher financing costs and utility balance-sheet weaknesses in many African countries, bankable project structures will require sovereign guarantees, robust offtake arrangements, and layered financing from export credit agencies, development finance institutions, and vendor nations. Comparisons with recent large nuclear projects in the United Arab Emirates (UAE) and Egypt underscore the central role of state-backed loans, long tenors, and concessional terms. Country case studies illustrate a spectrum of readiness and opportunity. South Africa operates two 920 MWe pressurized light water reactors (totaling 1,840 MWe) at Koeberg and has the most mature regulatory and industrial base, positioning it as a prime candidate for both large reactors and SMRs to replace coal, support desalination, and anchor industrial hubs. Egypt is constructing four VVER-1200 units at El Dabaa with strong state leadership and could later complement this fleet with SMRs for coastal and industrial applications. Kenya and Ghana are advancing through IAEA Milestones with growing institutional capacity and clear interest in SMRs that match their smaller grids and industrialization plans. Nigeria has the largest demand potential but faces acute constraints in grid reliability, project bankability, and regulatory capacity; targeted deployments of large reactors and SMRs near coastal or industrial sites could have high impact if accompanied by major grid upgrades and institutional reforms. The report identifies cross-cutting challenges such as financing, political continuity, public acceptance, nonproliferation and security, waste and back-end management, regulatory capacity, grid adequacy, and long deployment timelines for first-of-a-kind designs, and ANL/NSE-26/3 ii proposes broad directions for resolution. These include stronger multifaceted financing for nuclear, long-term national energy strategies that transcend electoral cycles, proactive stakeholder engagement, strengthened regional and national regulators, and systematic workforce development through centers of excellence and expanded training. The United States should develop partnerships with African countries and offer end-to-end nuclear package similar to those used effectively by competitors: coordinated project development, state-backed financing, long-term fuel services, and durable in-country support through regional offices and sustained workforce/regulatory training. With timely planning, sustained political commitment, and appropriate financing and institutional support, nuclear energy, both large reactors and advanced SMRs, can become a meaningful, though not dominant, pillar of Africa’s future power mix, enhancing energy security, enabling industrial growth, and supporting climate goals.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Electrical Load Forecasting Over Multihop Smart Metering Networks With Federated Learning

Electric load forecasting is essential for power management and stability in smart grids. This is mainly achieved via advanced metering infrastructure, where smart meters (SMs) record household energy data. Traditional machine learning (ML) methods are often employed for load forecasting, but require data sharing, which raises data privacy concerns. Federated learning (FL) can address this issue by running distributed ML models at local SMs without data exchange. However, current FL-based approaches struggle to achieve efficient load forecasting due to imbalanced data distribution across heterogeneous SMs. Here, this article presents a novel personalized FL (PFL) method for high-quality load forecasting in metering networks. A meta-learning-based strategy is developed to address data heterogeneity at local SMs in the collaborative training of local load forecasting models. Moreover, to minimize the load forecasting delays in our PFL model, we study a new latency optimization problem based on optimal resource allocation at SMs. A theoretical convergence analysis is also conducted to provide insights into FL design for federated load forecasting. Extensive simulations from real-world datasets show that our method outperforms existing approaches regarding better load forecasting and reduced operational latency costs.

Rahman, Ratun [Univ. of Alabama, Huntsville, AL (U↗

Feasibility Analyses for the Microgrid of the Mountain in the Cordillera Central Region of Puerto Rico

Distributed energy resource (DER) development can benefit communities through improvement of access to reliable electricity and a resilient energy system. Many place-specific considerations must be accounted for when designing electrical systems with co-located generation and loads. This paper presents an overview of four studies focusing on different aspects for regional DER development in the Cordillera Central region of Puerto Rico, including a grid and load stability study with the introduction of solar energy generation, microgrid design based on the solar resource in the area, resilience considerations during power outage scenarios, and qualitative risk aspects for components in the microgrid. Additionally, a conceptual substation microgrid analysis is conducted using the Microgrid Design Toolkit (MDT) to evaluate trade-offs between cost and energy availability, providing insights into optimal design strategies. A microgrid resilience assessment is performed using the Resilient Nodal Cluster Analysis Tool (ReNCAT) to identify critical loads and evaluates their accessibility during outages, emphasizing the importance of community needs. Finally, a qualitative risk assessment utilizing Hazard and Operability Analysis (HAZOP) methods highlights potential hazards and mitigations for microgrid components, ensuring robust system design and operation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Feature-Based PMU Event Classification under Variable PMU Participation and Overlapping Events

Danovo Energy Solution's presented its paper named: Feature-Based PMU Event Classification under Variable PMU Participation and Overlapping Events at the 2026 Georgia Tech Fault & Disturbance Analysis Conference. The full paper can be found at OSTI ID# 3169150 Paper Abstract—Phasor Measurement Units (PMUs) stream time synchronized, high-resolution measurements from the grid, enabling data-driven techniques for event detection and classification. Accurate event classification improves grid reliability and stability. Events can be detected by varying numbers of PMUs and exhibit different durations depending on the event type. This variability challenges standard classifiers that require uniform input sizes. Moreover, multiple events may coincide, which increases classification complexity. Standard classifiers assign each instance to the class with the highest predicted probability, whereas overlapping events may exhibit comparable probabilities across multiple classes. In this study, to handle data size variability, we extract a wide range of time–frequency domain features from all available PMUs for each event into a fixed-length vector, facilitating the application of standard machine learning classifiers, including Random Forest, XGBoost, LightGBM, Support Vector Machine, and Multilayer Perceptron. To account for overlapping events, a probabilistic post-processing step is applied. For a given data instance, if multiple predicted class probabilities exceed 30% and the differences between them are less than 10%, the event is assigned to multiple classes. Experiments using real-world PMU data demonstrate that the Random Forest and XGBoost models achieve the highest accuracy, while the proposed post-processing method yields perfect classification performance on external unseen test sets.

Nematirad, Reza [Danova Energy Solutions]↗

A Comprehensive Comparison of Methods for Evaluating Dispatch of Long-Duration Energy Storage in Power Systems Models

Long-duration energy storage (LDES) could play a pivotal role in the transformation of electricity grids with high shares of variable renewable energy (VRE) such as solar and wind. However, the weather-dependent nature of VRE introduces challenges for grid balancing and stability, which LDES - along with short-duration energy storage (SDES) - can help address. However, modeling LDES in production cost models (PCMs) is particularly challenging due to the need for high temporal resolution over extended optimization windows while preserving chronology, which ensures the alignment of energy storage operations with VRE generation over multi-day periods. This report compares traditional dispatch methods with advanced LDES dispatch strategies, such as the extended horizon approach, across different PCM platforms and examines tradeoffs and scalability. The comparison reveals that the traditional 1-day optimization horizon within the PCM leads to inefficient utilization of LDES. In contrast, extending the optimization horizon as much as possible significantly reduces curtailment and improves storage dispatch, especially in renewable-dense systems. There is also promise in using state-of-charge or end volume targets set by an external model, however this requires an additional modeling set and generally increases computational burden. This paper presents a comparison of these various methods in a number of power systems, showing algorithms initially in small test systems and scaling up to large, country-wide simulations. Overall, the research presents the trade-offs of various computational methods and illustrates how LDES may play an essential role in power systems of the future.

14 SOLAR ENERGY↗

Feature-Based PMU Event Classification under Variable PMU Participation and Overlapping Events

This paper is the basis for a presentation help at the 2026 Georgia Tech Fault & Disturbance Analysis Conference, which can be found at OSTI # 3168287 Paper Abstract—Phasor Measurement Units (PMUs) stream time synchronized, high-resolution measurements from the grid, enabling data-driven techniques for event detection and classification. Accurate event classification improves grid reliability and stability. Events can be detected by varying numbers of PMUs and exhibit different durations depending on the event type. This variability challenges standard classifiers that require uniform input sizes. Moreover, multiple events may coincide, which increases classification complexity. Standard classifiers assign each instance to the class with the highest predicted probability, whereas overlapping events may exhibit comparable probabilities across multiple classes. In this study, to handle data size variability, we extract a wide range of time–frequency domain features from all available PMUs for each event into a fixed-length vector, facilitating the application of standard machine learning classifiers, including Random Forest, XGBoost, LightGBM, Support Vector Machine, and Multilayer Perceptron. To account for overlapping events, a probabilistic post-processing step is applied. For a given data instance, if multiple predicted class probabilities exceed 30% and the differences between them are less than 10%, the event is assigned to multiple classes. Experiments using real-world PMU data demonstrate that the Random Forest and XGBoost models achieve the highest accuracy, while the proposed post-processing method yields perfect classification performance on external unseen test sets.

Nematirad, Reza [Danovo Energy Solutions]↗