Search NASA⌕ Search

SEARCH · Search NASA

Results for “WECC”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 145 records · Page 8

Communication enabled – fast acting imbalance reserve (CE-FAIR)

This letter presents a new frequency control strategy that takes advantage of communications and fast responding resources like PV generation, energy storage, wind generation, and demand response, termed collectively as converter interfaced generators (CIGs). The proposed approach uses an active monitoring of power imbalances to rapidly redispatch CIGs. This approach differs from previously proposed frequency control schemes in that it employs feed-forward control based on a measured power imbalance rather that relying on a frequency measurement. As a result, time-domain simulations of the full Western Electricity Coordinating Council (WECC) system are conducted to demonstrate the effectiveness of the proposed method, showing improved performance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Calibrating Parameters of Power System Stability Models Using Advanced Ensemble Kalman Filter

With the ever increasing penetration of renewable energy, smart loads, energy storage, and new market behavior, today's power grid becomes more dynamic and stochastic, which may invalidate traditional study assumptions and pose great operational challenges. Thus, it is of critical importance to maintain good-quality models for secure and economic planning and real-time operation. Following the 1996 Western Systems Coordinating Council (WSCC) system blackout, North American Electric Reliability Corporation (NERC) and Western Electricity Coordinating Council (WECC) in North America enforced a number of policies and standards to guide the power industry to periodically validate power grid models and calibrate poor parameters with the goal of building sufficient confidence in model quality. The PMU-based approach using online measurements without interfering with the operation of generators provides a low-cost alternative to meet NERC standards. This paper presents an innovative procedure and tool suites to validate and calibrate models based on a trajectory sensitivity analysis method and an advanced ensemble Kalman filter algorithm. The developed prototype demonstrates excellent performance in identifying and calibrating bad parameters of a realistic hydro power plant against multiple system events.

Huang, Renke (ORCID:0000000230947073)↗

Frequency Response Assessment and Enhancement of the U.S. Power Grids towards Extra-High Photovoltaic Generation Penetrations – an Industry Perspective

Nonsynchronous generations such as photovoltaics (PVs) are expected to undermine bulk power systems (BPSs)' frequency response at high penetration levels. Though the underlying mechanism has been relatively well understood, the accurate assessment and effective enhancement of the U.S. interconnections, frequency response under extra-high PV penetration conditions remains an issue. In this paper, the industry-provided full-detail interconnection models were further validated by synchrophasor frequency measurements and realistically-projected PV geographic distribution information were used to develop extra-high PV penetration scenarios and dynamic models for the three main U.S. interconnections, including Eastern Interconnection (EI), Western Electricity Coordinating Council (WECC), and Electric Reliability Council of Texas (ERCOT). Up to 65% instantaneous PV and 15% wind penetration were simulated and the frequency response change trend of each U.S. interconnection due to the increasing PV penetration level were examined. Most importantly, the practical solutions to address the declining frequency response were discussed. This paper will provide valuable guidance for policy makers, utility operators and academic researchers not only in the U.S. but also other countries in the world.

14 SOLAR ENERGY↗

Optimal Black Start Allocation for Power System Restoration

Equipment failures, operator errors, natural disasters and cyber-attacks can and have caused extended blackouts of the electric grid. Even though such events are rare, preparedness for them is critical because extended power outages endanger human lives, compromise national security, or result in economic losses of billions of dollars. Since most of the generating units cannot restart without connecting to an energized grid, the system operator relies on a few units with the ability to start autonomously, called Black Start (BS) units, to restore the power system. Allocating and maintaining these units is costly and can severely impact the restoration security and time. We formulate an optimization problem to optimally allocate BS units in the grid, while simultaneously optimizing over the restoration sequence. We extend existing optimal allocation models by including grid considerations such as active power nodal balance, transmission switching, nodal reactive power support and voltage limits. In order to aid the branch and bound tree that solves the resulting large scale mixed integer program, we propose a randomized heuristic that is executed multiple times in parallel on a high-performance computing environment to find feasible solutions. Here, we proceed to solve the IEEE-39, the IEEE-118, and a simplified WECC system with 225 nodes and 136 generators to near optimality.

97 MATHEMATICS AND COMPUTING↗

PMU-Based Monitoring and Mitigation of Delayed Voltage Recovery Using Admittances

This project analyzes the delayed voltage recovery phenomenon by simplifying the Western Electricity Coordinating Council (WECC) composite load model using the load admittance and the thermal relay dynamics. From this analysis, a closed form expression approximating the recovery time is derived and the key load parameters impacting the behavior of voltage recovery are identified. A monitoring scheme based on the measured load admittance is then proposed to detect the onset of stalling, even in the presence of voltage oscillations, and estimate the duration of the delayed voltage recovery. A mitigation scheme utilizing smart thermostats and offline learning is also derived to ensure that the voltage recovers to the pre-contingency voltage within a specified time. Both the monitoring and mitigation schemes only need local measurements at a substation making them promising for online applications. Results for the monitoring and mitigation schemes are described in detail for the IEEE 162 bus system validating the various assumptions used for the analysis and establishing the connection between the delayed voltage recovery phenomenon and load admittance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Approximate Latent Factor Algorithm for Scenario Selection and Weighting in Transmission Expansion Planning

One major difficulty in transmission expansion planning is selecting the representative scenarios to use to evaluate candidate transmission networks. The variability in demand and renewable generation makes the inclusion of several scenarios critical when calculating reliability and cost, but including too many scenarios in an optimization is computationally intractable. To reduce the number of representative operating conditions needed to obtain an accurate approximation of the system, we propose a method rooted in multivariate statistics that exploits the latent correlative structure between different scenarios and network configurations. The proposed algorithm includes an objective and rigorous way to select a subset of scenarios that provide as much information about the system as possible, and a method to accurately approximate the system cost from that scenario subset. The result is a set of scenarios and weights that are easily incorporated into traditional transmission expansion planning formulations. We apply this to a 312-bus WECC model with 8,736 distinct operating conditions. The transmission plans found with the proposed method are more reliable and have a lower total cost than those from other scenario reduction techniques, as well as a smaller error between the expected system performance from the optimization objective and the actual system performance.

42 ENGINEERING↗

A Homotopy-Based Method for Robust Computation of Controlling Unstable Equilibrium Points

This paper proposes a homotopy-based method for efficiently computing and precisely determining controlling unstable equilibrium points (CUEPs) in transient stability analysis and screening using direct methods. The proposed method is intended to overcome potential numerical convergence problems associated with computing CUEPs. These convergence problems are mostly due to irregularities in the region of convergence of CUEPs which make it difficult to determine suitable initial points. The most commonly used initial points in computing CUEPs are minimum gradient points (MGPs) on the stability boundary which in turn rely on the determination of exit points (EPs-points at which sustained-fault trajectories exit system stability boundaries). However, determination of MGPs and EPs are computationally involved and sophisticated numerical methods have been introduced such as stability-boundary-following procedure and shadowing method to correct the solution trajectory. The proposed method does not depend on MGPs and also does not require accurate EPs. The proposed method maps the solution from EPs to the CUEPs. The proposed method is applied on several known systems including the NE 39 bus system and the reduced WECC system and the results are provided. The results are compared with the traditional methods such as Boundary of stability region based CUEP method (BCU method).

42 ENGINEERING↗

Robust System Separation Strategy Considering Online Wide-Area Coherency Identification and Uncertainties of Renewable Energy Sources

With the fast growth of renewable energy sources (RES), more and more uncertainties are involved and influencing the stable operation of power systems. Controlled islanding is the last measure to prevent power system blackouts, thus this paper aims to propose a novel model of system separation based on Online Coherency Identification and Adjustable Robust Optimization Programming (OCI-AROP) for minimizing load shedding considering the uncertainties of RES. First, Fuzzy C-Means (FCM) clustering method with F-statistics is utilized to identify the coherent generator groups with the frequency data measured by Phasor Measurement Units (PMUs). Then, the OCI-AROP model considering coherent group constraints, connectivity constraints and robustness constraints about RES are presented. Finally, the case studies on IEEE-39 bus system and WECC-179 bus system are employed to demonstrate the effectiveness of the proposed OCI-AROP model, and comparisons among the OCI-AROP model and the other models are also given to show its superiority.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Forced Oscillation Source Location of Bulk Power Systems Using Synchrosqueezing Wavelet Transform

Forced oscillation source location (FOSL) plays a significant role in mitigating forced oscillations (FOs), which threaten the power system stability. Here, this paper proposes a data-driven approach for FOSL in power systems using synchrosqueezing wavelet transform (SWT). The proposed approach conducts SWT on the measured system responses to obtain the SWT matrix. Then, the SWT-based dissipating energy flow (DEF) model in time-frequency domain and dissipating energy spectrum (DES) model in frequency domain are derived from the traditional DEF model. Further, the characteristics of SWT-based DEF and DES are revealed by referring to the traditional DEF, and the FOSL criteria of the SWT-based DEF and DES can be hereby obtained. Using the obtained FOSL criteria, the FO source can be located from the measured responses. The performance of the proposed FOSL method is evaluated by simulation data of the WECC 179-bus test system and field-measurement PMU data of the ISO New England. The results confirm the accuracy and efficiency of the proposed method in the FOSL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Forced Oscillation Source Location in Power Systems Using MVMD-assisted DEF in TF Plane

Fast and accurate forced oscillation source location (FOSL) is critical for mitigating forced oscillations in power systems. Here, to overcome the shortcomings of traditional dissipating energy flow (DEF) in decomposing the forced oscillation components from the measurement responses, a multivariate variational mode decomposition (MVMD)-assisted FOSL is proposed in this paper to locate the forced oscillation sources from measurements in time-frequency (TF) plane. The multi-channel measurement matrix of each generator is formed, then the multi-channel modes are decomposed from the formed multi-channel measurement matrix using the MVMD. Further, the intrinsic mode functions (IMFs) associated with the forced oscillation mode are distinguished from the decomposed modes according to the relative energy weights. With the distinguished IMFs, the MVMD-assisted DEF calculation method is developed to locate the forced oscillation source. Finally, the performance of the proposed method is evaluated using the simulation data of the WECC 179-bus test system and IEEE-NASPI Oscillation Source Location Contest as well as the actual PMU data of ISO New England. The results validated the effectiveness and accuracy of the proposed method in the FOSL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Data-Driven Event Detection of Power Systems Based on Unequal-Interval Reduction of PMU Data and Local Outlier Factor

With the deployment of phasor measurement units (PMU) and wide area measurement system (WAMS), it is feasible to have an insight into the events occurred in power systems based on measured data. Thus, a novel data-driven algorithm based on local outlier factor (LOF) is proposed in this work to detect and locate events in power systems using reduced PMU data. First, the unequal-interval reduction method is presented to reduce the scale of PMU data in sub-stations and reconstruct it in master station of WAMS, which can relieve the burden of communication systems. Then, principle component analysis (PCA)-based similarity search method is proposed to measure the differences of operation state between any two buses. Next, LOF is presented to detect the abnormal events in power systems, and employed to determine the region of the event source. Finally, six cases from the Western electricity coordinating council (WECC) 179-bus power system, a case from the South China power system (SCPS), and a case from the Guangdong power system (GDPS) are utilized to demonstrate the effectiveness of the proposed algorithm. Overall, the results show that proposed algorithm is effective and can be applied to event detection, event location, and online monitoring, which can enhance the situation awareness ability of power system operators.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Time Series Classification for Locating Forced Oscillation Sources

Here, this article presents a machine learning based time-series classification method for using synchrophasor measurements to locate the source of forced oscillation (FO) for fast disturbance removal. First, multivariate time series (MTS) matrices are constructed by the most informative measurements selected by sequential feature selection from each power plant. Then, the Mahalanobis matrix is trained such that the Mahalanobis distance between the MTSs from the same class (i.e., with the same FO source location) are minimized and from different classes (i.e., with different FO source locations) are maximized. This allows MTSs to be classified by classifiers with class membership corresponding to the location of each FO source. To meet the runtime requirements of online matching, class templates are constructed to reduce data size and improve matching efficiency. To account for uncertainty in identifying the exact beginning of an FO event, dynamic time warping is used to align the out-of-sync MTSs. IEEE 39bus and WECC 179bus systems are used for algorithm development and validation. Simulation results demonstrate that the algorithm meets online operation runtime requirement with high accuracy using misaligned data sets.

42 ENGINEERING↗

Sizing Energy Storage to Accommodate High Penetration of Variable Energy Resources

Abstract—The variability and non-dispatchable nature of wind and solar energy production presents substantial challenges for maintaining system balance. Depending on the economic considerations, energy storage can be a viable solution to balance energy production with consumption. This paper proposes to use discrete Fourier transform to decompose the required balancing power into different time-varying periodic components, i.e., intra-week, intra-day, intra-hour, and real-time. Each component can be used to quantify the maximum energy storage requirement for different types of energy storage. This requirement is the physical limit that could be theoretically accommodated by a power system. The actual energy storage capacity can be further quantified within this limit by the cost-benefit analysis (future work). The proposed approach has been successfully used in a study conducted for the 2030 Western Electricity Coordinating Council (WECC) system model. Some results of this study are provided in this paper.

Makarov, Yuri V.↗

Synchrophasor Measurements-based Events Detection Using Deep Learning

Deep learning algorithms have been developed for phasor measurement units (PMUs) analysis aiming at providing grid operators to observe and react to significant real-time changes in the grid associated with multiple factors (e.g., power generation and load variations, different type of faults, and equipment mailfunction), or for offline post-event system diagnostics. In this study, a Long Short-Term Memory (LSTM)-based deep neural network (DNN) is adopted and evaluated to identify the most appropriate model configurations for event detection and longer-term anomalous pattern extraction. The proposed DNN model shows the potential on long-term predictions with the ability to capture nonlinear and nonstationary mixture complex patterns in PMU datasets. Real-world PMU in the WECC system were used for model development and validation.

deep learning↗

Open-Source Ambient-Signal-Based Inertia Monitoring Tool for Power systems [SWR-25-59]

This script, developed by NREL, implements an inertia estimation algorithm using a sliding window approach. The inertia (H) is estimated based on frequency deviations and active power deviations, utilizing the swing equation from power system dynamics. An example application is provided using the WECC 240-bus system.

Peng, Jiangkai [National Renewable Energy Laborato↗

Impact of simultaneous activities on frequency fluctuations — comprehensive analyses based on the real measurement data from FNET/GridEye

Simultaneous human activities such as the Super Bowl game would cause certain impacts on frequency fluctuations in power systems. With the help of FNET/GridEye measurements, this work aims to give comprehensive analyses on the frequency fluctuations during Super Bowl LIV held on Feb. 2, 2020, so as to better understand several phenomena caused by simultaneous activities and help system operation and control. First, recent developments of FNET/GridEye are introduced briefly. Second, the frequency fluctuations of Eastern Interconnection (EI), western electricity coordinating council (WECC), and electric reliability council of Texas (ERCOT) power systems during Super Bowl LIV are analyzed. Third, frequency fluctuations of Super Bowl Sunday and ordinary Sundays in 2020 are compared. Finally, the differences of frequency fluctuations among different years during the Super Bowl and their change trend are also given. Furthermore, several possible explanations including the simultaneity of electricity consumption at the beginning of commercial breaks and the halftime show, the increasing usage of the Internet, and the increasing size of TV screens are illustrated in detail in this work.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Algorithm Summary and Evaluation: Automatic Implementation of Ringdown Analysis for Electromechanical Mode Identification from Phasor Measurements

Small signal stability problems are one of the major threats to grid stability and reliability. Prony analysis has been successfully applied on ringdown data to monitor electromechanical modes of a power system using phasor measurement unit (PMU) data. To facilitate an on-line application of mode estimation, this paper develops a recursive algorithm for implementing Prony analysis and proposed an oscillation detection method to detect ringdown data in real time. By automatically detecting ringdown data, the proposed method helps guarantee that Prony analysis is applied properly and timely on the ringdown data. Thus, the mode estimation results can be performed reliably and timely. The proposed method is tested using Monte Carlo simulations based on a 17-machine model and is shown to be able to properly identify the oscillation data for on-line application of Prony analysis. In addition, the proposed method is applied to field measurement data from WECC to show the performance of the proposed algorithm.

24 POWER TRANSMISSION AND DISTRIBUTION↗

SCENARIOS FOR MEETING CALIFORNIA'S 2050 CLIMATE GOALS California's Carbon Challenge Phase II Volume I: Non-Electricity Sectors and Overall Scenario Results

This study provides an updated analysis of long-term energy system scenarios for California consistent with the State meeting its 2050 climate goal, including detailed analysis and assessment of electricity system build-out, operation, and costs across the Western Electricity Coordinating Council (WECC) region. Four key elements are found to be critical for the State to achieve its 2050 goal of 80 percent greenhouse (GHG) reductions from the 1990 level: aggressive energy efficiency; clean electricity; widespread electrification of passenger vehicles, building heating, and industry heating; and large-scale production of low-carbon footprint biofuels to largely replace petroleum-based liquid fuels. The approach taken here is that technically achievable energy efficiency measures are assumed to be achieved by 2050 and aggregated with the other key elements mentioned above to estimate resultant emissions in 2050. The energy and non-energy sectors are each assumed to have the objective of meeting an 80 percent reduction from their respective 1990 GHG levels for the purposes of analysis. A different partitioning of energy and non-energy sector GHG greenhouse reductions is allowed if emission reductions in one sector are more economic or technically achievable than in the other. Similarly, within the energy or non-energy sectors, greater or less than 80 percent reduction from 1990 is allowed for sub-sectors within the energy or non-energy sectors as long as the overall target is achieved. Overall emissions for the key economy-wide scenarios are considered in this report. All scenarios are compliant or nearly compliant with the 2050 goal. This finding suggests that multiple technical pathways exist to achieve the target with aggressive policy support and continued technology development of largely existing technologies.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗