HOPE (Hybrid and Optimized Energy and Power Management for DC Distributed EV Charging Hubs) [SWR-25-22]
HOPE is an MPC-based, optimized and robust controller algorithm developed for the energy and power management of DC distributed EV charging hubs.
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
HOPE is an MPC-based, optimized and robust controller algorithm developed for the energy and power management of DC distributed EV charging hubs.
Maintaining electric power system stability is paramount, especially in extreme contingencies involving unexpected outages of multiple generators or transmission lines that are typical during severe weather events. Such outages often lead to large supply-demand mismatches followed by subsequent system frequency deviations from their nominal value. The extent of frequency deviations is an important metric of system resilience, and its timely mitigation is a central goal of power system operation and control. This paper develops a novel nonlinear model predictive control (NMPC) method to minimize frequency deviations when the grid is affected by an unforeseen loss of multiple components. Our method is based on a novel multi-period alternating current optimal power flow (ACOPF) formulation that accurately models both nonlinear electric power flow physics and the primary and secondary frequency response of generator control mechanisms. We develop a distributed parallel Julia package for solving the large-scale nonlinear optimization problems that result from our NMPC method and thereby address realistic test instances on existing high-performance computing architectures. Our method demonstrates superior performance in terms of frequency recovery over existing industry practices, where generator levels are set based on the solution of single-period classical ACOPF models.
This work is the first of a two-part series that develops and experimentally demonstrates a first-of-its-kind hierarchical control solution for optimally dispatching thousands of deferrable loads and distributed energy resources (DERs) across a distribution feeder to provide fast frequency response (FFR) within 500 ms to the bulk power system. This approach rapidly coordinates resources online after a frequency event occurs, allowing fast-changing, behind-the-meter (BTM) resources to be incorporated and aggregate FFR power set points to be achieved more quickly and accurately than existing approaches. We also present a solution for determining the optimal amount of headroom to operate solar inverters with to minimize opportunity cost while ensuring the FFR response viability of a building with the inverter and deferrable loads. In Part I, we develop practical algorithms for fast, cost-based optimal dispatch at multiple aggregation scales (single building, multiple buildings, and full distribution feeder), establish their optimality, and demonstrate via simulation that they are faster than state-of-the-art, coordinated frequency response approaches. In Part II, the entire platform is implemented and experimentally verified using a unique power hardware-in-the-loop demonstration, including more than 100 powered loads and DERs connected to a real-world distribution network model and over 10,000 net-load resources dispatched.
This paper presents performance evaluation of a new distributed energy resource management system (DERMS) algorithm via an advanced hardware-in-the-loop (HIL) platform. The HIL platform provides realistic testing in a laboratory environment, including the accurate modeling of sub-transmission and distribution networks, the DERMS software controller, and 84 power hardware solar photovoltaic (PV) inverters, standard communication protocols, and a capacitor bank controller. The DERMS algorithm is also called, Grid-Optimization of Solar (GO-Solar) platform which includes predictive state estimation (PSE) and online multiple objective optimization (OMOO) to dispatch the legacy devices and distributed energy resources (e.g., PV). The voltage regulation performance is evaluated under three scenarios, volt-var smart inverter (baseline), and DERMS control for 100% and 30% of PV. The results show that controlling 30% of PV systems with the GO-Solar platform may provide the best balance of control performance and implementation cost.
Grid operators are now considering using distributed energy resources (DERs) to provide distribution voltage regulation rather than installing costly voltage regulation hardware. DER devices include multiple adjustable reactive power control functions, so grid operators have the difficult decision of selecting the best operating mode and settings for the DER. In this work, we develop a novel state estimation-based particle swarm optimization (PSO) for distribution voltage regulation using DER-reactive power setpoints and establish a methodology to validate and compare it against alternative DER control technologies (volt–VAR (VV), extremum seeking control (ESC)) in increasingly higher fidelity environments. Distribution system real-time simulations with virtualized and power hardware-in-the-loop (PHIL)-interfaced DER equipment were run to evaluate the implementations and select the best voltage regulation technique. Each method improved the distribution system voltage profile; VV did not reach the global optimum but the PSO and ESC methods optimized the reactive power contributions of multiple DER devices to approach the optimal solution.
Distributed Energy Resources (DER) have great potential to enhance the operation of electric power distribution systems. Previously, we explored the use of 2 Dimensional Extremum Seeking (2D-ES) control algorithms to enable model-free optimal control of DER to provide grid services to both the distribution and transmissions systems. Motivated by preliminary deployments of DER managed by 2D-ES algorithms in hardware-in-the-loop tests and in operational distribution grids, in this work, we extend the control scheme to accommodate communication delays and information loss. We propose a modification to the 2D-ES scheme to allow for the processing of batches of possibly noncontiguous objective function measurements at unknown and possibly uneven intervals. We provide a proof of the convergence of the batch 2D-ES (2D-BES) scheme when optimizing a generic convex objective function, as well as simulation results that demonstrate the suitability of the approach for substation active and reactive power target tracking.
Large-scale integration of renewables in power systems gives rise to new challenges for keeping synchronization and frequency stability in volatile and uncertain power flow states. To ensure the safety of operation, the system must maintain adequate disturbance rejection capability at the time scales of both rotor angle and system frequency dynamics. This calls for flexibility to be exploited on both the generation and demand sides, compensating volatility and ensuring stability at the two separate time scales. This article proposes a hierarchical power flow control architecture that involves both transmission and distribution networks as well as individual buildings to enhance both small-signal rotor angle stability and frequency stability of the transmission network. The proposed architecture consists of a transmission-level optimizer enhancing system damping ratios, a distribution-level controller following transmission commands and providing frequency support, and a building-level scheduler accounting for quality of service and following the distribution-level targets. Furthermore, we validate the feasibility and performance of the whole control architecture through real-time hardware-in-loop tests involving real-world transmission and distribution network models along with real devices at the Stone Edge Farm Microgrid.
Building cluster control has emerged as a promising approach for enabling flexible and coordinated operation of distributed building systems, yet its transition from pilot demonstrations to routine grid-interactive operation remains limited. This paper argues that this gap cannot be explained by control algorithms alone. Instead, it arises from interacting barriers in communication infrastructure, data and semantic interoperability, uncertainty management, stakeholder participation, market design, and policy support. Accordingly, the paper reviews both technical and non-technical barriers to building cluster control. Technical challenges include heterogeneous devices and protocols, communication latency and reliability, distributed decision-making, and uncertainty propagation across aggregated loads. Non-technical barriers include user participation, stakeholder coordination, incentive allocation, and data governance. Existing solution approaches are synthesized, including semantic interoperability frameworks, edge and hierarchical communication architectures, distributed and transactive control strategies, uncertainty-aware optimization, policy mechanisms, and market reforms. Based on this analysis, two research directions are identified: testing infrastructures that can evaluate control performance under realistic multi-building conditions, and abstraction methods that allow building clusters to interact with other energy sectors through standardized flexibility representations. Overall, the paper provides a structured review of how building cluster control can move from isolated demonstrations toward reproducible, market-compatible, and grid-relevant implementation.
A solid state power substation (SSPS) node is a microgrid that integrates distributed energy resources and loads and injects/absorbs power to/from the SSPS distribution network. It is an essential building block of a futuristic distribution grid network. This paper presents the development and demonstration of optimization use cases of a SSPS DC node. By adopting multi-layer hierarchical control architecture and developing automatic device identification and dynamic optimization formulation algorithms, the SSPS DC node can perform plug-and-play resource integration and seamless transition of the optimized node operation under on and off grid condition without sophisticated algorithms, control mode changes, and user interactions. Four optimization use cases including economic dispatches with price signal changes, a sudden PV power drop, and a single directional meter and its associated costs with sending power back to the grid, and resiliency under a grid inverter trip condition were demonstrated through the real-time controller hardware-in-the-loop simulation.
This paper proposes an online adaptive data-driven distributed energy resource (DER) dispatch optimization method for voltage control considering topology changes. By using a local sensitivity factor (LSF)-enabled voltage control, traditional DER control can be reformulated into a linear programming (LP) problem, leading to faster computation speeds. Power injection alteration and topology changes are two common operational changes in the distribution network that can affect the LSF and voltage control performance. To address this issue, a robust estimation method is developed to adjust the sensitivity matrix at each time step for the time-varying power injection changes. When topology changes occur, only the allocated predominant LSF submatrices are updated based on measurement data, allowing for a fast adaptation to the system reconfiguration. Results obtained from a real distribution feeder in Southern California demonstrate its robustness as compared to traditional volt-var control and constant LSF matrix dispatch control methods.
With the proliferation of distributed energy resources (DERs) in the distribution grid, it is a challenge to effectively control a large number of DERs resilient to the communication and security disruptions, as well as to provide the online grid services, such as voltage regulation and virtual power plant (VPP) dispatch. To this end, a hybrid feedback-based optimization algorithm along with deep learning forecasting technique is proposed to specifically address the cyber-related issues. The online decentralized feedback-based DER optimization control requires timely, accurate voltage measurement from the grid. However, in practice such information may not be received by the control center or even be corrupted. Therefore, the long short-term memory (LSTM) deep learning algorithm is employed to forecast delayed/missed/attacked messages with high accuracy. The IEEE 37-node feeder with high penetration of PV systems is used to validate the efficiency of the proposed hybrid algorithm. The results show that 1) the LSTM-forecasted lost voltage can effectively improve the performance of the DER control algorithm in the practical cyber-physical architecture; and 2) the LSTM forecasting strategy outperforms other strategies of using previous message and skipping dual parameter update.
As feeder-level microgrid controls begin to incorporate multiple GFM DER and voltage regulation equipment, island reactive power dispatch strategies can be improved. Although Volt-Var Optimization (VVO) control is typical in an Advanced Distribution Management System (ADMS), most microgrid controllers do not apply VVO during island operations. This report investigates reactive power control strategies for feeder-level microgrid operations. It also proposes evaluation metrics that can be applied to analyze the performance improvements of the new microgrid control strategy.
Volt-VAR control (VVC) is crucial in active distribution networks for optimizing voltage profiles and minimizing network losses. While traditional deep reinforcement learning (DRL) algorithms exhibit promise for VVC, they often require extensive computational resources to handle such a high-dimensional problem. As a potential solution, quantum reinforcement learning (QRL) algorithms integrate the computational capabilities of quantum computing into the DRL framework. However, existing QRL algorithms struggle with complex VVC problems due to the limitations of current quantum hardware. To bridge this gap, this paper proposes an innovative QRL algorithm featuring an end-to-end architecture that integrates a classical autoencoder, variational quantum circuits (VQCs), and classical post-processing layers. This design efficiently compresses high-dimensional grid states, enabling VQCs to leverage quantum advantages while producing multiple control device outputs tailored for VVC tasks. Numerical studies on three representative distribution systems verify the effectiveness and scalability of the proposed QRL algorithm, and demonstrate its enhanced performance over classical approaches with only approximately 1% of the parameters. Additionally, the robustness of our developed algorithm is validated through noisy quantum environments.
Buildings, as major energy consumers, can provide great untapped demand response (DR) resources for grid services. However, their participation remains low in real-life. One major impediment for popularizing DR in buildings is the lack of cost-effective automation systems that can be widely adopted. Existing optimization-based smart building control algorithms suffer from high costs on both building-specific modeling and on-demand computing resources. To tackle these issues, this paper proposes a cost-effective edge-cloud integrated solution using reinforcement learning (RL). Beside RL’s ability to solve sequential optimal decision-making problems, its adaptability to easy-to-obtain building models and the off-line learning feature are likely to reduce the controller’s implementation cost. Using a surrogate building model learned automatically from building operation data, an RL agent learns an optimal control policy on cloud infrastructure, and the policy is then distributed to edge devices for execution. Simulation results demonstrate the control efficacy and the learning efficiency in buildings of different sizes. A preliminary cost analysis on a 4-zone commercial building shows the annual cost for optimal policy training is only 2.25% of the DR incentive received. Results of this study show a possible approach with higher return on investment for buildings to participate in DR programs.
In the transactive energy (TE) paradigm, the devices of participative consumers, or prosumers, may be aggregated and employed to drive operational objectives at the network level. Home heating, ventilation and air-conditioning (HVAC) systems in particular are well-suited to modulate their behaviours based on both home thermal flexibility and requests from the utility grid. This paper develops a robust, hierarchical power dispatch scheme in the context of a residential distribution network. The formulation couples a unique, multiphase linear distribution optimal power flow (OPF) at the upper level with model predictive control (MPC)-based HVAC fleet controllers at the lower level. The proposed approach is tested on nearly 2000 homes with a three-phase distribution network in an intraday market setting, where two major applications are explored and analysed.
Reactor designs with mixed catalysts play an important role in transforming a multiple reactor system to single-shot reactors. In addition to savings in capital and ease of implementation, single-shot reactors are useful to break equilibrium limitations, thereby increasing the yield and selectivity of desired product as shown in previous studies. However, the nonlinear and highly exothermic nature of mixed-catalyst systems makes it difficult for commercial process simulation and optimization tools to optimize these systems. This study describes the development and application of optimization strategies for mixed-catalyst, single-shot reactors for syngas to olefin (STO) processes. Finding the optimal catalyst distribution is challenging and requires advanced solution strategies for singular optimal control problems, which are poorly conditioned and often lead to flat response surfaces. The graded bed and partial-moving finite-element approaches are used to find the optimal catalyst distribution that maximizes the olefins yield. A 1.3% increase in the yield is observed from one zone to three zones. The yield further improves from three zones to the exact infinite dimensional solution by 0.2%. This improvement can be realized in practice by changing only the catalyst distribution, without any extra investment. Lastly, the results suggest that a mixed-catalyst single shot reactor bed can be applied to other reaction mechanisms to increase reactor performance.
Active distribution networks are being challenged by frequent and rapid voltage violations due to renewable energy integration. Conventional model-based voltage control methods rely on accurate parameters of the distribution networks, which are difficult to achieve in practice. This paper proposes a novel physical-model-free two-timescale voltage control framework for active distribution systems. To achieve fast control of PV inverters, the whole network is first partitioned into several subnetworks using voltage-reactive power sensitivity. Then, the scheduling of PV inverters in the multiple sub-networks is formulated as Markov games and solved by a multi-agent soft actor-critic (MASAC) algorithm, where each subnetwork is modeled as an intelligent agent. All agents are trained in a centralized manner to learn a coordinated strategy while being executed based on only local information for fast response. For the slower time-scale control, OLTCs and switched capacitors are coordinated by a single agent-based SAC algorithm using the global information with considering control behaviors of the inverters. Particularly, the two-level agents are trained concurrently with information exchange according to the reward signal calculated from the data-driven surrogate model. Comparative tests with different benchmark methods on IEEE 33-and 123-bus systems and 342-node low voltage distribution system demonstrate that the proposed method can effectively mitigate the fast voltage violations and achieve systematical coordination of different voltage regulation assets without the knowledge of accurate system model.