Voltage Regulation Operational Strategies
These posters describe results of the VROS project between HECO and NREL showing the impacts to the utility and to the solar customer of different grid support functions.
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
These posters describe results of the VROS project between HECO and NREL showing the impacts to the utility and to the solar customer of different grid support functions.
This paper proposes a new distributed model-free control (MFC) strategy for dynamic voltage control to diminish distribution systems' voltage violations. The objective is to maintain all critical load bus voltages within the acceptable ANSI Range A (+/- 5% of nominal). The distributed MFC strategy, which only requires local voltage measurements from designated load buses, controls online the reactive power generation of available synchronous generator (SG)-based and photovoltaic (PV)-based distributed generators (DGs). The distributed MFC strategy is computationally efficient and does not require modelling of the different system components and disturbances. Time-domain dynamic simulations are conducted for the 21-bus test distribution system fed by multiple DGs to verify the performance of the proposed MFC strategy, and the results are compared against the conventional model-based microgrid voltage stabilizer (MGVS) control strategy. The simulation results show that the distributed MFC strategy provides minimal voltage violations and achieves the dynamic voltage stability of the system under diverse disturbances.
Renewable portfolio standards are targeting high levels of variable solar photovoltaics (PV) in electric distribution systems, which makes reliability more challenging to maintain for distribution system operators (DSOs). Distributed energy resources (DERs), including smart, connected appliances and PV inverters, represent responsive grid resources that can provide flexibility to support the DSO in actively managing their networks to facilitate reliability under extreme levels of solar PV. This flexibility can also be used to optimize system operations with respect to economic signals from wholesale energy and ancillary service markets. Here, we present a novel hierarchical scheme that actively controls behind-the-meter DERs to reliably manage each unbalanced distribution feeder and exploits the available flexibility to ensure reliable operation and economically optimizes the entire distribution network. Each layer of the scheme employs advanced optimization methods at different timescales to ensure that the system operates within both grid and device limits. The hierarchy is validated in a large-scale realistic simulation based on data from the industry. Simulation results show that coordination of flexibility improves both system reliability and economics, and enables greater penetration of solar PV. Discussion is also provided on the practical viability of the required communications and controls to implement the presented scheme within a large DSO.
In the last decades, modem grids with distributed energy resources, such as photovoltaic (PV) farms, are increasingly vulnerable to cyber-attacks that seriously affect the stability and performance of the power system. While cyber-physical security of smart grids is extensively studied, most of the existing work focuses on the grid level and neglects the modeling and features of device-level power electronics converters (PECs). Furthermore, establishing a high-fidelity simulation testbed that can simulate harmonic frequencies of the PV farm is in urgent need. In this paper, a high-fidelity and real-time hardware-in- the-loop testbed is built to simulate the harmonics of power electronics converters for cyber-physical security of PEC-enabled PV farms. Based on this testbed, the impact of typical cyber-attacks and physical faults on the PV converter can be analyzed, thus providing a foundation for cyber-attack detection, root cause diagnosis, and resilient control to mitigate the adverse effects of cyber-attacks.
Abstract not provided.
Abstract not provided.
Here, we report on the optimization of in situ passivation of ink-based CuIn(S,Se) 2 thin-film solar cells via controlled incorporation of Al 2 O 3 in CuIn(S,Se) 2 films by the addition of Al(NO 3 ) 3 to the molecular ink precursor. For this purpose, the Al/(Al + In) (AAI) metal ratio was varied from 0.05 to 0.30. We observe that the efficiency of the cells made of Al 2 O 3 -incorporated CuIn(S,Se) 2 is consistently higher than those without Al 2 O 3 , especially due to an improvement in open-circuit voltage (V OC ) and fill factor (FF), for all tested AAI ratios. With an AAI of 0.05, a maximum efficiency of 11.2% and an average efficiency of 8.5% (measured across 18 cells) was achieved, compared to 8.5% maximum efficiency and 6.5% average efficiency for Al-free CuIn(S,Se) 2 . Furthermore, we find that cells made of Al 2 O 3 -incorporated CuIn(S,Se) 2 with an AAI of 0.2 show a narrow distribution in the photovoltaic performance, indicating higher reproducibility and higher FF. Energy-dispersive X-ray spectroscopy shows that, at AAI = 0.2, Al 2 O 3 is distributed more homogeneously at the surface of the Al 2 O 3 -incorporated CISSe. Capacitance-voltage measurements reveal a reduced defect density by incorporation of Al 2 O 3 , which could be partly responsible for the higher V OC . Furthermore, using detailed surface analysis with various X-ray and electron spectroscopy methods, we derive chemical and electronic structure information from the surface. With ultraviolet photoelectron (UPS) and inverse photoemission spectroscopies (IPES), the electronic band gap of the CuIn(S,Se) 2 thin-film surface is found to increase from 1.22 to 1.88 eV (+-0.12 eV) with Al 2 O 3 incorporation. This is accompanied by a clear reduction of the conduction band spike at the CdS/CISSe interface due to Al 2 O 3 addition, as derived by both UPS and IPES as well as temperature-dependent V OC measurements.
Large solar photovoltaic (PV) penetration using inverters in low voltage (LV) distribution networks may pose several challenges, such as reverse power flow and voltage rise situations. These challenges will eventually force grid operators to carry out grid reinforcement to ensure continued safe and reliable operations. However, smart inverters with reactive power control capability enable PV systems to support voltage quality in the distribution network better. Here, this paper gives an overview of the current state-of-the-art control strategies for handling voltage problems through PV inverters and other devices. In addition, the (control) technical issues of PV systems integrated into the LV distribution network are considered from a control point of view. By comparing the control issues of PV integration into the grid, the paper aims to help distribution system operators to expand the volume of PV generation in the distribution system in an efficient and safe manner. Additionally, it will help control engineers and researchers select proper control strategies for PV systems as well as other distributed renewable sources.
This paper proposes an analytic neural network Gaussian process (NNGP)-based chance-constrained real-time voltage regulation method for active distribution systems with photovoltaics (PVs), batteries, and electric vehicles (EVs). NNGP can utilize historical measurement data to achieve real-time probabilistic node voltage estimation through Bayesian inference. Then, NNGP is fully analytically embedded into the optimal power flow model to perform voltage regulation and adapt to various topological changes. The uncertainties of voltage estimations are easily considered via the chance constraint, and it has been shown that the adoption of this chance constraint can significantly improve the reliability of voltage regulation under various scenarios. The comparison results with other methods, carried out on a real 759-node distribution system located in western Colorado, U.S., show that the proposed method can achieve accurate voltage estimation across different topologies and reliably perform voltage regulation considering PVs, batteries, and EVs.
Due to the increasing penetration of distributed behind-the-meter photovoltaic (PV) systems and the installed utility revenue metering limited to monitoring only the net power import/export of the household, it is increasingly challenging for utilities to effectively plan and operate the grid. This paper proposes a methodology that estimates behind-the-meter PV generation using a selected subset of monitored PV systems. It is a data-driven approach, and the PV output is estimated utilizing a statistic regression model. A Minimum Redundancy Maximum Relevance (MRMR) algorithm is applied to preselect the optimal subset of the monitored PV systems. The performance of this approach is compared with a spatial interpolation method and a model-based approach. The proposed method is validated using high-resolution meter data recorded from 18 residential rooftop PV systems located on the island of Maui, Hawaii.
This work provides cybersecurity analytics for a high photovoltaic (PV) penetrated distribution network, representing future power electronics dominated grid (PEDG). Firstly, the impact of active and reactive power (PQ) set-points manipulation on the network is studied. Then, an intrusion detection system (IDS) is developed for identifying the potentially compromised PV inverters in the network. The proposed IDS is based on defining the normal, safe, and abnormal operation regions of the PV inverters from point of view of the steady state voltage stability of the network. These three-operation regions are identified by utilizing active power, reactive power, and voltage (PQV) limits of each specific grid-following inverter in the network. Each grid-following inverter's PQV contour includes the information of network topology, inverter ratings, and inverter controller. The developed PQ limits are integrated into the centralized secondary control layer for realization of the proposed IDS. Furthermore, the proposed secondary control layer is capable of providing remedial actions during an anomaly event to enhance the grid resiliency. The theoretical analyses are verified by several attack scenarios for a network of grid-following inverters.
The increasing integration of distributed energy resources (DERs), such as photovoltaics (PVs) and smart buildings into distribution systems complicate power system operation and controls. This paper proposes a coordinated optimal control strategy for PV inverters and Heating, ventilation, and air conditioning (HVAC) loads in smart buildings to minimize the total network loss in a distribution system. For the HVAC units, we enforce minimum on and off time constraints to avoid frequent switching that can degrade the unit. The proposed control will dispatch optimal control signals of active and reactive power to PV inverters and on/off commands to HVAC units while maintaining the nodal voltage within a secure range and the temperature of HVAC units at a comfort level. The simulation results on a modified IEEE 33-node distribution system demonstrate that the proposed coordinated control scheme can reduce the network loss.
This paper presents a hardware-in-the-loop (BIL) simulation to evaluate the performance of an advanced grid automation architecture, referred to as data-enhanced hierarchical control (DEHC), in achieving voltage regulation and conservation voltage reduction (CVR) in distribution networks with very high photovoltaic (PV) generation. This architecture comprises an advanced distribution management system (ADMS), a distributed energy resource management system (DERMS), and grid-edge devices working synergistically to provide the grid benefits. The HIL setup used for the evaluation includes ADMS, DERMS, and grid-edge devices. The DEHC performance is evaluated in two representative scenarios considering loose and tight constraints of the power factor at the substation. The results show that the DEHC architecture is effective in achieving voltage regulation and CVR and thus enables the grid integration of high levels of PV generation.
Managing the digitalization of increasingly diversity energy resources is a complex challenge for energy systems planners and managers. As the penetration of solar photovoltaics (PV) and other distributed renewable energy resources (DERs) expands, distributed energy resource management systems (DERMS) will play an increasingly important role in managing, monitoring, and controlling DERs as electric systems before more distributed, interconnected, and networked. However, the cybersecurity implications of DERMS deployments are not well understood today. A lack of understanding around the cybersecurity implications of DERMS deployments and variability in the security posture of DERMS vendors, owners, and operators could introduce new security risks to evolving electric power systems. This paper describes cybersecurity attack scenarios on DERMS, identifies related cybersecurity standards and guidelines, reviews the security features of state-of-the-art DERMS solutions, and offers cybersecurity guidance for DERMS vendors, owners, and operators to protect DERMS' unique capabilities. Standardizing cybersecurity requirements for DERMS could help improve the security of DERMS integrations and improve innovations that are more secure by design. The cybersecurity guidance found in this paper is intended to offer a unified approach and lay the foundation for future standardization of DERMS cybersecurity to reduce risk to the solar industry and other renewable energy stakeholders when integrating these technologies with electric power systems.
This paper proposes a Lyapunov optimization-based online distributed (LOOD) algorithmic framework for active distribution networks (ADNs) with numerous photovoltaic inverters and inverter air conditionings (IACs). In the proposed scheme, ADNs can track an active power setpoint reference at the substation in response to transmission-level requests while concurrently minimizing the social utility loss and ensuring the security of voltages. Conventional distributed optimization methods are rarely feasible to track the optimal solutions in fast variable environments using a fine-grained sampling interval where the underlying optimization problem evolves with the iterations of the algorithms. In contrast, based on the framework of online convex optimization (OCO), the developed approach uses a distributed algebraic update to compute the next round decisions relying on the current feedback of measurements. Notably, the time-coupling constraints of IACs are decoupled for online implementation with Lyapunov optimization technique. An incentive scheme is tailored to coordinate the customer-owned assets in lieu of the direct control from network operators. Optimality and convergency are characterized analytically. Finally, we corroborate the proposed method on a modified version of 33-node test feeder. Benchmark tests show that the proposed method is computationally and economically efficient, and outperforming existing algorithms.
This report presents an analytical methodology to identify alternative options to manage interconnection costs and streamline interconnection timelines for distribution system-connected photovoltaic (PV) systems not co-located with load. Specifically, the report details the methodology and results of an analysis that: 1. Identifies potential grid violations that would be induced by a PV system requesting interconnection to a distribution circuit; 2. Identifies multiple technically viable options for mitigating the potential violations, including infrastructure upgrades, downsizing the PV system size, curtailment of PV, and addition of battery energy storage; 3. Defines the required technical operating parameters of the system in order to mitigate all potential violations (the "Operating Envelope"); 4. Compares the economics of each option, from the PV developer's perspective. The analysis supports the ongoing evolution of interconnection standards for combined PV and energy storage systems by providing a methodology to define allowable maximum export limits during each hour. The methodology presented could be used by utilities as part of the interconnection study process, to inform negotiations with DER developers and the drafting of mutually acceptable interconnection agreements. The resulting technical operating parameters could be included as part of the interconnection service agreement (ISA) between the system owner and the utility company. The companion report to this analysis, Gill et al. (2022), details the envisioned framework for the implementation of the technical operating parameters.
Advanced ceramic integration technologies dramatically impact the energy landscape due to wide scale application of ceramics in all aspects of alternative energy production, storage, distribution, conservation, and efficiency. Examples include fuel cells, thermoelectrics, photovoltaics, gas turbine propulsion systems, distribution and transmission systems based on superconductors, nuclear power generation and waste disposal. Ceramic integration technologies play a key role in fabrication and manufacturing of large and complex shaped parts with multifunctional properties. However, the development of robust and reliable integrated systems with optimum performance requires the understanding of many thermochemical and thermomechanical factors, particularly for high temperature applications. In this presentation, various needs, challenges, and opportunities in design, fabrication, and testing of integrated similar (ceramic ceramic) and dissimilar (ceramic metal) material www.nasa.gov 45 ceramic-ceramic-systems have been discussed. Experimental results for bonding and integration of SiC based Micro-Electro-Mechanical-Systems (MEMS) LDI fuel injector and advanced ceramics and composites for gas turbine applications are presented.
Traditionally, transmission and distribution system dynamic simulations are performed independently. However, dynamic co-simulation of transmission-distribution systems can be beneficial in analyzing distribution systems with high penetration of distributed renewable resources. The authors describe a framework for conducting transmission-distribution dynamic co-simulation (TDDS). A model of a real network including detailed models of solar photovoltaic units in the distribution system is constructed. The initial operating point of the network is validated against field measurements. The TDDS tool is used to simulate a single line-to-ground fault on the distribution system, highlighting the need for conducting transmission-distribution co-simulations.