130 records · Page 8

Nuclear Power Fault Diagnostics and Preventative Maintenance Optimization NPIC presentation

The nuclear industry is beginning to see reactors shut down—even after their operating licenses have been extended—because they are not economically competitive with other energy sources. These early closures happen primarily due to economic reasons, despite excellent safety records. Therefore, it is imperative to reduce costs in order to prevent these early closures. One of the contributors to these economic reasons is the large operations and maintenance costs. This paper showcases recent research on advanced fault diagnostics techniques and preventative maintenance optimization (PMO) for reducing NPP maintenance costs. Specifically, it focuses on the feedwater and condensate system (FWCS) for both pressurized- and boiling-water reactor (BWR) systems. The computerized maintenance management system (CMMS), which contains the plant’s digital record of all corrective maintenance (CM) and preventative maintenance (PM) work orders, provided the ground truth for locating potential faults and labeling the process data as either healthy or faulted. Various feature extraction techniques were used to further differentiate the faulted data from the healthy data. Through a cross-validation procedure, support vectors machines were used to label other test sets of process data as either healthy or faulted. With relatively few faults identified in the BWR system, the potential for PMO opens up, since an unnecessary amount of PM leads to inflated maintenance costs. The steps for PMO are summarized, from component health determinations to recommendations for action. An example of PMO assessment is presented for condensate pumps, condensate booster pumps, and the respective motors that drive them.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗

Performance Results for Sensor Assignment Problem as Solved on a Multi-Node Cluster

An earlier report described a procedure for optimal sensor set selection and its implementation on a computational cluster. This new and innovative capability was developed to facilitate a reduction in operations staffing levels to improve plant economics. By automating surveillance and maintenance tasks through early detection of degrading sensors and equipment, staff can be more efficiently deployed. The method uses automated reasoning and domain knowledge in the form of the conservation equations to infer from plant measurements the state of equipment health. Inclusion of domain knowledge addresses the problem that exists with pure data-driven methods that there are no rigorous guidelines for determining what constitutes an adequate sensor set. Formalizing the procedure for sensor set selection as we have done results in a more reliable and explainable diagnosis of plant equipment health. Importantly, from the standpoint of the plant owner, personnel are provided with an early and explicit diagnosis of an equipment problem. That in principle automates the process and eliminates having to send personnel into the plant to find the cause as typically occurs when a data-driven method detects an anomaly. In this report we describe first results obtained using a computational cluster to solve the sensor set selection problem as framed above. The case described addresses the problem of equipment health monitoring in the high-pressure (HP) feedwater system of a pressurized light water reactor as seen through the eyes of our collaborating utility partner. Maintenance of this system can amount to millions of dollars per year if equipment health issues go undiagnosed and lead to loss of function. On examining the potential that is inherent in the installed sensor set for diagnosing equipment health degradation, it was found that greater fault resolution capability can be achieved using a sensor set that is 20 percent fewer in number. The take-away is that compared to the installed sensor set there exists a more strategic assignment of sensors that will furnish better health monitoring capability and with fewer sensors. Where the problem defies solution by manual inspection, as is the case here, one can be found by an algorithm. The solution was obtained in four hours using 30 computational cores. The HP feedwater problem as posed above illustrates the added value of approaching the sensor selection problem as one amenable to algorithmic solution. This problem is of interest to advanced reactor designers and to utilities that are setting up remote monitoring and diagnostic centers.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗

Using discrete Bayesian networks for diagnosing and isolating cross-level faults in HVAC systems

Fault detection and diagnosis (FDD) technologies are critical to ensure satisfactory building performance, such as reducing energy wastes and negative impacts on occupant comfort and productivity. Existing FDD technologies mainly focus on component-level FDD solutions, which could lead to mis-diagnosis of cross-level faults in heating, ventilating, and air-conditioning (HVAC) systems. Cross-level faults are those faults that occur in one component or subsystem, but cause operational abnormalities in other components or subsystems, and result in a building level performance degradation. How to effectively diagnose the root cause of a cross-level fault is the focus of this study. Here, this paper presents a novel discrete Bayesian Network (DisBN)-based method for diagnosing cross-level faults in an HVAC system commonly used in commercial buildings. A two-level DisBN structure model is developed in this study. The parameters used in the DisBN model are obtained either from expert knowledge or through machine-learning strategies from normal system operation data. Meanwhile, the probability parameters are discretized to incorporate the uncertainties associated with typical expert knowledge. Thus, the developed DisBN method addresses the challenges many other BN based FDD methods face, i.e., the lack of fault data for BN parameter training. The developed DisBN represents causal relationships between a fault and its cross-level system impacts (i.e., fault symptoms or fault indicators) by considering how fault impacts propagate across different levels in an HVAC system. A weather and schedule information-based Pattern Matching (WPM) method is employed to automatically create WPM baseline data sets for each incoming real time snapshot data from the building systems. Consequently, BN inference and real-time diagnostics are achieved by comparing incoming snapshot data and the WPM baseline data set. The proposed method is evaluated using experimental fault data collected in a campus building. Fault diagnosis results demonstrate that the WPM-DisBN method is effective at locating the root causes of cross-level faults in an HVAC system.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

LCOE reduction through proactively optimized monitoring of PV Systems (Final Technical Report)

The project demonstrates the value proposition for a high-resolution monitoring system (HRMS) with diagnostic-prognostic capability and determine its impact on LCOE. The HRMS differs from conventional monitoring systems in a number of ways. First it will include the capability to automatically measure IV curves at the string and module levels. This provides a much richer view into the DC performance of the PV system and allows classification of many typical failure and degradation modes. Second, it will incorporate software capable of quantifying power and energy losses in the field as well as define the location and mechanism of the power and energy loss. Moreover, we aimed to deliver a prognostic system that is capable of predicting certain failures before they occur and giving system operators the opportunity to more efficiently plan operations and maintenance (O&M) activity in order to lower costs and increase yield over the life of the system. The research identifies cost targets required for different monitoring stages, including at the string combiner, at the individual string, and at the module level, to lower the levelized cost of energy (LCOE). Finally, a comprehensive guide determines the value PV monitoring brings to PV field operations. The guide assists plant operators in maximizing value from existing plants and identify the trade-offs of different monitoring solutions for future plants depending on the size, location, and expected system lifetime.

14 SOLAR ENERGY↗