Designing Hydropower Flows to Balance Energy and Environmental Needs (HydroWIRES Topic A Final Project Report)

Hydropower is expected to play a new role in the US electricity grid as more variable renewable energy sources like wind and solar come online. Wind and solar generation increase fluctuations in electrical supply increasing the value of flexible generation sources that can quickly ramp generation up and down. The flexible generation hydropower can provide as well as the ancillary services (e.g., frequency and voltage regulation and reserves, black start capability) it provides for balancing and stabilizing the power grid are predicted to be of increased value in these future grid scenarios. Yet, the flexibility of hydropower may come with environmental costs due to up- and down-ramping of hydropower plants (i.e., quickly increasing or decreasing generation flows, respectively) which may strand fish, dewater or scour fish nests, alter habitat, or create unsafe recreational conditions that may be unacceptable to participants in the hydropower regulatory process. These types of environmental impacts are often mitigated through environmental flow requirements that specify minimum or maximum flow releases, or ramp-rates changes allowed at a hydropower facility. While it is not currently known to what degree electrical grid reliability could be affected by environmental flow requirements, gaining a better understanding of these interactions before the grid becomes more deeply decarbonized can help define what policy, regulation, or infrastructure may be needed to support the clean energy transition. As the future grid will rely on hydropower to provide both flexibility and robust environmental protections, the analyses and tools described in this report are centered on making mechanistic linkages between energy and the environment in hydropower systems. This understanding of energy-environment linkages can provide the foundational understanding needed to quantitatively assess the trade-offs between the increased generation flexibility that hydropower will be expected to provide and the environmental impacts of this flexibility. This report seeks to provide an objective foundation for building future science and tools that can be used by a broad spectrum of the hydropower community that is involved in licensing or environmental regulatory proceedings tasked with balancing energy and environmental objectives through flow management.

13 HYDRO ENERGY↗

Optimal Operation and Impact Assessment of Distributed Wind for Improving Efficiency and Resilience of Rural Electricity Systems

This project aims to empower rural utilities by developing advanced optimization models and algorithms for effectively integrating distributed wind energy alongside battery storage and other distributed energy resources (DERs). The primary objectives are to reduce peak demand, ensure reliable emergency power supply, and regulate voltage and frequency. To address operational challenges, the project introduces innovative mitigation strategies and ultrafast assessment frameworks to evaluate the impacts of distributed wind and DERs on rural grids, offering actionable solutions to potential issues. Economic viability is assessed through cost-benefit analysis using real rural utility data, ensuring the practical application of the project outcomes.

17 WIND ENERGY↗

Grid regulation services for energy storage devices based on grid frequency

Disclosed herein are representative embodiments of methods, apparatus, and systems for charging and discharging an energy storage device connected to an electrical power distribution system. In one exemplary embodiment, a controller monitors electrical characteristics of an electrical power distribution system and provides an output to a bi-directional charger causing the charger to charge or discharge an energy storage device (e.g., a battery in a plug-in hybrid electric vehicle (PHEV)). The controller can help stabilize the electrical power distribution system by increasing the charging rate when there is excess power in the electrical power distribution system (e.g., when the frequency of an AC power grid exceeds an average value), or by discharging power from the energy storage device to stabilize the grid when there is a shortage of power in the electrical power distribution system (e.g., when the frequency of an AC power grid is below an average value).

24 POWER TRANSMISSION AND DISTRIBUTION↗

Plants cope with fluctuating light by frequency‐dependent nonphotochemical quenching and cyclic electron transport

Summary In natural environments, plants are exposed to rapidly changing light. Maintaining photosynthetic efficiency while avoiding photodamage requires equally rapid regulation of photoprotective mechanisms. We asked what the operation frequency range of regulation is in which plants can efficiently respond to varying light. Chlorophyll fluorescence, P700, plastocyanin, and ferredoxin responses of wild‐types Arabidopsis thaliana were measured in oscillating light of various frequencies. We also investigated the npq1 mutant lacking violaxanthin de‐epoxidase, the npq4 mutant lacking PsbS protein, and the mutants crr2‐2 , and pgrl1ab impaired in different pathways of the cyclic electron transport. The fastest was the PsbS‐regulation responding to oscillation periods longer than 10 s. Processes involving violaxanthin de‐epoxidase dampened changes in chlorophyll fluorescence in oscillation periods of 2 min or longer. Knocking out the PGR5/PGRL1 pathway strongly reduced variations of all monitored parameters, probably due to congestion in the electron transport. Incapacitating the NDH‐like pathway only slightly changed the photosynthetic dynamics. Our observations are consistent with the hypothesis that nonphotochemical quenching in slow light oscillations involves violaxanthin de‐epoxidase to produce, presumably, a largely stationary level of zeaxanthin. We interpret the observed dynamics of photosystem I components as being formed in slow light oscillations partially by thylakoid remodeling that modulates the redox rates.

59 BASIC BIOLOGICAL SCIENCES↗

Using distributed power electronics-based devices to improve the voltage and frequency stability of distribution systems

Methods include, in response to a line frequency variation of a power grid, adjusting a voltage setpoint of a voltage regulator coupled to the power grid at a grid edge to maintain a voltage at the grid edge, wherein the adjusting the regulated voltage setpoint is configured to reduce the line frequency variation to stabilize the line frequency of the power grid. Apparatus include a voltage regulator configured to couple to a power grid at a grid edge and to maintain a voltage at the grid edge, wherein the voltage regulator is further configured to adjust a voltage setpoint of a voltage regulator in response to a line frequency variation of the power grid to reduce the line frequency variation and stabilize the line frequency of the power grid.

Du, Wei↗

Flashlamp drive system for a high-energy 10–100 kHz pulse-burst Nd:YAG laser

We present the design of the flashlamp drive system for the NG100 laser, a 1 J/pulse, 10–100 kHz, pulse-burst Nd:YAG laser system being developed for application in a Thomson scattering plasma diagnostic. This flashlamp drive system is under active development, with a prototype now being constructed. The flashlamp drive system is modular, with each module capable of driving a series pair of linear flashlamps. Each drive module contains and is controlled by a dedicated Analog Regulator Controller. Thus each module is independently operable and controllable. This modular approach imposes no intrinsic limit to the number of modules that may be applied to drive the flashlamp pairs in a laser system. Each flashlamp drive module has a switch-regulated topology. An 1800 V main capacitor bank provides 25 kJ of energy storage, while a lower voltage output capacitor bank provides filtering and the initial energy delivered to the flashlamps at the start of the drive pulse. The main bank is recharged after each flashlamp drive pulse. As energy is drawn from the output bank by the flashlamps, an IGBT switching regulator feeds current from the main bank through an inductor to replenish the output capacitor bank. The rate of replenishment is feedback-controlled to maintain a regulated supply of power to the flashlamp load, with a setpoint range of 0.07 to 1.65 MW. An Analog Regulator Controller produces two-state variable pulse width feedback switching of the regulator IGBT. The switching frequency is ≤ 20 kHz, dynamically adjusted to limit ripple of the flashlamp power to ±3% statistical standard deviation of mean. For development or troubleshooting, each module is operable independent of the laser digital control system (microcontroller and FPGA).

Plasma diagnostics - interferometry↗

A Secondary Control Framework for Microgrid Interoperability With Vendor-Agnostic Grid-Forming Units: Design, Implementation, and Demonstration via Large-Scale Hardware Setup

The reliable operation of islanded microgrids increasingly depends on secondary controls that restore voltage and frequency to nominal values and ensure accurate active and reactive power sharing. Centralized secondary control architectures achieve high accuracy through global coordination at the cost of single-point failures and limited scalability compared with decentralized/distributed approaches. But a critical gap remains in addressing the interoperability and vendor-agnostic operation of secondary controls in real-world microgrids where heterogeneous diesel generator(s) and grid-forming (GFM) inverter(s) from multiple manufacturers always coexist. Practical and vendor-agnostic interoperability guidelines for the secondary control architecture of microgrids with multiple GFM units have not yet been developed; therefore, this paper proposes an interoperable and vendor-agnostic secondary control framework that operates seamlessly across GFM units from different vendors without relying on proprietary controls and protocols, hardware, or lock-ins. The framework leverages existing communication infrastructures (e.g., Modbus TCP/IP) to enable cost-effective deployment while addressing practical challenges, such as packet loss and quantization errors. Mitigation strategies-including data averaging, situational event-triggered control, and finite-iteration execution-are introduced to enhance reliability under real-world conditions. A generalized modeling and design framework is also presented, supported by robustness analysis to demonstrate independence from vendor-specific implementations. The proposed framework is validated through a large-scale hardware demonstration using a 3-$\phi$, 480-V, 60-Hz, 713-kVA laboratory hardware microgrid involving a heterogeneous diesel generator and multiple GFM inverters, showcasing its effectiveness in achieving stable voltage and frequency restoration and accurate power sharing under practical constraints. The results highlight the framework's potential as a scalable and practical solution for next-generation microgrids requiring openness, standard framework, and interoperability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

On Control Schemes for Grid-Forming Inverters

Grid-forming inverters can collaboratively regulate the voltage and frequency of a microgrid. These inverters are expected to be seen more in the future microgrid, undertaking the roles of the conventional power generators. Like conventional power generators, they must balance supply and demand, contribute to power-sharing between inverters and other power generators, and restore the voltage and frequency after any power changes. These technical challenges are typically achieved through different primary and secondary controllers. This article reviews some state-of-the-art primary and secondary control schemes for the emerging technology of grid-forming inverters. First, the typical control schemes for grid-following inverters are briefly presented for the continuity of the discussion on the roles of the grid-forming inverters in future power-grid, followed by two basic control schemes for the grid-forming inverters. Then, two decentralized power-sharing techniques, i.e., droop, and virtual inertia, are analyzed. The technical challenges for inverter synchronization and some control methods are discussed afterward. Finally, several secondary control methods for the voltage and frequency restoration in grid-forming inverters are reviewed.

Sadeque, Fahmid↗

Providing Ancillary Services with Photovoltaic Generation in Multi- Timescale Grid Operation

With penetration levels of photovoltaic (PV) generation substantially increasing, electric power systems need more flexible resources that can provide ancillary services to mitigate the variability and uncertainty of the PV. On one hand, the increase in PV generation necessitates more flexible resources; on the other hand, because of its low operation cost, PV generation has been replacing conventional generation, which is currently the main flexible resource. Consequently, there is a trend to require renewable generation, including PV, to provide flexible ancillary services. This paper proposes a multi-timescale grid operation model considering the various control strategies of PV providing different ancillary services. Numerical case studies demonstrate that with PV providing both regulation reserve and primary frequency reserve, the system operating costs and PV curtailment will be reduced significantly. Results show that not only the system reliability can be improved but also PV profitability with PV providing more ancillary services.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Bulk Power System Dynamics with Varying Levels of Synchronous Generators and Grid-Forming Power Inverters

Inverters using phase-locked loops for control depend on voltages generated by synchronous machines to operate. This might be problematic if much of the conventional generation fleet is displaced by inverters. To solve this problem, grid-forming control for inverters has been proposed as being capable of autonomously regulating grid voltages and frequency. Presently, the performance of bulk power systems with massive penetration of grid-forming inverters has not been thoroughly studied as to elucidate benefits. Hence, this paper presents inverter models with two grid-forming strategies: virtual oscillator control and droop control. The two models are specifically developed to be used in positive-sequence simulation packages and have been implemented in PSLF. The implementations are used to study the performance of bulk power grids incorporating inverters with gridforming capability. Specifically, simulations are conducted on a modified IEEE 39-bus test system and the microWECC test system with varying levels of synchronous and inverter-based generation. The dynamic performance of the tested systems with gridforming inverters during contingency events is better than cases with only synchronous generation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distributed Cooperative Control of Hybrid AC/DC Microgrid

This paper presents a distributed cooperative control-based power management algorithm for a hybrid AC/DC microgrid. The proposed algorithm for a hybrid microgrid system controls the power flow through the interface converter between the AC and DC microgrids. This algorithm allows power sharing between the distributed generators in the microgrid according to their power ratings. Moreover, it enables the fixed scheduled power delivery through the interface converters in both directions at different operating conditions while maintaining voltage regulation and improving the frequency profile. The effectiveness of the controller is confirmed by simulation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Robust Optimal Control of Inverter-Based Resources Under Grid-Forming Operation

In this paper, we propose and solve a robust control problem for inverter-based resources under grid-forming operation to regulate the voltage and frequency. One major challenge is to mitigate the effect of unmeasurable load current disturbance, grid and load parametric uncertainties. Moreover, strong coupling between the state variables on both the AC and DC sides, as well as between the modulating control input and the frequency impose additional challenges. To address these challenges, first, a robust control problem is solved at the high level via transformation into an equivalent, but more tractable, optimal control problem. Then, in the middle layer a voltage control law is designed on the one side, and a frequency control law on the other side. Finally, an inverter filter current controller is designed to complete the controller design. Theoretical results are derived to provide stability guarantees for the resulting closed-loop system. Specifically, we show that the inverter current injection error is dissipative, the frequency error is semi-globally asymptotically stable, and the inverter terminal voltage error is globally asymptotically stable, all with provided sufficient conditions. Here, numerical simulation experiments are used to validate the theoretical claims. Furthermore, the developed controller is compared with existing work in literature to show the efficacy of the proposed approach.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Two-Stage Current Limiting Control Strategy for Direct-Droop-Controlled Grid-Forming Inverters

This paper presents a two-stage current limiting control strategy with fault ride-through capability for the direct-droop-controlled grid-forming (GFM) inverters. The proposed approach comprises Stage 1 and Stage 2 current limiting controls. During faults, Stage 1 current limiting control instantly clamps the inverter output current magnitude to its maximum transient limit by blocking the switching pulses to the insulated-gate bipolar transistors (IGBTs) with the help of a hysteresis loop control, and Stage 2 current limiting control limits the inverter output current magnitude to its steady-state limit by regulating the amplitude and frequency of the modulating waveform utilizing the active and reactive current limiting control loops. By implementing the current limiting actions in two stages, this approach can effectively limit the over-current within a few cycles after the fault occurrence and ensure synchronism to the grid after long-term fault events. The efficacy of the proposed control approach is validated through electromagnetic transient (EMT) simulation results conducted on a single GFM inverter-based test system and the IEEE 39-bus test system with multiple GFM inverters in the PSCAD platform.

Mohiuddin, Sheik Mohammad↗

Accurate Consensus-based Distributed Averaging with Variable Time Delay in Support of Distributed Secondary Control Algorithms

We report that distributed secondary control has been widely used in hierarchical control structures, where multiple distributed generators (DGs) need to coordinate to regulate system voltage and frequency. In these systems, consensus algorithms determine the average of a group of dynamic states (e.g. voltages measured by a group of DGs). To be useful, consensus algorithms must be computationally efficient, stable and accurate. In practice, numerous practical implementation challenges significantly affect the consensus equilibrium. In this paper, we quantify the accuracy deviations of the distributed average observer algorithms proposed in the literature to demonstrate the problems with the state-of-the-art distributed averaging techniques. A novel approach is proposed that achieves accurate average tracking in the presence of time-varying communication delays among agents. In our implementation, time synchronization of all distributed controllers is enabled by a novel software platform, called Resilient Information Architecture Platform for the Smart Grid (RIAPS). The proposed distributed average observer is implemented on hardware controllers and its effectiveness is validated in a controller hardware-in-the-loop testbed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

EXERGETIC: De-Risking Next-Generation Resilient Geothermal Hybrids via At-Scale Evaluation Using Virtual Emulation Digital Twin Environment for Efficient Operation

The DOE-GTO-funded project, award number 5.1.2.12, entitled "EXERGETIC - De-risking Next Generation Resilient Geothermal Hybrids via at-Scale Evaluation Using a Virtual Emulation Digital Twin Environment for Efficient Operation," advances the solution to these challenges by developing and validating a geothermal co-emulation environment implemented at the National Laboratory of the Rockies (NLR)'s Advanced Research on Integrated Energy Systems (ARIES) platform. This framework enables the de-risking of next-generation geothermal and geothermal hybrid systems through high-fidelity modeling, real-time digital emulation, advanced control strategies, and techno-economic assessment. The project focused on geothermal hybrid configurations that integrate geothermal power plants with concentrated solar power and underground thermal energy storage, enabling enhanced efficiency, flexibility, and grid support capabilities. The main goal of this project was the development of a geothermal digital co-emulation environment to demonstrate the technical and economic value of geothermal hybrid systems and their contribution to grid stability and flexibility. The EXERGETIC framework combined physics-based models, controls, and real assets at ARIES, including digital real-time simulators (DRTS), a 20-MW-scale controllable grid interface (CGI), and a 2-MW conventional generator. Detailed transient models were developed for the key subsystems of a hybrid geothermal plant, including parabolic trough solar collectors, reservoir thermal energy storage (RTES), and a binary Organic Rankine Cycle (ORC) power plant. The ORC model explicitly captured thermal inertia and off-design operation and integrated control strategies to dynamically respond to electric load profiles. The models were validated against published experimental and numerical studies, demonstrating strong agreement and confirming the accuracy and robustness of the modeling approach. The resulting digital twin represents geothermal-solar-storage systems at multiple scales (1 MW to 100 MW) and enables realistic emulation of grid-connected operation. The control architecture allows the geothermal resource to provide stable baseload generation, while solar and stored thermal energy supply flexible, dispatchable support during periods of high demand or variable grid conditions. A key contribution of the EXERGETIC project is the demonstration that geothermal hybrid systems can be designed to be active grid assets rather than passive baseload generators. Using the ARIES platform, the digital twin was evaluated under multiple grid scenarios, including load following, voltage support at the distribution level, and frequency response at the transmission level. Results show that hybrid geothermal systems can respond effectively to dynamic grid conditions, providing inertia-like behavior, primary frequency support, and voltage regulation through coordinated control. In addition to the performance and grid services capability analysis of geothermal and hybrid geothermal systems, the EXERGETIC project also focused on scalability and techno-economic analysis of geothermal hybrid plants. In particular, for the scalability analysis, machine-learning (ML)-based surrogate models were trained using data generated from the geothermal digital twin under different grid-connected scenarios and plant capacities. These ML models demonstrated strong interpolation and extrapolation capabilities across plant sizes, accurately reproducing both steady-state and transient responses with very low errors. Regarding the techno-economic analysis, plant performance results were integrated with cost models for hybrid geothermal systems, and the levelized cost of electricity (LCOE) was used as the main economic metric to evaluate system performance across a range of system capacities, solar shares, solar multiples, and storage durations. Results indicate that economies of scale significantly reduce geothermal LCOE as plant capacity increases, with large-scale systems (25-100 MW) achieving substantially lower costs than small plants. Hybridization with solar thermal energy and storage further improves economic performance by increasing capacity utilization and enabling flexible dispatch. In addition, thermal storage plays a critical role in reducing LCOE by maximizing geothermal, solar, and stored energy resources. In summary, the results from this project demonstrate that geothermal hybrid systems represent a promising alternative for increasing the energy conversion efficiency of geothermal technologies, contributing to the preservation of geothermal resources, and supporting the transition of geothermal plants from traditional baseload resources into flexible, resilient, and cost-competitive energy conversion technologies.

15 GEOTHERMAL ENERGY↗

Providing Ancillary Services with Photovoltaic Generation in Multi-Timescale Grid Operation: Preprint

With photovoltaic (PV) generation substantially increases, electric power systems need more flexible resources that can provide ancillary services to mitigate the variability and uncertainty of the PV generation. On the one hand, the increase of PV generation necessitates the needs of more flexible resources. On the other hand, PV generation, because of its low operation cost, has been replacing the conventional generation in the system which is the main flexible resources in the current system. Consequently, there is a trend to require the renewable generation including PV to provide flexible ancillary services to further accommodate more PV integration. This paper proposes a multi-timescale grid operation model considering the various control strategies of PV providing different ancillary services. Numerical case studies demonstrate that with PV providing both regulation reserve and primary frequency reserve, the system operating costs and PV curtailment will be reduced significantly. It shows that not only the system reliability but also PV's profitability can be improved with PV providing more ancillary services.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Advanced control techniques for modern inertia based inverters

In this research three artificial intelligent (AI)-based techniques are proposed to regulate the voltage and frequency of a grid-connected inverter. The increase in the penetration of renewable energy sources (RESs) into the power grid has led to the increase in the penetration of fast-responding inertia-less power converters. The increase in the penetration of these power electronics converters changes the nature of the conventional grid, in which the existing kinetic inertia in the rotating parts of the enormous generators plays a vital role. The concept of virtual inertia control scheme is proposed to make the behavior of grid connected inverters more similar to the synchronous generators, by mimicking the mechanical behavior of a synchronous generator. Conventional control techniques lack to perform optimally in nonlinear, uncertain, inaccurate power grids. Besides, the decoupled control assumption in conventional VSGs makes them nonoptimal in resistive grids. The neural network predictive controller, the heuristic dynamic programming, and the dual heuristic dynamic programming techniques are presented in this research to overcome the draw backs of conventional VSGs. The nonlinear characteristics of neural networks, and the online training enable the proposed methods to perform as robust and optimal controllers. The simulation and the experimental laboratory prototype results are provided to demonstrate the effectiveness of the proposed techniques.

24 POWER TRANSMISSION AND DISTRIBUTION↗