Droop Control-Based Dispatch of an Islanded Microgrid With Multiple Grid-Forming Sources

Before rotating, fossil fuel-based, synchronous generators (SGs) are phased out, in line with renewable generation goals, grid-forming (GFM) inverters are expected to parallel SGs. Primary droop control allows GFM inverters to share power without communication; however, it is necessary to dispatch GFM inverters and/or SGs with the desired output power for better energy management (e.g., one GFM inverter needs to charge the battery due to a low state of charge). Therefore, this paper develops an analytic approach to dispatching GFM inverters and SGs with the desired output power by shifting the droop intercept up/down while maintaining the same frequency operating point for improved transient stability. This concept is demonstrated through a pure hardware setup with two off-the-shelf inverters and one diesel generator under an islanded microgrid, and we provide insight on the real-world implementation of the proposed concept.

droop control↗

Oscillation Risks of Grid-Following and Grid-Forming Inverter-Based Resources in Series-Compensated Networks

Here, this paper investigates the dynamic behavior of a grid-connected inverter-based resource (IBR) when connected radially to a series compensated line. Potential interactions between the series compensation and the IBR have been identified for both types: grid-following (GFL) or grid-forming (GFM). The study begins with electromagnetic transient (EMT) simulations to demonstrate stability issues. Subsequently, nonlinear analytical models are formulated in the dq frame, validated against the EMT simulation, and leveraged to assess eigenvalues and participation factors. Influencing factors of the dominant oscillation modes have been identified. The analysis results show that series compensation may make a mode associated with the synchronization unit unstable. Furthermore, customized feedback systems are built for the synchronizing loop. Series compensation can increase the sensitivity of the voltage phase angle towards the synchronizing angle, and introduce phase lag in the real power response towards the synchronizing angle. These factors may cause interactions with the phase-locked loop in GFL-IBR systems and with power-based synchronization in GFM-IBR systems, potentially leading to instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Inverter Controls for Smooth Transition Operation and Voltage Balancing of Networked Microgrids

With increasing penetrations of distributed energy resources (DERs), researchers have extensively studied the formation and networking of microgrids to improve reliability during distribution system outages. However, these operations might require DERs in the microgrids to switch between grid-following (GFL) and grid-forming (GFM) modes of operation. A smooth transition between the operation modes should be ensured to have a stable system operation and to avoid nuisance tripping. Additionally, as we network microgrids, inverter control schemes with voltage-balancing controls are needed for unbalanced distribution networks. This paper presents the design of a GFM and GFL capable inverter control scheme for reliable operation in networked microgrids with mechanisms for 1) smooth transition between the GFL and GFM modes, and 2) negative sequence voltage control for voltage balancing. Using electromagnetic transient (EMT) simulations, the control scheme is first tested on a simple two-source power system using a digital real-time simulator. Next, a real-world distribution feeder with unbalanced loading and multiple DERs is used to demonstrate stable operation during the networking of microgrids with voltage balance support.

distributed energy resources↗

Critical Clearing Time for Droop-Controlled Grid-Forming Inverters With Circular Current Limiting and Virtual Impedance Current Limiting

The critical clearing time is a crucial parameter for assessing the large-signal stability of grid-forming (GFM) inverters. Variations in current limiters can significantly impact an inverter's transient behavior during large disturbances. Here, this letter introduces a method based on the power-angle relationship to evaluate the fault recovery of a droop-controlled GFM inverter under a three-phase bolted fault scenario, considering both the circular current limiter and the virtual impedance method. High-fidelity simulations validate the accuracy of the proposed formulas in estimating the critical clearing time of the GFM inverter.

42 ENGINEERING↗

Power Flow Models of Grid-Forming Inverters in Unbalanced Distribution Grids

Load unbalance in electric distribution systems is unavoidable. Unbalanced load currents will lead to negative sequence (NS) voltages that may damage electric equipment. Unbalanced power flow analysis is a common tool to detect and mitigate NS voltage issues and requires accurate models of grid components. While traditional source models are available, grid-forming (GFM) inverter models are not well developed. GFM inverters implement various control strategies, which affect their power flow models. Here, in this paper, a novel GFM inverter model considering control effects is proposed. We show that for some control methods, unbalanced system loading will lead to unbalanced terminal voltages of the GFM inverters, which are modeled through an equivalent negative sequence impedance. The proposed models are initially validated using a simple test circuit. Then, they are applied in the power flow analysis on the IEEE 13-bus and 34-bus systems to demonstrate the accuracy improvement over the state-of-the-art. Using time-domain simulations as benchmarks, we show that the proposed models reduce the calculation error of negative sequence voltages by at least 25% in unbalanced distribution systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Holistic Small-Signal Stability Analysis for Large-Scale Inverter-Intensive Power Systems with Coupled and Full-Order Dynamics from Control Systems and Power Networks

The increasing penetration of inverter-based resources (IBRs) into the existing power systems introduces tremendous benefits for enhanced sustainability but also poses inevitable challenges in terms of insufficient inertia, potential instability, and complex network dynamics, among others. However, the additional coupling introduced by the interactions among gridfollowing (GFL) and grid-forming (GFM) IBRs and the other components (i.e., synchronous generators [SGs], loads, and network, etc.) has not been clearly explored. A holistic, scalable, and quantitative stability analysis framework with the control systems and power networks is still missing. Here, in this paper, to fill in the technical gaps, a holistic small-signal model of the entire system with both rotating generation units and IBRs is established. An extended power flow model with operation dynamics from both generator control schemes and power networks is proposed to provide the varying steady-state operating points for small-signal modeling. The proposed method is compared with MATLAB solvers, and the results show that the proposed approach has a minimum calculation time, which can be less than 12 seconds for a large-scale power system with up to 2,000 buses. Furthermore, a quantitative method is developed to identify the impacts of IBRs on system performance with emphases on the potential stability issues with GFL IBRs, additional benefits of employing GFM IBRs, the feasibility of replacing SGs with GFM IBRs, and the impact of penetration level of different kinds of generation units. Finally, a field island power system is used to verify the proposed approach, and hardware-in-the-loop (HIL) tests are provided to further demonstrate the effectiveness of the proposed analysis.

14 SOLAR ENERGY↗

Demonstration of Power System Black Start with Hydropower Generator and Battery Energy Storage: Preprint

Battery energy storage systems (BESS) are an important asset for power systems with high integration levels of renewable energy, and they can be controlled to provide various services to the grid. This paper presents the hardware demonstration and characterization of using a utility-scale BESS with grid-following (GFL) and grid-forming (GFM) controls and a run-of-river (ROR) hydropower plant to perform a bottom-up power system black start that enhances power systems' resiliency. ROR hydropower plants are generally not used for power system restoration due to their frequency instability during islanded operation; however, BESS with droop control can provide critical damping to convert a ROR hydropower generator into a blackstart- capable unit. To demonstrate this, we carry out hardware experiments at the megawatt-scale integrating a synchronous generator driven by a dynamometer, an actual GFL/GFM BESS, a medium-voltage impedance network, and a load bank. The demonstration shows the different roles of BESS with GFL and GFM control in power system restoration. GFL BESS can suffer from high-frequency oscillations, even instability, depending on the droop control gain and loading condition. The results provide further insights for system operators on how GFL- or GFMcontrolled BESS can enhance grid stability and how hydro-BESS hybrids can operate as a black-start-capable unit. The presented experimental results are also a valuable resource to understand the different stability characteristics of real-world BESS with different control modes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Stabilizing Inverter-Based Transmission Systems: Power Hardware-in-the-Loop Experiments with a Megawatt-Scale Grid-Forming Inverter

This article presents what the authors believe to be the first experimental verification of the ability of grid-forming (GFM) inverters to stabilize a transmission electric power system that is otherwise unstable. The experiments described here were performed using power hardware-in-the-loop (PHIL) simulation to connect a megawatt-scale battery inverter to a real-time electromagnetic transient (EMT) simulation of the near-future Maui power system. This allows the dynamic interactions between the inverter and the power system to be observed without putting the real power system at risk. The ability to use the actual inverter hardware removes the need to rely on a computer model approximation of the inverter's behavior.

electromagnetic transient simulations↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations: Preprint

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: droop, virtual synchronous machine (VSM), and dispatchable virtual oscillator control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy with up to 150x lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

circuit-equivalent model↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: Droop, Virtual Synchronous Machine (VSM), and dispatchable Virtual Oscillator Control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy, and with no explicit tuning of the solver, lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

electromagnetic transient simulation↗

Virtual Self-Excited Induction Generator-Based Grid-Forming Inverter Control for Robust Voltage Regulation Under Nonideal Loading

This paper presents a generator-inspired control methodology for grid-forming (GFM) inverters that deliberately emulates a self-excited induction generator so that the inverter can hold its voltage and frequency under difficult loading and severe terminal disturbances across wide voltage and frequency ranges. The design integrates a Lyapunov energy function-based inner loop to provide high bandwidth and strong disturbance rejection, and it complements this with a passivity-based argument that furnishes a coherent large-signal stability guarantee beyond small-signal limits. Analytical insights are developed via the Krylov-Bogoliubov-Mitropolsky averaging method, which reveals an intrinsic resistive droop characteristic; these closed-form relations both explain the observed dynamics and yield simple, decentralized tuning rules. The methodology is validated on a controller-hardware-in-the-loop platform and exercised in real time across balanced, unbalanced, and nonlinear loads, as well as during parallel operation. Across these scenarios, the inverter maintains balanced three-phase voltages, limits harmonic content, settles quickly with well-damped transients, and remains resilient when multiple units operate in parallel. The contributions are a self-excited-machine-inspired GFM controller with enhanced dynamic performance and robustness, a single stability rationale grounded in passivity, closed-form expressions that guide tuning, and comprehensive hardware-in-the-loop validations demonstrating effectiveness and superiority under challenging operating conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Two-Stage Current Limiting Control Strategy for Direct-Droop-Controlled Grid-Forming Inverters

This paper presents a two-stage current limiting control strategy with fault ride-through capability for the direct-droop-controlled grid-forming (GFM) inverters. The proposed approach comprises Stage 1 and Stage 2 current limiting controls. During faults, Stage 1 current limiting control instantly clamps the inverter output current magnitude to its maximum transient limit by blocking the switching pulses to the insulated-gate bipolar transistors (IGBTs) with the help of a hysteresis loop control, and Stage 2 current limiting control limits the inverter output current magnitude to its steady-state limit by regulating the amplitude and frequency of the modulating waveform utilizing the active and reactive current limiting control loops. By implementing the current limiting actions in two stages, this approach can effectively limit the over-current within a few cycles after the fault occurrence and ensure synchronism to the grid after long-term fault events. The efficacy of the proposed control approach is validated through electromagnetic transient (EMT) simulation results conducted on a single GFM inverter-based test system and the IEEE 39-bus test system with multiple GFM inverters in the PSCAD platform.

Mohiuddin, Sheik Mohammad↗

Large-signal Stability Analysis of Grid-forming Inverters with Equivalent-circuit Models

Here, this paper proposes an energy function-based direct method for large-signal stability assessment of grid-forming (GFM) inverters leveraging an equivalent-circuit representation of all involved control- and physical-layer dynamics. Three different primary controls, a standard inner-current outer-voltage cascaded-control architecture, output LCL filter, and reference-current saturation limiting are featured in the modeling and analysis framework. A composite energy function for the GFM inverter is obtained by summing up individual energy contributions gleaned from the circuit representation. The approach can readily be generalized to different primary controls, output-filter arrangements, and current limiters since it is based on a circuit-theoretic foundation. Numerical simulations validate the efficacy of the approach in estimating the critical clearing time following a large-signal disturbance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Secondary Control Framework for Microgrid Interoperability With Vendor-Agnostic Grid-Forming Units: Design, Implementation, and Demonstration via Large-Scale Hardware Setup

The reliable operation of islanded microgrids increasingly depends on secondary controls that restore voltage and frequency to nominal values and ensure accurate active and reactive power sharing. Centralized secondary control architectures achieve high accuracy through global coordination at the cost of single-point failures and limited scalability compared with decentralized/distributed approaches. But a critical gap remains in addressing the interoperability and vendor-agnostic operation of secondary controls in real-world microgrids where heterogeneous diesel generator(s) and grid-forming (GFM) inverter(s) from multiple manufacturers always coexist. Practical and vendor-agnostic interoperability guidelines for the secondary control architecture of microgrids with multiple GFM units have not yet been developed; therefore, this paper proposes an interoperable and vendor-agnostic secondary control framework that operates seamlessly across GFM units from different vendors without relying on proprietary controls and protocols, hardware, or lock-ins. The framework leverages existing communication infrastructures (e.g., Modbus TCP/IP) to enable cost-effective deployment while addressing practical challenges, such as packet loss and quantization errors. Mitigation strategies-including data averaging, situational event-triggered control, and finite-iteration execution-are introduced to enhance reliability under real-world conditions. A generalized modeling and design framework is also presented, supported by robustness analysis to demonstrate independence from vendor-specific implementations. The proposed framework is validated through a large-scale hardware demonstration using a 3-$\phi$, 480-V, 60-Hz, 713-kVA laboratory hardware microgrid involving a heterogeneous diesel generator and multiple GFM inverters, showcasing its effectiveness in achieving stable voltage and frequency restoration and accurate power sharing under practical constraints. The results highlight the framework's potential as a scalable and practical solution for next-generation microgrids requiring openness, standard framework, and interoperability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Analysis of Grid-Forming Inverter Controls for Grid-Connected and Islanded Microgrid Integration

Autonomous grid-forming (GFM) inverter testbeds with scalable platforms have attracted interest recently. In this study, a self-synchronized universal droop controller (SUDC) was adopted, tested, and scaled in a small network and a test feeder using a real-time simulation tool to operate microgrids without synchronous generators. We presented a novel GFM inverter control adoption to better understand the dynamic behavior of the inverters and their scalability, which can impact the distribution system (DS). This paper provides a steady-state and transient analysis of the GFM power inverter controller via simulation to better understand voltage and frequency stabilization and ensure that the critical electric loads are not affected during a prolonged power outage. The controllers of the GFM inverter are simulated in HYPERSIM to examine voltage and frequency fluctuations. This analysis includes assessing the black start capability for photovoltaic microgrids, both grid-connected and islanded, during transient fault conditions. The high photovoltaic PV penetration levels open exciting opportunities and challenges for the DS. The GFM inverter control demonstrated appropriate response times for synchronization, connection, and disconnection to the grid. The DS has become more resilient and independent of fossil fuels by increasing the penetration of inverter-based distributed energy resources (DERs).

Ward, Laura (ORCID:0000000345501581)↗

Field Verification of Grid-Forming Inverter-Based Power Plant Performance for Transmission System Reliability

This report describes some examples of the operation of two grid-forming (GFM) inverter-based photovoltaic-battery hybrid power plants connected to the electric system of the island of Kauai in Hawaii. Both plants are photovoltaic power plants with battery energy storage and are connected to the networked transmission system operated by Kauai Island Utility Cooperative (KIUC), along with several other power plants including an oil-fired plant, diesel generators, small hydroelectric plants, a biofuel plant, and several other photovoltaic plants.

14 SOLAR ENERGY↗

Modelling and control coordination scheme of a wind‐to‐hydrogen set for future renewable‐based power systems

New challenges regarding system stability and efficiency arise when power systems operate with a high penetration level of inverter‐based renewable sources (IBRSs) and few synchronous generators. Since IBRSs have been on the rise, to secure the stable operation of future power systems, IBRSs will be required to support systems without having to rely on remaining synchronous generators. Also, to efficiently manage the uncertainty of renewable production, power‐to‐gas technology can provide the required flexibility. This study proposes modelling and a control coordination scheme (CCS) of a wind‐to‐hydrogen (W2H) set to optimise electricity production from a variable‐speed wind turbine generator (WTG) while helping balance between supply and demand in a system. To achieve this, a grid‐forming (GFM) inverter‐based WTG is modelled and a set of electrolyser and fuel cell is integrated at the DC circuit of a GFM‐WTG to be coordinated. Furthermore, the CCS offers an opportunity to reduce the investment cost for deploying a W2H set by utilising the control capabilities of a WTG and reducing the need for an additional device. The performance of the proposed W2H set with the CCS was verified considering the variations in system load and wind speed by using Power System Computer Aided Design (PSCAD)/ElectroMagnetic Transients including Direct Current (EMTDC).

Kim, Jinho↗

A New Impedance-Based Modeling and Stability Analysis Approach for Power Oscillations Between Grid-Forming Inverters

This paper presents a new modeling and analysis approach to address the small-signal stability issues among interconnected grid-forming (GFM) inverters. A novel phasor domain “power impedance” model is developed to capture the terminal characteristics of GFM inverters. Based on the developed models, a sum-type impedance stability criterion is proposed to analyze the power oscillations between GFM Inverters. The developed models are validated with EMT simulations and the stability analysis results using the proposed stability criterion can match both EMT simulations and eigenvalue analysis. In addition, the application of the developed model can be extended to the stability analysis of large-scale power system with high penetration of GFM inverters.