Search NASA⌕ Search

SEARCH · Search NASA

Results for “Inverter Based Resources”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 163 records · Page 9

Grid Resiliency with a 100% Renewable Microgrid

San Diego Gas & Electric Company (SDG&E) installed America’s first and largest utility-scale microgrid in Borrego Springs in 2013. The first generation Borrego Springs Microgrid utilized diesel generators to form and stabilize the microgrid island, with support from grid-scale batteries and local solar photovoltaic (PV) generation. In this project, SDG&E in partnership with National Renewable Energy Laboratory (NREL) demonstrated through modeling, simulation and utility field testing that blackstart and islanding of the microgrid can be led with 100% renewable, inverter based resources (IBRs), to help reduce community reliance on conventional generation resources. Through equipment upgrades, grid-forming island leader capability was transitioned to a battery IBR instead of the Borrego Springs Microgrid diesel generators. A new microgrid controller was integrated to the microgrid and programmed to control and manage multiple energy storage systems. Synchrophasor and other power quality data verified autonomous, high-speed response of the IBRs through blackstart, islanding, and load step testing. Results of project field evaluations provide distribution systems operators (DSO) with increased confidence that renewable, IBR can replace traditional generators to blackstart and island microgrids and rapidly establish stable island frequency with rapid changes in peak power demand. Importantly, the project validated the integration feasibility of a distributed energy resource management system (DERMS) controller that manages multiple grid-forming and grid-following IBRs, establishing a standard design interface to reduce the complexity of integrating new DERs in the future and supporting replication by the industry. As a result of learnings in this project, SDG&E has implemented the microgrid controller strategy at multiple other microgrid sites, thereby validating the replicability of the solution. Hardware-in-the-loop (HIL) simulations including power and controller HIL hardware — along with electromagnetic transient (EMT) simulations of Borrego Springs Microgrid —informed adjustments to inverter parameters and were important to characterize the performance of the IBRs in relevant operating conditions before deployment. The EMT and HIL simulations of islanding the entire community are important contributions in providing confidence in IBR performance prior to future islanding of the community in the field. High-fidelity EMT and/or HIL simulation of IBRs can de-risk field operations, and its relevance and importance as a tool is increasing as distribution grids and microgrids become more complex and dynamic with an increasing proportion of renewable generation, distributed energy storage, and two-way power and energy flows.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Development of a Practical Secondary Control for Hardware Microgrids

Practical, vendor-agnostic interoperability guidelines for the secondary control architecture of microgrids (MGs) with multiple grid-forming (GFM) inverter-based resources (IBRs) have not yet been developed. Therefore, this paper proposes a generic and vendor-agnostic secondary control architecture that operates with all GFM IBRs and synchronous generators. This secondary control does not require the use of additional measurement devices in the MG and utilizes the inherent communication systems of the GFM units, such as Modbus TCP/IP. The practical challenges of Modbus registers, such as packet loss and quantization error, and their detrimental impacts on secondary control actions are investigated. The proposed three-stage modification for any secondary control architecture to mitigate these impacts includes: 1) averaging the data read, 2) situational event-triggering of the controller, and 3) finite iteration of the controlling action. The proposed method is validated using a three-phase electric power, 480 V, 60 Hz, 500 kVA laboratory hardware microgrid with commercial two GFM IBRs and one diesel generator. The experimental results corroborates the fact the proposed modification in the secondary control architecture is advantageous for practical usage under erroneous measurements.

grid-forming inverter↗

SVM-Based Synchronized Fault Detection for 100% Renewable Microgrids

Traditional protection schemes face significant challenges when applied to microgrids with high penetrations of renewables with inverter-based resources (IBRs). The proliferation of advanced sensing and communication technologies has generated copious data, offering an opportunity to overcome these limitations using data-driven machine learning approaches. This work proposes a novel approach based on a support vector machine (SVM) for detecting faults within a 100% renewable microgrid. The approach encompasses a systematic offline training stage for the development of a linear SVM-based fault detection algorithm. This process covers offline data collection from the microgrid under study, the extraction of features such as positive- and negative-sequence components and the total harmonic distortion of the voltage and current measurements of the relays, and the design of the linear SVM-based classifier. During the online implementation, however, different classifiers can exhibit asynchronicity in detecting the fault inception at different subcycle-to-cycle period-level delays. To circumvent this asynchronicity issue, a separate algorithm is developed for each relay to estimate the fault inception time as close to the real fault time. The performance of the proposed SVM-based synchronized fault detection method is evaluated using online time-domain simulation studies on a microgrid test system. The results corroborate the reliability of the fault detection scheme when tested under various fault cases (fault types, locations, and impedances) and non-fault cases during both grid-tied and islanded operation modes.

100% microgrid↗

SVM-Based Synchronized Fault Detection for 100% Renewable Microgrids: Preprint

Traditional protection schemes face significant challenges when applied to microgrids with high penetrations of renewables with inverter-based resources (IBRs). The proliferation of advanced sensing and communication technologies has generated copious data, offering an opportunity to overcome these limitations using data-driven machine learning approaches. This work proposes a novel approach based on a support vector machine (SVM) for detecting faults within a 100% renewable microgrid. The approach encompasses a systematic offline training stage for the development of a linear SVM-based fault detection algorithm. This process covers offline data collection from the microgrid under study, the extraction of features such as positive- and negative-sequence components and the total harmonic distortion of the voltage and current measurements of the relays, and the design of the linear SVM-based classifier. During the online implementation, however, different classifiers can exhibit asynchronicity in detecting the fault inception at different subcycle-to-cycle period-level delays. To circumvent this asynchronicity issue, a separate algorithm is developed for each relay to estimate the fault inception time as close to the real fault time. The performance of the proposed SVM-based synchronized fault detection method is evaluated using online time-domain simulation studies on a microgrid test system. The results corroborate the reliability of the fault detection scheme when tested under various fault cases (fault types, locations, and impedances) and non-fault cases during both grid-tied and islanded operation modes.

100% microgrid↗

Studying the Impact of Momentary Cessation of IBRs Compliant With IEEE Std. 2800-2022 on Transmission Line Protection Elements

This paper examines the impact of inverter-based resource (IBR) momentary cessation timing on transmission system protection relays. IEEE Std. 2800 mandates voltage ride-through, requiring IBRs to remain online during voltage disturbances. However, for severe voltage dips (|V| = 0.1 p.u.), the standard permits current blocking. In practice, vendors implement momentary cessation with varying delays, potentially affecting relay operation if IBRs cease too early. This article studies the impact of the time IBRs enter momentary cessation on transmission line protective relays. Using an electromagnetic transient (EMT) simulation, this study models IBR momentary cessation with tunable delays in a realistic transmission network. COMTRADE files generated from EMT simulations are analyzed in MATLAB using detailed protective relay models. Results indicate that IBRs must sustain operation for at least one cycle to ensure proper relay response; otherwise, relays may fail to oper- ate. These findings guide IBR vendors in optimizing momentary cessation settings to enhance transmission line protection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Transient Stability Study of IEEE 2800-2022 Standard Negative-Sequence-Current Compliant GFM IBRs

The primary function of grid-forming (GFM) inverter-based resources (IBRs) is to maintain voltage and fre- quency/phase angle stability; however, during unbalanced grid faults, IEEE Std. 2800-2022 requires IBRs to inject both positive- and negative-sequence reactive current. Enforcing compliance with this standard could compromise the stability of GFM IBRs under such fault conditions. This paper presents a preliminary transient stability study focused on the power angle stability of GFM IBRs operating in compliance with IEEE Std. 2800 during unbalanced faults. The goal is to assess potential stability issues associated with the standard's current injection requirements under fault ride-through conditions. The results show that injecting positive-sequence current with d-axis priority during unbalanced faults better preserves the power angle stability than the q-axis priority while still enabling negative-sequence current injection. These findings suggest that, to ensure stability, GFM IBRs might need to partially comply with IEEE Std. 2800 by prioritizing positive-sequence current injection along the d-axis.

14 SOLAR ENERGY↗

Adaptation of virtual synchronous generators to dynamic conditions in power grids

Virtual synchronous generators (VSGs) are widely adopted as grid-forming controls for inverter-based resources. However, when grid conditions vary significantly as characterized by changes in short-circuit ratio (SCR) and the reactance-to-resistance (X/R) ratio, fixed-gain designs and the commonly used P–Q decoupling assumption can become inaccurate. Such conditions can degrade transient power performance, leading to oscillations, prolonged settling, and overshoot, particularly in stiff-grid operating points. This paper quantifies how grid strength and impedance-dependent coupling affect the active–reactive power dynamics of a conventional VSG over a broad range of SCR and X/R values. An adaptive VSG tuning framework is then developed by combining (i) a coupling-explicit, impedance-parameterized state-space model to enable systematic controller synthesis, (ii) a full-state-feedback law designed via pole placement to meet prescribed damping and settling-time specifications, and (iii) a physics-informed neural network (PINN)–based online grid-impedance estimator that updates controller gains in real time as grid conditions vary. Offline simulations in MATLAB/Simulink and real-time validation on an OPAL-RT platform show that the proposed method preserves consistent damping and settling behavior with reduced overshoot across wide SCR and X/R ranges, compared with fixed-gain VSG baselines.

Adaptive control↗

Threat Hunt Guide for BESS Environments

The rapid digitalization of the electric grid - driven by the integration of inverter-based resources (IBRs), battery energy storage systems (BESS), and advanced grid control platforms - has significantly enhanced grid efficiency, visibility, and flexibility. However, this evolution also introduces new cybersecurity risks, particularly through supply chain dependencies and operational blind spots at the grid edge. To address these challenges, Idaho National Laboratory (INL), through the Department of Energy (DOE) Office of Cybersecurity, Energy Security, and Emergency Response (CESER) Rapid Risk initiative, conducted a series of rapid risk assessment engagements with energy organizations across the United States. Drawing on lessons learned from these engagements, INL developed the following threat hunting guide for asset owners and operators (AOOs) to enhance their cybersecurity visibility within BESS and IBR systems. The guide demonstrates how to use passive network monitoring to baseline device behavior, detect adversarial activity, and investigate anomalies without disrupting operations. By implementing these practices, energy sector stakeholders can improve coordination between cybersecurity and operations teams and strengthen the resilience of distributed energy resources (DERs) within the modern power grid. Prior to implementing any network monitoring, packet capture, or threat hunting activity described in this guide, AOOs are strongly advised to review applicable governance frameworks, legal requirements, and organizational policies. This guide is intended for informational and educational purposes only. It does not replace compliance with any federal, state, or local cybersecurity mandates or industry standards. Implementation of described configurations, technologies, or analytic workflows is performed at the discretion and responsibility of the asset owner and operator.

25 - ENERGY STORAGE↗

End-To-End Decentralized Transmission Line Protection in IBR-Dominated Weak Grids Using Interpretable Data-Driven Methods

Traditional transmission line protection relies on predictable synchronous-based fault signatures, which frequently fail under the non-standard, current-limited fault characteristics of Inverter-Based Resources (IBRs). This study investigates how to achieve secure, communication-free fault isolation in IBR-dominated weak grids without relying on opaque, computationally heavy "black-box" machine learning algorithms. To address this, we propose a novel, standalone, and inherently interpretable data-driven protection framework. Unlike centralized methods requiring multi-terminal communication, this decentralized approach relies solely on local measurements using a hierarchical linear-kernel Support Vector Machine (SVM). The methodology decomposes the protection task into four sequential stages that mimic traditional protection elements: fault detection and fault direction identification, fault type classification, zone classification, and location estimation. This multi-stage architecture allows for specialized feature engineering at each stage, combining high computational efficiency with logic traceability. The framework's end-to-end performance was validated via C-code and PSCAD/EMTDC co-simulation, utilizing a real-world utility network and an OEM black-box IBR model. The proposed relay achieves 97.2% overall accuracy and provides a reliable trip decision within a 2.5-cycle window. The results confirm 100% accuracy in fundamental fault detection, reliable zone selectivity across low to moderate fault resistances, and robust security against non-fault transients, proving its immediate viability for integration into commercial numerical relays.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Dynamic security assessment of systems powered only by grid-forming power plants with uncertain dispatch using polynomial vectors

A modern challenge in power engineering is to perform the dynamic security assessment (DSA) of grids that are 100% powered by inverter-based resources (IBRs). Addressing this challenge is difficult because: (i) the dispatch of IBRs can be uncertain as a result of the variability of renewable resources and (ii) they have hard current control limits that cannot be neglected, contrasting synchronous machines. To address this problem, this paper sets forth a framework to conduct DSA of bulk power systems that are 100% powered by grid-forming IBRs. Furthermore, the framework considers that IBR operational conditions are unknown but bounded by a zonotope which is also expressed as a polynomial vector for uncertainty propagation via Dormand–Prince integration. The framework is applied to modified versions of the WSCC 9-bus and IEEE 39-bus grids.

14 SOLAR ENERGY↗

Active Learning of Microgrid Frequency Dynamics Using Neural Ordinary Differential Equations

Accurate frequency modelling of inverter‐based resource (IBR)‐dominated power systems is crucial for ensuring stable, reliable and resilient operations, particularly given their inherent low‐inertia characteristics and fast dynamics that traditional swing equation‐based models inadequately capture. This paper explores neural ordinary differential equations (Neural ODEs) as a computationally efficient, data‐driven framework for modelling power system frequency dynamics, specifically within microgrids integrating high penetrations of distributed energy resources (DERs). The developed neural ODEs framework incorporates a neural network architecture designed to capture input dynamics. By actively perturbing the system with a known signal, the Python‐based neural ODEs framework was trained using measured system states and inputs, without the need for detailed system information. The framework, tested on a model of the Cordova, AK, microgrid, achieved a goodness of fit ranging from 60% to 99% across different state variables and maintained a mean square error in the 10 -6 p.u. range under square and step excitation signals. The proposed approach demonstrated robustness to measurement noise and initial condition variations while maintaining low computational complexity suitable for real‐time power system control applications. Furthermore, transfer learning enabled the neural ODEs model to adapt to the following changes in system topology or generator dispatch, highlighting its effectiveness for dynamic microgrids with frequently evolving configurations and diverse DERs.

Aryal, Tara [South Dakota State Univ., Brookings, ↗

Inertia Estimation and Trend Analysis of the United States Power Grid Interconnections

The transition from conventional to modern power systems is causing an increase in integration of inverter-based resources (IBRs). This generally leads to a decrease in total system inertia, which in-turn increases the system’s rate-of-change-of-frequency (RoCoF) during disturbances. This poses a threat to the frequency stability of the system and may falsely trigger protective devices. To monitor system status and plan for integrating renewable energy sources like photovoltaic, wind, and energy storage systems, a realistic study of inertia estimation and analysis in the United States (US) over the past decade is needed. This paper uses field-measured phasor measurement unit (PMU) data collected throughout the US from 2013 to 2023 via the Frequency Monitoring Network (FNET/GridEye) operated by the University of Tennessee, Knoxville (UTK) and Oak Ridge National Laboratory (ORNL). The collected PMU frequency data is utilized to estimate the system inertia of the three US interconnections: Eastern, Western, and Texas. Various RoCoF time windows are investigated for estimating the inertia of each interconnection by maximizing the correlation coefficient between the measured RoCoF and power mismatch. The resulting inertia trends over the past decade show approximately a 6% decline in inertia in the Eastern interconnection, a 15% decline in inertia in the Western interconnection, and a 16% increase in inertia in Texas. Key insights into how inertia is changing amidst the complex energy landscape are extracted using the fuel mix trend data. This provides valuable information for future energy strategies and planning.

30 DIRECT ENERGY CONVERSION↗

Performance Evaluation of a Novel Sequence-Based Directional Detection Strategy for Protection of Active Distribution Networks

Directional elements are relied on to achieve selectivity in fault detection in power systems. Although such elements have been deployed successfully for many years, there is an increased need for novel methods to deal with the unique challenges of directional protection in modern distribution networks. This article analyzes the impact of inverter-based resources (IBRs) on existing directional protection methods in distribution systems. It identifies parts of such elements that pose a risk of misoperation when IBRs are used in distribution networks. The authors have developed a new directional detection method for unbalanced faults in such networks using superimposed symmetrical sequence quantities. The phase angle of the superimposed negative sequence admittance is used to determine fault direction. The paper also presents a real-time co-simulation platform between a simulated distribution system and physical protection relay, using OPAL-RT. An SEL-411L relay is used to program the detection algorithm. This hardware-in-the-loop (HIL) setup is used to verify the performance of the method and the results are compared with existing directional methods

24 POWER TRANSMISSION AND DISTRIBUTION↗

Toward 100% Renewable Power Grids: A Review

The transition to a 100% renewable power grid remains beset by significant technical challenges. This paper critically examines the obstacles arising from the variability and unpredictability of renewable energy sources (RES), which complicate the real-time balancing of power generation and load demand. In addition to traditional stability concerns (e.g., rotor angle, voltage, and frequency stability), the increasing penetration of inverter-based resources (IBRs) introduces novel challenges, including resonance stability issues and converter-driven dynamics. Moreover, the dynamic behavior and fault response of IBRs diverge markedly from those of conventional synchronous generators, rendering traditional protection schemes increasingly inadequate. This paper reviews state-of-the-art solutions in power balancing, grid flexibility, stability enhancement, and advanced protection strategies, discussing their implications for future grid design. The analysis provides a comprehensive assessment of recent technological advancements, thereby outlining critical research directions essential for achieving a resilient, 100% renewable power grid.

100% renewable power grid↗

Development of a Practical Secondary Control for Hardware Microgrids

Practical, vendor-agnostic interoperability guidelines for the secondary control architecture of microgrids (MGs) with multiple grid-forming (GFM) inverter-based resources (IBRs) have not yet been developed. Therefore, this paper proposes a generic and vendor-agnostic secondary control architecture that operates with all GFM IBRs and synchronous generators. This secondary control does not require the use of additional measurement devices in the MG and utilizes the inherent communication systems of the GFM units, such as Modbus TCP/IP. The practical challenges of Modbus registers, such as packet loss and quantization error, and their detrimental impacts on secondary control actions are investigated. The proposed three-stage modification for any secondary control architecture to mitigate these impacts includes: 1) averaging the data read, 2) situational event-triggering of the controller, and 3) finite iteration of the controlling action. The proposed method is validated using a 3-..phi.., 480 V, 60 Hz, 500 kVA laboratory hardware microgrid with commercial two GFM IBRs and one diesel generator. The experimental results corroborates the fact the proposed modification in the secondary control architecture is advantageous for practical usage under erroneous measurements.

communication systems↗

Modeling and Power-Hardware-in-the-Loop Validation of Synchronous Wind: An Inverterless Grid-Forming Wind Power Plant

Grid-forming (GFM) control of Type-3 and Type-4 wind turbine generators (WTGs) has attracted substantial attention in power systems research; however, the limited overcurrent capability of power electronics converters continues to deteriorate the grid strength of the evolving power systems. Synchronous wind, also known as a Type-5 WTG, offers a unique GFM solution to address grid integration and grid strength issues by keeping the grid largely synchronous at very high integration levels of renewable generation. A Type-5 WTG interfaces with the electric grid via a synchronous generator driven by a variable-speed hydraulic torque converter; hence, the wind rotor operates in variable-speed mode for maximum power generation, and the generator shaft remains synchronous to the grid. This paper develops and tests a high-fidelity model of a Type-5 WTG in a power-hardware-in-the-loop (PHIL) testing environment. The PHIL demonstration shows that a Type-5 WTG inherently behaves as a GFM unit and can obtain similar performance in terms of power responses, wind rotor dynamics, and efficiency compared to a Type-3 WTG in high-wind conditions. The developed model provides further insight into how Type-5 WTGs can benefit the smooth transition to power systems with high integration levels of inverter-based resources.

grid strength↗

Optimization-Based Model Reduction Scheme for Renewable Energy Power Plants Using Standardized Testing Scenarios

This paper presents an optimization-based model reduction scheme for renewable energy (RE) power plants consisting of inverter-based resources (IBRs) operating in grid-following (GFL) or grid-forming (GFM) modes. More importantly, the datasets feeding the optimization-based model reduction scheme are generated and re-used through the standardized grid-interactive testing scenarios. Particularly, the proposed scheme makes use of the power plant point of common coupling (PCC) measurements of various quantities specified by standardized tests (e.g., voltage and frequency ride through) as per IEEE 2800, to estimate the parameters of the reduced-order model such that its dynamic performance aligns with the original detailed power plant model. The proposed model reduction approach does not require the parameters of individual IBRs and using standardized test data as input to the formulated optimization problem simplifies the reduced-order modelling scheme. Extensive case studies following standardized test scenarios verified the remarkable accuracy of the proposed approach.

Yallamilli, Ram S. [Purdue University]↗

Small-Signal Stability Constrained Optimal Power Flow of Inverter-Dominated Power Systems with Flexible Operation Mode Selection

Given the intermittence and low inertia nature of inverter-based resources (IBRs), modern power systems with high penetration of IBRs challenge the conventional optimal power flow (OPF) analysis and the system may experience unexpected failures if stability constraints are not incorporated. This study proposes a small-signal stability-constrained OPF (SSSC-OPF) with flexible operation mode selection between grid-forming (GFM) and grid-following (GFL) modes for IBRs to address these challenges. The approach aims to maintain system stability with a sufficient stability margin while minimizing operation costs. The effectiveness of the proposed method is validated through extensive case studies on the IEEE 14-bus system. The results demonstrate that the proposed method is able to support system-level power flow analysis, reduce generation costs, and ensure stability under various disturbances.

grid-following↗