Impedance-Based Prediction of SSR-Generated Harmonics in Doubly-Fed Induction Generators

Doubly-fed induction generators (DFIGs) are prone to subsynchronous resonance (SSR) with series-compensated transmission lines and experiencing SSR-generated harmonics of wide-ranging magnitudes. This paper presents a large-signal impedance-based approach for the prediction of the magnitude of SSR-generated harmonics in DFIGs. Note that the large-signal impedance of a network shows variation in its impedance response with the magnitude of perturbation at its terminals. It is discovered in this paper that the impedance of a series-compen- sated transmission line starts changing with the magnitude of SSR because of the metal-oxide varistor-based protection of series capacitors in the line. The changing line impedance halts the growth of the SSR beyond a certain point, where the DFIG forms a limit-cycle mode and emits harmonics at the SSR frequency. The discovered role of the protection of series capacitors in SSR not only enables the prediction of SSR-generated harmonics but also can be used for the timely detection of an SSR event to avoid system disruption and sudden loss of bulk generation. The large- signal impedance-based prediction of SSR-generated harmonics in DFIG-based wind and hydro generators is demonstrated using numerical simulations of a 2.5-MVA, 690-V DFIG supplying to a series-compensated transmission line.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Aqueous Bromide Discharges from U.S. Coal-Fired Power Plants: Points of Origin, Concentration Ranges, and Effluent Treatment Costs

Bromide discharges from coal-fired power plants have received increased attention from regulatory bodies due to their contribution to the formation of disinfection byproducts (DBPs) in downstream drinking water treatment plants. Here, this paper characterizes the relative contributions of bromide from coal feedstocks and bromine-based mercury control processes, estimates the distribution of bromide concentrations at 85 active coal-fired power plants across the United States (U.S.) with wet flue gas desulfurization units, and estimates the cost of bromide removal from wastewater discharge using year 2020 data. Bromide discharges are estimated at the plant level using a combination of the reported coal rank and composition combusted, estimates of bromide addition in mercury control techniques under multiple halogen addition scenarios, and the estimated flue gas desulfurization (FGD) wastewater flow rate. The median, simulated plant-level estimation of total FGD wastewater flow is 18.3 gallons/min at a bromide concentration of 319 mg/L, equivalent to ~11.6 tonnes/year of bromide discharges to the environment. Next, we evaluated the expected cost of employing the best available technology (BAT) to control bromide discharges in FGD wastewater to prevent contributions to DBP formation. Treatment would need to remove more than 99.8% of bromide to reach the 0.2 mg/L voluntary incentive program (VIP) limit. The total cost of treatment depends on whether disposal is on- or off-site; the average costs for all plants combined come to an average of $110 million ($95.2/kgal) in 2021 U.S. dollars for on-site disposal, or $134 million ($115/kgal) for off-site disposal.

01 COAL, LIGNITE, AND PEAT↗

PID-Regulated Heating System for PIP-II Reference Line

The Proton Improvement Plan 2 (PIP-II) centers on building a new superconducting linear particle accelerator (Linac) at Fermilab. At the heart of the accelerator is the reference line. It is a critical system that defines the ideal path for the beam as it passes through magnets, RF cavities, and other beamline elements. Temperature stability is crucial for the reliable operation of RF components, such as mixers and filters. Fluctuations affect key performance parameters like conversion loss, isolation, and linearity. To mitigate any drift caused by ambient temperature changes, a heating plate assembly is utilized to maintain key components at a controlled temperature of 40 C. Utilizing an actively regulated heating system, a metal-oxide-semiconductor field-effect transistor (MOSFET) based power control circuit which provides input to a controller; forming a closed-loop system that maintains the desired setpoints with high precision.

Mosher, Alexander [U. Illinois, Chicago]↗

Human Factors for Advanced Reactors

Existing light water reactors in the U.S. are primarily large baseload electricity generating facilities. The concept of operations for these plants remains largely unchanged since the advent of commercial nuclear power—the main control room serves as the hub of plant activities and is staffed with multiple licensed operators who work in tandem under the shift supervisor, and staff such as field workers support the control room remotely. While newer plants have brought the advent of digital human-machine interfaces to replace earlier analog and mechanical instrumentation and controls, much of the control process remains unchanged and manual. It is simply a newer version of legacy concepts. Advanced reactors potentially bring considerable changes to the size, fuel type, automation, and staffing of nuclear power plants, necessitating a fundamental shift not just from analog to digital, but further from human to automation, from onsite to remote, from control to monitoring, and from many to few operators. Despite this multitude of parallel evolutions in reactor designs, many of the vendors developing the next generation of reactors represent smaller research and development enterprises. It is therefore not feasible to address all aspects of plant design at the same time. In particular, the competing design aspects of new reactors present a significant challenge to the development of robust and human factored systems at the plant. As vendors develop new reactor designs, much of the early focus is naturally on the fuel and reactor system technology. Looming behind these early advances is the daunting prospect of first-of-a-kind control concepts that have not yet been developed or validated. A failure to address the human element of reactor design early will lead to missed opportunities. The quickest development process is the replication of existing concepts of operations at legacy plants, even when such systems were long ago surpassed by better human-machine technologies outside the nuclear industry. Conversely, attempting to undertake novel concepts of operations late in the design life cycle of a plant could result in protracted development efforts and delays in licensing and deployment. This does not have to happen, and it is imperative that human factors be considered now, early in the design of new reactors.

99 GENERAL AND MISCELLANEOUS↗

Cyber-Physical Smart Light Control System Integration with Smart Grid using Zigbee

This paper presents a hardware-in-the-loop cyber-physical system architecture design to monitor and control smart lights connected to the active distribution grid. The architecture uses Zigbee-based (IEEE 802.15.4) wireless sensor networks and publish-subscribe architecture to exchange monitoring and control signals between smart-light actuators (SLAs) and a smart-light central controller (SLCC). Each SLA integrated into a smart light consists of a Zigbee-based endpoint module to send and receive signals to and from the SLCC. The SLCC consists of a Zigbee-based coordinator module, which further exchanges the monitoring and control signals with the active distribution management system over the TCP/IP communication network. The monitoring signals from the SLAs include light status, brightness level, voltage, current, and power data, whereas, the control signals to the SLAs include light intensity, turn ON, turn OFF, standby, and default settings. We have used our existing hardware-in-the-loop (HIL) cyber-physical system (CPS) security SCADA testbed to process signals received from the SLCC and respond suitable control signals based on the smart light schedule requirements, system operation, and active distribution grid dynamic characteristics. We have integrated the proposed cyber-physical smart light control system (CPSLCS) testbed to our existing HIL CPS SCADA testbed. We use the integrated testbed to demonstrate the efficacy of the proposed algorithm by real-time performance and latency between the SLCC and SLAs. The experiments demonstrated significant results by 100% realtime performance and low latency while exchanging data between the SLCC and SLAs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Pushing the Envelope-Moving Dynamic Building Envelope Thermal Energy Storage Systems Mainstream: Preprint

Buildings contribute to nearly 40% of the U.S. national energy consumption and a significant portion of CO2 emissions. More importantly, disadvantaged communities are disproportionately affected by energy burden and thermal discomfort in their homes. This paper will discuss two novel DOE's BTO supported thermal energy storage (TES) integrated dynamic building envelope technologies, their ability to harvest ambient energy, and improve energy efficiency by reducing HVAC loads and peak electricity demand while enhancing energy and thermal resilience in buildings. The paper will also discuss the recent advancements that have made these systems more affordable and easier to integrate into new and existing buildings. The first solution is a thermally anisotropic building envelope (TABE) system that can redirect ambient thermal energy (heat or coolness) from diurnal outdoor conditions, solar irradiance, and night sky radiation from the envelope to a hydronic loop. The redirected thermal energy can be stored in a TABE-integrated thermal energy storage system and use the stored energy to offset HVAC energy use and peak demand. The second solution is an innovative plug-and-play thermal switch in the form of insertable plugs integrated with a phase change material (PCM). The plug can vary its thermal resistance based on the indoor and outdoor conditions, thus allowing preferential directional heat flow, and enhancing utilization of free ambient cooling and heating to charge/discharge the PCM, much like a solid-state economizer. While the fist solution can be actively controlled, the second solution is passive, requiring no external power, and work solely based on the ambient temperature.

anisotropic envelope↗

Pushing the Envelope—Moving Dynamic Building Envelope Thermal Energy Storage Systems Mainstream

Buildings contribute to nearly 40% of the U.S. national energy consumption and a significant portion of CO2 emissions. More importantly, disadvantaged communities are disproportionately affected by energy burden and thermal discomfort in their homes. This paper will discuss two novel DOE's BTO supported thermal energy storage (TES) integrated dynamic building envelope technologies, their ability to harvest ambient energy, and improve energy efficiency by reducing HVAC loads and peak electricity demand while enhancing energy and thermal resilience in buildings. The paper will also discuss the recent advancements that have made these systems more affordable and easier to integrate into new and existing buildings. The first solution is a thermally anisotropic building envelope (TABE) system that can redirect ambient thermal energy (heat or coolness) from diurnal outdoor conditions, solar irradiance, and night sky radiation from the envelope to a hydronic loop. The redirected thermal energy can be stored in a TABE-integrated thermal energy storage system and use the stored energy to offset HVAC energy use and peak demand. The second solution is an innovative plug-and-play thermal switch in the form of insertable plugs integrated with a phase change material (PCM). The plug can vary its thermal resistance based on the indoor and outdoor conditions, thus allowing preferential directional heat flow, and enhancing utilization of free ambient cooling and heating to charge/discharge the PCM, much like a solid-state economizer. While the fist solution can be actively controlled, the second solution is passive, requiring no external power, and work solely based on the ambient temperature.

Shrestha, Som↗

Nanoelectromechanical Control of Spin–Photon Interfaces in a Hybrid Quantum System on Chip

Color centers (CCs) in nanostructured diamond are promising for optically linked quantum technologies. Scaling to useful applications motivates architectures meeting the following criteria: C1 individual optical addressing of spin qubits; C2 frequency tuning of spin-dependent optical transitions; C3 coherent spin control; C4 active photon routing; C5 scalable manufacturability; and C6 low on-chip power dissipation for cryogenic operations. Here, we introduce an architecture that simultaneously achieves C1–C6. We realize piezoelectric strain control of diamond waveguide-coupled tin vacancy centers with ultralow power dissipation necessary. The DC response of our device allows emitter transition tuning by over 20 GHz, combined with low-power AC control. We show acoustic spin resonance of integrated tin vacancy spins and estimate single-phonon coupling rates over 1 kHz in the resolved sideband regime. Combined with high-speed optical routing, our work opens a path to scalable single-qubit control with optically mediated entangling gates.

77 NANOSCIENCE AND NANOTECHNOLOGY↗

A Cost-Effective Wave Energy Harvesting System with Maximum Power Point Tracking Capability

In this paper, we propose a low-cost bidirectional four-switch inverter that transfers three-phase energy between a permanent magnet synchronous generator (PMSG) driven by a wave energy collector and the power grid or a local ac load. To achieve high control performance, the machine-side inverter uses a high-gain observer for rotor position estimation and a Lyapunov-based approach for torque control. For the gridside inverter control, we estimate the filter capacitor voltage with a model reference adaptive system and control the dc-link voltage with a Lyapunov-based energy function. We also track the maximum power point from the sea waves with an integral control law that actively matches the generator impedance with that of the wave collection device. The proposed system supports both grid-following/forming modes. We validate our control design with simulation results on a 3-kW hardware setup.

wave energy, power systems integration, control de↗

Optimal Control Strategy With Efficiency and Reliability Improvement for Offshore DC Microgrids

Offshore microgrids, due to their remote location and lack of external energy support, face significant challenges in wide-range load operation and maintenance. Consequently, efficiency and reliability are critical concerns for converters in offshore dc microgrids. This article presents an optimal control strategy aimed at enhancing both efficiency and reliability. A normalized nonlinear relationship between power loss and thermal stress of a paralleled converter is first established. Based on this, a dual-objective optimization function with an active weight function as well as a system overall performance index is established. The active weight function dynamically adjusts the control priority based on converter efficiency and switching device thermal stress. Then, the optimal power-sharing strategy is derived by the Lagrange multiplier method with the proposed optimal function. Additionally, to accommodate a wide load range, an optimal selection strategy for operating converter combinations is proposed, requiring only low-bandwidth communication. Experiment verification is given to validate the effectiveness of the proposed control strategy. The experiment results demonstrate that the proposed control strategy can improve the overall performance of offshore microgrids by optimizing efficiency and reliability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Grid-Forming Split-Phase Three-Leg Inverter with Unbalanced Loading and Active Power Decoupling

This paper presents a split-phase three-leg inverter that regulates 180-degree phase-shifted AC voltages to support residential house loads under unbalanced loading conditions and decouples double line frequency power pulsation by utilizing the third half-bridge switching leg. The active power decoupling function is added without extra active switching components. The control feasibility and effectiveness are verified through MATLAB Simulink simulation and controller hardware-in-the-loop test.

Kim, Namwon [ORNL] (ORCID:0000000200438489)↗

A Localized Cyber Threat Mitigation Approach For Wide Area Control of FACTS

We propose a localized oscillation amplitude monitoring (OAM) method for the mitigation of cyber threats directed at the wide area control (WAC) system used to coordinate control of Flexible AC Transmission Systems (FACTS) for power oscillation damping (POD) of active power flow on inter-area tie lines. The method involves monitoring the inter-area tie line active power oscillation amplitude over a sliding window. We use system instability - inferred from oscillation amplitudes growing instead of damping - as evidence of an indication of a malfunction in the WAC of FACTS, possibly indicative of a cyber attack. Monitoring the presence of such a growth allows us to determine whether any destabilizing behaviors appear after the WAC system engages to control the POD. If the WAC signal increases the oscillation amplitude over time, thereby diminishing the POD performance, the FACTS falls back to POD using local measurements. The proposed method does not require an expansive system-wide view of the network. We simulate replay, control integrity, and timing attacks for a test system and present results that demonstrate the performance of the OAM method for mitigation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Model-Agnostic Algorithm for Real-Time Attack Identification in Power Grid using Koopman Modes

Malicious activities on measurements from sensors like Phasor Measurement Units (PMUs) can mislead the control center operator into taking wrong control actions resulting in disruption of operation, financial losses, and equipment damage. In particular, false data attacks initiated during power systems transients caused due to abrupt changes in load and generation can fool the conventional model-based detection methods relying on thresholds comparison to trigger an anomaly. In this paper, we propose a Koopman mode decomposition (KMD) based algorithm to detect and identify false data attacks in real-time. The Koopman modes (KMs) are capable of capturing the nonlinear modes of oscillation in the transient dynamics of the power networks and reveal the spatial embedding of both natural and anomalous modes of oscillations in the sensor measurements. The Koopman-based spatio-temporal nonlinear modal analysis is used to filter out the false data injected by an attacker. The performance of the algorithm is illustrated on the IEEE 68-bus test system using synthetic attack scenarios generated on GridSTAGE, a recently developed multivariate spatio-temporal data generation framework for simulation of adversarial scenarios in cyber-physical power systems.

Nandanoori, Sai Pushpak↗

A Cyber Threat Mitigation Approach For Wide Area Control of SVCs using Stability Monitoring

We propose a stability monitoring approach for the mitigation of cyber threats directed at the wide area control (WAC) system used for coordinated control of Flexible AC Transmission Systems (FACTS) used for power oscillation damping (POD) of active power flow on inter-area tie lines. The approach involves monitoring the modes of the active power oscillation on an inter-area tie line using the Matrix Pencil (MP) method. We use the stability characteristics of the observed modes as a proxy for the presence of destabilizing cyber threats. We monitor the system modes to determine whether any destabilizing modes appear after the WAC system engages to control the POD. If the WAC signal exacerbates the POD performance, the FACTS falls back to POD using local measurements. The proposed approach does not require an expansive system-wide view of the network. We simulate replay, control integrity, and timing attacks for a test system and present results that demonstrate the performance of the SM approach for mitigation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Structure-Activity Relationships of Hydrothermally Aged Titania-Supported Vanadium-Tungsten Oxide Catalysts for SCR of NOx Emissions with NH3

Supported V2O5-WO3/TiO2 materials employed as selective catalytic reduction (SCR) catalysts for NOx emission control from power plants. Fresh SCR catalysts usually receive exposure to harsh treatments in industry to accelerate catalyst activation (calcination in air at 650oC) and catalyst aging (hydrothermal aging at 650oC) in a way that represents various points in the catalyst/product lifetime. The present study investigates the catalyst structural and chemical changes occurring during such harsh treatments. Three series of supported V2O5-WO3/TiO2 catalysts were prepared by incipient-wetness impregnation of aqueous ammonium metavanadate and metatungstate precursors. The catalysts were subsequently dried and calcined at 550oC in O2, 650oC in O2, and hydrothermal conditions (10% O2, 8% H2O, 7% CO2 and 75% N2) at 650oC. The resulting catalysts were physically characterized by numerous techniques (in situ Raman, in situ IR, in situ High Field-High Spinning solid-state 51V MAS NMR, in situ EPR, XRD, BET surface area and ICP) and chemically probed with adsorbed ammonia, SCR-TPSR, and the SCR reaction. The surface WOx sites on the TiO2 support behave as a textural promoter that stabilizes the TiO2 (anatase) phase from sintering and transforming to the undesirable crystalline TiO2 (rutile) phase that can lead to formation of a Ti1-xVxO2 (rutile) solid solution with reduced V4+ cations (~7-15%). The surface VOx sites are mostly oligomerized as surface V+5Ox sites (~50-85% oligomers) and the extent of oligomerization tends to increase with surface WOx coverage and calcination temperature. A major difference between the calcined and hydrothermally treated catalysts was the low concentration of surface NH3* species on Lewis acid sites for the hydrothermally treated catalysts, yet the SCR activity was almost comparable for both catalysts. This finding suggests that surface NH4+*, primarily associated with the surface VOx sites, are able to efficiently perform the SCR reaction. Given that multiple catalyst parameters were simultaneously varying during these treatments, it was difficult to correlate the SCR activity with any single catalyst parameter. A correlation, however, was found between the SCR TOF/activity and the sum of the surface NH3* and NH4+* species, which is dominated by the surface NH4+* species.

SCR, NO, NH3, catalyst, V2O5, WO3, TiO2, promotion↗

Self-Secure Inverters Against Malicious Setpoints

The next generation of grid-interactive inverters brings a communication feature that allows data sharing from utility supervisory controllers and smart devices that are connected to the same network. This feature enhances the control capabilities of grid-interactive inverters to provide services beyond active power injection. However, communication networks entail more vulnerable surfaces to malicious attacks that may result in modifying active and reactive power setpoints and causing weak-grid conditions or abnormal inverter operation. In this paper, steady-state and the dynamic behavior of the inverter for the incoming setpoints are analyzed to detect false data injection attacks and provide device-level security. The steady-state behavior of the inverter in the operating region is determined from the grid parameters such as the grid voltage and the grid impedance. These estimations are accomplished by the proposed self-security technique through a low-frequency signal injection-based approach combined with the recursive least square method. Moreover, a reduced fourth-order inverter model is used as the dynamic reference model, and grid parameters as well as the incoming setpoints are implemented to the reference model to verify whether the dynamic behavior of the inverter is inside the permissible region of operation. The validity and performance of the proposed method are verified experimentally through Allen-Bradley Powerflex 755 three-phase inverter and a 12 kW NHR 9410 regenerative power grid emulator. The results show that the self-secure smart-inverter is able to accept or reject the incoming commands and thus is protected from malicious cyber-physical attacks.

Hossen, Tareq↗

Integrating Electric Vehicle Charging Infrastructure into Commercial Buildings and Mixed-Use Communities: Design, Modeling, and Control Optimization Opportunities: Preprint

This paper discusses modeling and field studies of controlled EV charging that have been performed with the goal of minimizing requirements for infrastructure upgrades, minimizing building peak demand charges, and maximizing the use of on-site generation. We present a large-scale workplace charging pilot of a demand-controlled scheduled EV charging system with over 250 active daily commuters, successfully demonstrating management of aggregate charging power to avoid new infrastructure investments, mitigate peak demand charges, and provide cost-effective workplace charging to users. In addition to understanding opportunities for demand management, integrating these controllable loads into the energy modeling process for new buildings will also be necessary. This paper then presents an example energy modeling process that evaluates the potential effects of EV charging on building load profiles and infrastructure requirements for a mixed-use community. Finally, we discuss an illustration of how EV charging can be controlled to be synergistic with other building loads and distributed generation.

buildings↗