High Impedance Fault Detection Through Quasi-Static State Estimation: A Parameter Error Modeling Approach

This paper presents a model for detecting high impedance faults using parameter error modeling and a two step per-phase weighted-least squares state estimation process. The proposed scheme leverages the use of Phasor Measurement Units and synthetic measurements to identify per-phase power flow and injection measurements which indicate a parameter error through ?2 Hypothesis Testing applied to the composed measurement error. Although current and voltage waveforms are commonly analyzed for high-impedance fault detection, wide area power flow and injection measurements, which are already inherent to the state estimation process, also show promise for real-world high-impedance fault detection applications. The error distributions after detection share the measurement function error spread observed in proven parameter error diagnostics and can be applied to high-impedance fault identification. Further, this error spread across measurement functions related to the fault will be clearly discerned from measurement error. Case studies are performed on the IEEE 33-Bus Distribution System along with the proposed model in Simulink.

Cooper, Austin↗

High-Impedance Non-Linear Fault Detection via Eigenvalue Analysis with low PMU Sampling Rates

This work presents a hybrid data-driven and physics-based framework for high-impedance fault detection in power systems. An innovative method based on eigenvalue analysis is expanded and validated. Phasor Measurement Unit data is used to estimate eigenvalues corresponding to the powerlines being monitored. The projection and drift of these eigenvalues is then tracked and evaluated. Faults are detected as they drive eigenvalues outside of their normal zones. Eigenvectors are leveraged to support and validate the decisions made by the main algorithm. This technique holds several advantages over contemporary techniques in that it utilizes technology that is already deployed in the field, it offers a significant degree of generality, and so far it has displayed a very high-level of sensitivity without sacrificing accuracy. Validation takes place in the form of simulations in the IEEE 13 Node System considering a popular high-impedance non-linear fault model. Test results are encouraging indicating potential for real-life applications.

Paramo, Gian↗

Extended Frequency Divider for Bus Frequency Estimation Considering Virtual Inertia from DFIGs

Accurate estimation of local bus frequency is important for effectively controlling both synchronous and nonsynchronous generators. As the power grid evolves to accommodate essential reliability services such as virtual inertia from nonsynchronous generators, conventional techniques to estimate frequency face challenges. This paper proposes a new frequency estimation method that can effectively include the inertia contributions from double-fed wind generators (DFIGs). This is achieved through the proposed extended frequency divider formula (FDF) to include the contributions of DFIGs via Thevenin equivalents. The proposed extended FDF does not suffer from numerical issues as compared to existing phasor angle derivative-based approaches. Moreover, the knowledge of the rotor speeds of the synchronous machine and DFIGs as well as of the network admittance matrix allows estimating the frequencies of all buses in the grid, thereby significantly improving system situational awareness with a limited number of measurements. Numerical results on the IEEE 39-bus power system with DFIGs show that the proposed method achieves more accurate bus frequency estimations than the original FDF formula and other approaches based on the numerical derivation of the bus voltage phase angles.

double-fed induction generator↗

Secondary-Side Active Rectifier Synchronization and Control in LCC-LC Compensated Inductive Power Transfer Systems

This paper proposes a communication-less synchronization and output power control strategy for LCC-LC compensated inductive power transfer systems with a secondaryside active rectifier. By replacing the passive rectifier with an active bridge, the proposed architecture eliminates the need for a separate secondary-side DC-DC converter and enables direct regulation of battery power. The key challenge in such a system is achieving robust synchronization of the secondary active bridge with the primary inverter without access to primary-side signals. To address this issue, the secondary-side variables are analyzed and the current through the secondary series inductor is identified as a load-independent synchronization variable with a fixed phase relationship to the primary excitation. A fixed-frequency second order generalized (SOGI)-based phase locked loop (PLL) is used to estimate the switching phase and frequency, and a phase-shift-based output power controller is developed using a phasor-transformer model of the active bridges. A modified control formulation is further introduced to remove phase-dependent loop-gain variation and simplify controller design. Simulation results validate the proposed method under both fixed and varying switching-frequency conditions, demonstrating successful frequency tracking from 82 kHz to 88 kHz and accurate output power regulation over a wide operating range. The proposed method offers a compact and effective solution for high-power IPT systems by enabling secondary-side synchronization and control without wireless communication or an additional DC-DC conversion stage.

Fernandes, Arnold Anthony [ORNL] (ORCID:0009000631↗

Proactive Frequency Stability Scheme via Bayesian Filters and Synchrophasors

Underfrequency (UF) load shedding schemes are traditionally implemented in two ways: One approach is based on manual load shedding, with system operators requesting loads to be shed ahead of anticipated stressful operating conditions. Manual load shedding is usually done through phone calls. The second method is automatic load shedding via underfrequency relays. Using static static settings, these schemes can be designed to operate in stages and drop previously identified loads. The main limitation of traditional load shedding schemes is that they are reactive and leave little room for optimized corrective actions. This work presents a proactive and automatic underfrequency load shedding solution for power systems. Measurements are captured via phasor measurement units (PMUs) at relatively low sampling rates of 30 Hz. These measurements are then processed by particle filters who predict the future state of the system's frequency. Based on these predictions excess load is determined and shed. Comparative case studies are performed in simulated environments. Easy-to-implement models, without hard-to-derive parameters, highlight potential aspects for real-life implementation.

Paramo, Gian↗

A Hybrid Framework Combining Model-Based and Data-Driven Methods for Hierarchical Decentralized Robust Dynamic State Estimation

This paper combines model-based and data-driven methods to develop a hierarchical, decentralized, robust dynamic state estimator (DSE). A two-level hierarchy is proposed, where the lower level consists of robust, model-based, decentralized DSEs. The state estimates sent from the lower level are received at the upper level, where they are filtered by a robust data-driven DSE after a principled sparse selection. This selection allows us to shrink the dimension of the problem at the upper level and hence significantly speed up the computational time. The proposed hybrid framework does not depend on the centralized infrastructure of the control centers; thus it can be completely embedded into the wide-area measurement systems. This feature will ultimately facilitate the placement of hierarchical decentralized control schemes at the phasor data concentrator locations. Also, the network model is not necessary; thus, a topology processor is not required. Finally, there is no assumption on the dynamics of the electric loads. The proposed framework is tested on the 2,000-bus synthetic Texas system, and shown to be capable of reconstructing the dynamic states of the generators with high accuracy, and of forecasting in the advent of missing data.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Step Towards Machine Learning-based Coherent Generator Grouping for Emergency Control Applications in Modern Power Grid

A dynamic neural network (NN) based multi-class classifier is proposed for improving online prediction of coherent generator groups (CGGs), following the occurrences of various contingencies in the power grid. This is motivated by the increasing availability of the measurements from phasor measurement units (PMUs) and the number of grouping schemes is limited. The proposed method consists of three steps. First, by performing offline simulations, a library of system dynamic responses characterized by post-contingency rotor angles and speeds of individual generators is obtained. To generate sufficient data, up to N-2 contingencies and the uncertain parameters associated with the power grid including type and location of disturbance and fault clearing times are modeled. Secondly, the training data-set is produced by generating labels for individual contingencies using a hierarchical clustering method based on rotor angle and speed data. Lastly, the dynamic NN models are trained for online applications such as emergency controls and controlled islanding. The proposed method is tested on the standard 16-generator 68-bus system to demonstrate its performance. Furthermore, the impact of the sample data lengths on the CGG numbers is evaluated. It is interesting to observe that the time domain stability behaviors can be determined by examining the changes in the CGG numbers.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Estimation Matrix Calibration of PMU Data-driven State Estimation Using Neural Network

Linear state estimation (LSE) is a phasor measurement unit (PMU) data-based power system state estimation that incorporates a linear measurement model in rectangular coordinates. Due to the high computational efficiency and high observational time-resolution, LSE can act as a supplementary state estimation in a wide-area monitoring system (WAMS). The performance of LSE is relatively sensitive to noises in measurements. Therefore, the estimation accuracy relies heavily on the accuracy of the estimation matrix, which is directly influenced by the measurement weight matrix. This paper proposes two novel calibration method of the estimation matrix using neural networks. One is based on the minimum absolute network loss (ANL), and the other is based on the minimum average squared network loss (ASNL). Both methods are tested and compared with LSE algorithms on the IEEE 14-bus system

neural network↗

Using Distributed Dynamic Voltage Restorers to Improve the Frequency Stability of Low-Inertia Networked Microgrids

This paper elucidates the novel concept of using distributed dynamic voltage restorers (DVRs), which are traditionally used to compensate for voltage sags, to improve the frequency stability of low-inertia networked microgrids. During frequency transients, the distributed DVRs rapidly regulate load voltages within an acceptable range, resulting in a fast change of load power consumption and helping improve frequency stability. To enable large-scale network simulation, a phasor-based model of DVRs is developed and validated against real data from a commercially available device. Finally, simulation results of a modified IEEE 123-node test feeder that comprises three microgrids and six DVRs verify the effectiveness of the proposed method.

Du, Wei↗

Data-Driven Adaptive Damping Controller for Wind Power Plants with Doubly-Fed Induction Generators

This paper presents an adaptive damping controller for wind power plants in which the turbines are equipped with doubly-fed induction generators. The controller is designed to respond to an input control signal that is triggered according to the system operating conditions. A processing unit continuously estimates the electromechanical modes of oscillation based on real-time streaming data acquired from a phasor measurement unit that is strategically positioned on the grid. The decision to trigger (or not trigger) the control signal is automatic, based on the relative damping of the dominant mode. The modes are estimated using the dynamic mode decomposition algorithm with time-delay embedding. Numerical simulations performed on the two-area system demonstrate that the proposed controller enhances the rotor angle stability for both small-signal and large disturbances, and is adaptive to changing grid conditions.

damping controller↗

State Estimation for Distribution Networks with Asynchronous Sensors Using Stochastic Descent: Preprint

This paper investigates the problem of state estimation for distribution networks with asynchronous sensors comprising of a mix of smart meters and phasor measurement units (PMUs) with multiple sampling and reporting rates. We consider two independent scenarios of state estimation and tracking, with either voltages or currents as states. With these two sets, we investigate estimation under (a) full data, assuming all measurements are available and (b) limited data, where an online algorithmic approach is adopted to estimate the possibly time-varying states by processing measurements as and when available. The proposed algorithm, inspired by the classical Stochastic Gradient Descent (SGD) approach updates the states based on the previous estimate and the newly available measurements. Finally, we demonstrate the estimation and tracking efficacy through numerical simulations on the IEEE-37 test network, while also highlighting how estimation with currents as states leads to faster convergence.

asynchronous sensors↗

Novel Real- Time EMT- TS Modeling Architecture for Feeder Blackstart Simulations

This paper presents the development and benchmarking of a novel real-time electromagnetic-transient and transient-stability (EMT-TS) modeling architecture for distribution feeder restoration studies. The work presents for the first time in the literature a real-time EMT-TS testbed in which the grid-forming unit is simulated in EMT domain, operating as the slack bus of the phasor domain while including unbalanced voltage conditions. To evaluate the performance and limitations of the proposed model, an equivalent EMT testbed is developed to serve as a benchmark. First, the co-simulation framework and the domain coupling methodology are introduced. Next, the steady state operation of the EMT-TS and EMT models are matched. Then, tests are conducted to analyze the transient performance of the proposed EMT-TS model when compared to its EMT benchmark. Results reveal that when utilizing a battery energy storage system (BESS) as the grid-forming unit, the EMT-TS testbed can maintain high accuracy for typical load steps.

Paduani, Victor↗

Real-time Event Detection Using Rank Signatures of Real-world PMU Data

Timely detection of power system events is a crucial task, which can facilitate the implementation of remedial actions to improve reliability, resiliency, and security of the system. Meanwhile, the widespread deployment of phasor measurement units (PMUs) makes it possible to develop data-driven event detection techniques. However, relying purely on data without incorporating domain knowledge for the event detection task in power systems poses substantial security and stability risks due to issues associated with data misinterpretation and model accuracy. In this regard, we propose a real-time event detection method using real-world PMU data by incorporating domain knowledge to adequately capture the event signatures. Specifically, we track the change in rank signatures of PMU data to accurately localize the events. To optimize the detection process, we incorporate an offline Bayesian optimization algorithm to tune the parameters by efficiently searching for the best values. The experiments using the real-world PMU dataset from a U.S. interconnection show that the proposed event detection approach can efficiently detect the events from PMU data streams with high accuracy.

Ghasemkhani, Amir↗

Weakly Supervised Event Classification Using Imperfect Real-world PMU Data with Scarce Labels

This paper studies event classification using imperfect real-world phasor measurement unit (PMU) data with scarce event types (labels). By investigating the real-world PMU data, it is observed that most real-world PMU data's event type is unknown, which makes it challenging to directly use such dataset to build event classifiers as existing classification techniques require high-quality training data with known event type (i.e., label). To address this challenge, a weakly supervised learning based event classification approach is developed, which can use noisy and low-quality PMU data for the training. First, data quality issues are fixed using data preprocessing techniques and then event features are constructed from the PMU data. Using these features, a series of labeling functions are learnt to generate initial estimates of the labels of large amounts of unlabeled PMU data. As the labeling functions are learnt using the same data with scarce labels, the label estimates from the labeling functions can be correlated, noisy, and bias. To enhance these initial estimates, a generative model is developed to characterize the dependencies among the estimated labels, based on which better labels are obtained for training event classifiers. Numerical experiments using the real-world dataset from the Western Interconnection of the U.S. power transmission grid show that the proposed weakly supervised event classifier trained using the dataset with only 5% labeled data can achieve 78.4% classification accuracy.

Liu, Yunchuan↗

Online Detection of Power Grid Anomalies via Federated Learning

Data from sensors is critical for advanced applica- tions that support efficient, reliable, and resilient electric grid operations. Historically, data from phasor measurement units (PMU) has been utilized to develop a wide variety of wide area control and protection applications suitable for power grid control centers. However, until now, most of these could not be deployed for automated operations due to a set of data corruption challenges and uncertainty in the incoming data pipeline. In this paper, we address the problem of detecting different variety of anomalies that are evident in different high- speed power grid measurements. The paper discusses a workflow for handling problems with data acquisition and highlights some of the key findings suitable for anomaly detection in a centralized and distributed environment. The effectiveness of the proposed method was demonstrated with results utilizing realistic PMU datasets

Shinkle, Matthew W.↗

PMU Data Quality and Sensor Health Monitoring

Phasor Measurement Units (PMUs) play a critical role in the evolution of the electric power industry by providing high-precision, real-time monitoring of essential power system metrics. However, effectively detecting abnormalities and critical events from PMU data is a complex task, complicated by intricate temporal patterns, a scarcity of labeled data for training algo- rithms, and constraints on online computational power. In this study, we apply TranAD, an innovative algorithm that combines transformer architectures with the refinement of adversarial learning, to both synthetic and real-world PMU datasets for developing a data quality and sensor online health monitoring platform for utilities. Our findings reveal that TranAD not only provides efficient detection and localization but also enhances the detail with which abnormalities are detected, marking a a significant step forward in the field of clean data acquisition processes for power system monitoring

deep neural network, machine learning (ML)↗

Estimation of Participation Factors Using the Synchrosqueezed Wavelet Transform

This paper proposes a data-driven approach for estimating participation factors for a power system using only simulation results on selected disturbances. The approach is purely response-based and does not need a linearized system model for eigen-analysis, which makes it applicable to systems whose detailed, complete mathematical models are not available. Considering the unavoidable nonlinearity as exhibited in the transient period of a system response, the Synchrosqueezed Wavelet Transform is applied to simulated responses for modal analysis to obtain participation factors. Based on simulations of Kundur's two-area system using both the electromagnetic transient model and phasor model, the participation factors estimated by the proposed approach are compared with two other signal processing tools, the Prony analysis and continuous wavelet transform, and are also benchmarked with conventional model-based participation factors.

participation factor↗