Interoperable, Inverter - Based Distributed Energy Resources Enable 100% Renewable and Resilient Utility Microgrids

As microgrids transition away from use of conventional generating resources and increasingly rely on renewable resources towards decarbonization goals, it is crucial to evaluate the capability inverter-based resources to provide microgrid stability and resilience. Particularly, microgrids with a high contribution of intermittent solar photo voltaic generation and higher load variability present unique challenges requiring fast voltage and frequency support. At the San Diego Gas & Electric Company(R) (SDG&E(R)) Borrego Springs Microgrid, a battery inverter was upgraded with grid-forming (GFM) capability to serve as island leader, transitioning responsibility away from diesel generators. An interoperable microgrid control scheme was developed, coordinating GFM and grid-following (GFL) inverters. Hardware-in-the-loop (HIL) simulations using relevant power and controller HIL interfaces between real-time simulators and field equipment are being conducted to de-risk field deployment.

battery energy storage↗

Performance Evaluation of Next-Generation Grid Automation and Controls with High PV Penetration

This paper presents a hardware-in-the-loop (BIL) simulation to evaluate the performance of an advanced grid automation architecture, referred to as data-enhanced hierarchical control (DEHC), in achieving voltage regulation and conservation voltage reduction (CVR) in distribution networks with very high photovoltaic (PV) generation. This architecture comprises an advanced distribution management system (ADMS), a distributed energy resource management system (DERMS), and grid-edge devices working synergistically to provide the grid benefits. The HIL setup used for the evaluation includes ADMS, DERMS, and grid-edge devices. The DEHC performance is evaluated in two representative scenarios considering loose and tight constraints of the power factor at the substation. The results show that the DEHC architecture is effective in achieving voltage regulation and CVR and thus enables the grid integration of high levels of PV generation.

ADMS↗

Evaluation of Centralized Model-Based FLISR in a Lab Setup: Preprint

Utilities are installing advanced distribution management systems (ADMS) around the globe to improve the sensing and control of distribution systems. ADMS is becoming a critical component to improve the resiliency and reliability of distribution systems. These management systems host a multitude of applications that can be used to sense, control, and operate distribution systems. Fault location, isolation, and service restoration (FLISR) is one of the ADMS applications that is critical to improving resilience during fault conditions. FLISR applications use smart, controllable devices that are installed in the distribution system for FLISR operation. These controllable devices include distributed energy resources (DER) and reclosers. Evaluating such ADMS applications before installation in the field can help de-risk the field implementation and avoid costly failures in the field. This paper presents a background on experimental setup that are typically used to evaluate ADMS applications. This is followed by briefly presenting the setup used to evaluate the FLISR application in an off-the-shelf ADMS tool. Finally, results from the evaluation experiments are presented.

94 GMLC - Grid Modernization Laboratory Consortium↗

Situational Awareness of Grid Anomalies (SAGA)

The modern power industry becomes more vulnerable to cyber events due to the growing interconnectivity, interdependence, and complexity of the electric power grid. High-fidelity modeling and simulation tools that support the preventative risk analysis on potential cyber-relevant events is essential for ensuring the situational awareness of the system operator as it provides an inexpensive and risk-free environment to test the system responses under various cyber-relevant events and hereby can support research on cyber anomaly detection, optimal protective resource allocation, and mitigation measures. In this webinar, we will share NREL's cybersecurity research capabilities by highlighting the development of a scalable cyber-physical event test bed and demonstration with real hardware in the loop. The developed cyber-physical event test bed is backboned by an integrated transmission, distribution, and communication dynamic co-simulation framework and a plug-and-play cyber event generation module. It is designed to be modular and compatible with parallel computing, and thereby supports large-scale system simulations at an affordable computation cost. The test bed can capture millisecond-to-minutes dynamic frequency and voltage responses under cyber events from the bulk transmission system to the active distribution systems and distributed energy resources at the grid edge.

co-simulation↗

Converter-Interfaced CHP Plant for Improved Grid-Integration, Flexibility and Resiliency

GE Research and its partner GE Renewables have proposed the use of an interface converter solution to increase the penetration of small to medium-sized CHP (1MWe to 20MWe) into distribution grids and improve their flexibility and grid support capability. Indeed, the proposed interface converter solution thanks to presence of the grid-ready inverter, allows to streamline the compliance to grid codes requirements, reduce the interconnection delays and costs and ultimately one of the main barriers for CHP adoption by commercial and industrial facilities. An additional benefit provided by the interface converter is the use of the grid-ready inverter for reactive power which eliminates the need of sizing the generator for that capability. These two benefits highly favor the economic feasibility of converter-interfaced CHP. Five user cases, each in one of the leading U.S states for CHP potential reported by the DOE in its estimation of the U.S Technical Potential of CHP, were selected to compare the economic performances of converter-interfaced CHP as compared with directly-coupled. They include a college campus in California, a hospital in New York, a water reclamation plant in Texas, a hotel in Minnesota, and a large office building in Pennsylvania. Results showed that, the presence of the interface converter allows to increase the return on investment (ROI) by 0.5 to 2 percentage points in most of the cases (4 of 5). Indeed, the interface converter by shortening the interconnection process allows to accelerate revenues while reducing interconnection costs. Added to the reduced cost of the required generator these savings trade favorably the capital cost of the converter. The analysis also showed that the profitability of the converter-interfaced CHP is highly sensitive to the energy price, interconnection delay, and converter cost. However, it appears that if the interface converter can shorten the interconnection process by at least 6 months, adopting this solution will be more economically viable than directly-coupled configuration in almost all the +23,000 sites of the U.S Technical Potential CHP. The evaluation of the benefits of a converter-interfaced CHP also showed that it enables higher ROI when coupled with other distributed energy resources (DER) such as battery energy systems (BESS) or solar photovoltaic (PV). Indeed, in those scenario, the grid-ready inverter included in the interface converter eliminates the need of separate inverters if DC-coupling is used. On the technical performance, it has been verified that the presence of the interface converter allows to reduce by 70% to 80% the CHP short-circuit contribution to grid faults. This not only reduces the mechanical and thermal stresses exposed to the CHP electrical components but also increases the grid hosting capacity which ultimately enables higher penetrations CHP. Another key benefit of the interface converter validated with hardware-in-the-loop simulations and testing is its superior capability for reactive power support. Indeed, using a power hardware testbed with two +700kW inverters configured in back-to-back, a microgrid controller and actual facilities loads it was demonstrated that the presence of the interface converter can help maintain a power factor near ~1 or regulate the voltage to ~1.0pu at the point of common coupling. This benefit can be highly valuable if in the future, due to higher penetration of renewable distributed energy resources (DER), utilities start billing demand charge based on kVA instead of kW as currently. It was also validated that converter-interfaced CHP can dispatch heat and power commands and seamlessly switch between the two modes while consistently controlling the power factor or voltage at PCC. Indeed, the power hardware testing showed that grid-connected converter-interfaced CHP can follow either the power or heat demand while maintaining a unity power factor at converter output. This research proved that the adoption of an interface converter as the solution for interconnection of CHP system into the distribution grid can greatly improve the economic feasibility of small to medium-sized CHP as well as the plant power quality, flexibility and resiliency. Additionally, it allows increased penetrations of CHP into the distribution grid, extends their grid support capability, and facilitates the integration of BESS and PV DER by streamlining their collocation within the same facilities. This ultimately provides an opportunity for commercial and small industrial facilities in the U.S to accelerate their energy transition thanks to the high energy efficiency of CHP systems and its reliable, flexible, and resilient microgrid operation when interconnected with an interface converter.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Understanding Line Losses and Transformer Losses in Rural Isolated Distribution Systems

Rural, isolated power systems in the mainland U.S. and in states like Alaska and Hawaii are powered by assets like diesel generators. These rural, isolated power systems also cannot operate at the higher band of medium voltage (like 69kV). They are primarily in the 12 to 14 kV range to keep the cost of the distribution investments lower. Because of this mid-band medium voltage range, the line losses and distribution transformers losses consume significant diesel consumption (almost 10 percent of the peak load). This work considers one such power system powering an isolated system and presents key findings online losses, and transformer losses. Understanding and documenting the impacts is critical for these communities operating their power systems and take actions to reduce expensive diesel consumption. In this paper, we will present one such typical grid and model it in electromagnetic transients (EMT) domain. We used the tower structure, under ground cabling installation to develop high fidelity models of lines. We also used high fidelity models of distribution transformers to present the no-load losses and full load loses. We will also present technical solutions available commercially off-the-shelf to reduce these losses and reduce diesel consumption. This work will be a primer for communities to understand the technical challenges and to understand the possible solution available to solve such challenges for rural, isolated power system operators.

blackstart↗

Real-Time Inertia Estimation Tool Implementation Based on Probing Signals

As renewable energy penetration increases and the traditional generators retire in power grids, system inertia decreases and exhibits significant daily fluctuations. Furthermore, fast frequency responses (FFRs) provided by the inverter-based resources (IBRs) begin to playa very critical role and bring new challenges to real-time system inertia monitoring due to the difficulties of quantifying its artificial inertia contribution. Thus, necessitating an accurate real-time inertia estimation tool will not only benefit the secure power grid operations, but also provide insights on assessing the artificial inertia contribution from the IBRs. This paper presents a probing-based real-time inertia estimation tool that has been validated through a power-hardware-in-the-Ioop (PHIL) test system using identical hardware battery energy storage system (BESS) and control in an actual power grid. Preliminary results indicate high estimation accuracy of the developed tool and pave the way for the field test and deployment.

inverter-based resources↗

Hawaiian Electric Company (HECO) Grid Optimization with Solar (Cooperative Research and Development Final Report)

The purpose of this project is to provide a software platform that gives utility companies the capability to seamlessly dispatch legacy devices (at both the distribution and subtransmission levels) and distributed energy resources (DERs) to achieve system-wide performance and reliability targets–such as minimizing loss, reducing voltage violation, and corresponding imbalance–for extreme solar futures with well over 100% (capacity) penetrations.

14 SOLAR ENERGY↗

High-fidelity wave data from MarineLabs CoastScout™ buoys supporting WEC demonstration at Scripps Pier

Two MarineLabs CoastScout™ buoys were deployed off La Jolla, California in February 2020 to provide high-resolution wave elevation time series data in support of CalWave Power Technologies’ XWave WEC deployment. The buoys are positioned approximately 300m from a longterm wave monitoring station operated by the Coastal Data Information Program. Both CoastScout hull types showed excellent agreement with the reference Datawell Directional Waverider MkIII (Hs r 2 =0.94, m0 r 2 =0.88). The CoastScout buoys maintained 100% uptime throughout an initial 6- month intercomparison period. CalWave used 5-Hz wave train data from this period to drive physical hardware-in-the-loop tests of the XWave power take-off. Throughout the deployment, the CoastScout buoys will provide near-real-time bulk wave parameters to help CalWave operators safely and efficiently operate the WEC. In post-processing, high-fidelity wave resolution will be used to associate individual waves with onboard measurements from Fiber Bragg Grating strain gauges and external pressure sensors.

16 TIDAL AND WAVE POWER↗

A Multi-Site Networked Hardware-in-Loop Platform for Evaluation of Interoperability and Distributed Intelligence at Grid-Edge

Electric power systems have experienced large increases in the number of intelligent, connected and controllable devices being deployed, leading to a high degree of distributed intelligence at the grid-edge. These devices, both utility-owned and consumer-owned, include but are not limited to: renewable generation sources, energy storage, remote switches, voltage regulators, and smart controllable loads such as electric vehicles. These new devices provide significant potential for increased operational flexibility that can be leveraged to achieve system reconfiguration, resiliency improvements, power quality improvements, and distribution system automation. However, there are two significant challenges that must be addressed before these assets can be leveraged for operations: interoperability and system level validation prior to deployment. Because of the complexity of distributed control systems, and their interactions with legacy centralized controls, a purely simulations-based approach for pre-deployment validation is not sufficient. It requires hardware-in-loop testing to emulate the operational hardware devices and evaluate their performance. Additionally, securely integrating multiple test facilities at utility operators and vendors might enable rapid scale-up of evaluation platforms, and remove the need for multiple expensive standalone installations. Presented in this paper, is the development of a multi-site evaluation platform that employs Advanced Distribution Management Systems (ADMS), distributed control devices, real-time hardware-in-loop assets, secure communication links, and protocol adapters. This platform uses standards-based approaches and open-source tools, and hence can serve as a template for other researchers and institutions to implement their multi-site evaluation frameworks for pre-deployment testing.

Essakiappan, Somasundaram↗

Real-Time Hardware-in-the-Loop Simulation of Ares I Launch Vehicle

The Ares Real-Time Environment for Modeling, Integration, and Simulation (ARTEMIS) has been developed for use by the Ares I launch vehicle System Integration Laboratory at the Marshall Space Flight Center. The primary purpose of the Ares System Integration Laboratory is to test the vehicle avionics hardware and software in a hardware - in-the-loop environment to certify that the integrated system is prepared for flight. ARTEMIS has been designed to be the real-time simulation backbone to stimulate all required Ares components for verification testing. ARTE_VIIS provides high -fidelity dynamics, actuator, and sensor models to simulate an accurate flight trajectory in order to ensure realistic test conditions. ARTEMIS has been designed to take advantage of the advances in underlying computational power now available to support hardware-in-the-loop testing to achieve real-time simulation with unprecedented model fidelity. A modular realtime design relying on a fully distributed computing architecture has been implemented.

Tobbe, Patrick↗

Propulsion Powertrain Real-Time Simulation Using Hardware-in-the-Loop (HIL) for Aircraft Electric Propulsion System

It is essential to design a propulsion powertrain real-time simulator using the hardware-in-the-loop (HIL) system that emulates an electrified aircraft propulsion (EAP) systems power grid. This simulator would enable us to facilitate in-depth understanding of the system principles, to validate system model analysis and performance prediction, and to demonstrate the proof-of-concept of the EAP electrical system. This paper describes how subscale electrical machines with their controllers can mimic the power components in an EAP powertrain. In particular, three powertrain emulations are presented to mimic 1) a gas turbo-=shaft engine driving a generator, consisting of two permanent magnet (PM) motors with brushless motor drives, coupled by a shaft, 2) a motor driving a propulsive fan, and 3) a turbo-shaft engine driven fan (turbofan engine) operation. As a first step towards the demonstration, experimental dynamic characterization of the two motor drive systems, coupled by a mechanical shaft, were performed. The previously developed analytical motor models1 were then replaced with the experimental motor models to perform the real-time demonstration in the predefined flight path profiles. This technique can convert the plain motor system into a unique EAP power grid emulator that enables rapid analysis and real-time simulation performance using hardware-in-the-loop (HIL).

turbo-electric propulsion↗

Oak Ridge National Laboratory Pilot Demonstration of an Attestation and Anomaly Detection Framework using Distributed Ledger Technology for Power Grid Infrastructure

This report summarizes the design and pilot demonstration of a framework called Grid Guard that was created to provide increased data and device trustworthiness to electric grid devices by leveraging distributed ledger technology (DLT), specifically blockchain. Grid Guard contains a combination of core cryptographic methods such as the secure hash algorithm (SHA), and asymmetric cryptography, private permissioned blockchain, baselining configuration data, consensus algorithm (Raft) and the Hyperledger Fabric (HLF) framework. The system implements a low energy, fast, and robust enhancement to system trustworthiness within and across electric grid systems such as substations, control centers and metering infrastructures. Blockchain is a distributed database structured that provides a practically unalterable (immutable) timeline of stored transactions. By relying on hashing and the Raft consensus algorithm, if an entity tries to illegitimately alter a record at one instance of the database the other ledger nodes are not altered. They work to cross-reference each other and easily locate any incorrectly added data and remove it. The bulk raw data is stored in an off-chain storage (outside of the blockchain ledger) and a hash of this baseline data is stored in the Blockchain ledger via hashing windows of time-series and configuration data, after aggregation and filtering. The bulk off-chain data repository is then considered to be trust-anchored using the hashes stored in the blockchain. To secure the electric grid testbed devices and data, device configuration baselines were compared to those baselines that had been previously stored in the ledger. Statistical baselines for device configurations, network communication patterns, and high-speed sensor data are calculated and then stored off-chain and hashes stored in the ledger. Measurements such as three-phase voltage and current, frequency, breaker status, protection scheme settings, network configuration settings (and other device configuration artifacts) and network traffic features (packet interarrival times) are compared every minute or other selected time windows. During phase 1 of the Grid Guard DLT project different DLT technologies were studies, and an assessment was performed on DLT technology vulnerabilities, uses, and key characteristics. DLT consensus protocols were studies (e.g., RAFT, named after Reliable, Replicated, Redundant, And Fault-Tolerant). Also, cryptography, public, private and permissioned or permissionless systems were assessed. Grid Guard implements a permissioned private DLT. Consensus algorithm selection and choice of DLT implementation depended heavily on the use-case. For this use-case, parameters were selected to measure performance and existing tools for assessment. Benchmarking was performed theoretically and practically. During phase 2 hashed transactions/blocks were inserted into the ledger every second. During phase 2 of the Grid Guard DLT project, a prototype framework was developed and demonstrated for attestation of critical substation devices and data using precision timing systems that use PTP and IRIG-B protocols) on a testbed of operational devices that emulated a distribution substation, control center, and power metering infrastructure using real Operational Technology (OT). The testbed includes OT devices such as protective relays, human machine interfaces (HMI), and power meters. To determine when to collect and compare system and network baselines, an initial examination of an anomaly detection capability to identify malicious manipulation of data streams was conducted. The resulting anomaly detection was demonstrated in a set of experiments and leveraged to trigger device artifact attestation checks. Attestation checks occur against device configuration baselines when compared with the immutable blockchain-stored baselines, which provided a cryptographically supported means by which to store baselines. The electrical substation-grid testbed was created to test the Grid Guard framework. The testbed emulates the operations of a portion of a power grid and SCADA systems as closely as possible. The testbed integrates real protocols, mainly IEC 61850 standard protocols, such as the Sampled Value (SV) and the GOOSE protocols. The testbed also supports DNP3 and other layer 2 and layer 3 protocols such as Telnet, SSH, SFTP/FTP and other proprietary protocols needed to connect to industrial control system equipment. The testbed emulates real power conditions using the OpalRT hardware-in-the-loop (HIL) device which can create fault situations that cannot be easily tested on real systems. The electrical substation-grid testbed was created using real measurement, communication, and protection devices that electrical utilities commonly use.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Data-Driven Scalable Emulation of Hydropower Using Real-Time Hardware-in-the-Loop

This presentation covers Motivation: (1) With the increased grid integration of inverter-based resources, hydropower plays a crucial role in maintaining the bulk power system reliability and resilience; and (2) A more dynamic response and new control designs are required to meet the grid requirements. To evaluate any modification, control-prototyping, performance validation and de-risking grid integration of hydropower, a high-fidelity environment is required. Also covers Objectives: (1) To develop data-driven emulation of hydropower using hardware-in-the-loop for different size, types of hydro plants; and (2) To characterize hardware and obtain accurate dynamic response for shaft speed, torque, and power. Provide a mechanical power interface with emulated dynamics of a hydro-turbine shaft that can be coupled to electrical generators for mechanical and electrical PHIL.

electrical↗

Assessment of the Electrical Substation-Grid Testbed with Inside/Outside Devices and Distributed Ledger Technology

The electrical substation-grid testbed was created to integrate the GOOSE and/or DNP (Distributed Network Protocol) messages with time synchronized sources and Distributed Ledger Technology (DLT). The objective was to study the impact of faults and cyber-events at an electrical substation with inside (protective relays) and outside (power meters) substation devices. The electrical substation-grid testbed was based on the design of a 34.5/ 12.47 kV electrical substation (sectionalized bus configuration) with two power transformers, connected to radial power lines and load feeders. The electrical substation-grid testbed was installed at 252 lab space (Advanced Power System Protection), Grid Research Integration and Deployment Center (GRID-C), Oak Ridge National Laboratory. This testbed was created for Task 5, DarkNet project. The electrical substation-grid testbed was created to simulate fault and/or cyber events that could potentially result in damage to the electrical infrastructure. In addition, tests were run that are usually not allowed to be performed in an operational electrical power grid, because these test scenarios could trip breakers and/or generate fault situations that could potentially damage equipment. The number of tests performed in the electrical substation-grid testbed were executed in a better way than in a real electrical substation and/or power grid, because multiple tests could be run in a short period of time, and complex permits, and safety/ schedule restrictions like in a real electrical substation environment were not needed. The electrical substation-grid testbed was created using real measurement, communication, and protection devices that are used by electrical utilities, to have same conditions that we could observe in a real power grid or electrical substation. The electrical substation-grid testbed was based on using a real time simulator and expansion box with amplifiers that were wired to electrical substation-grid devices. This hardware-in-the-loop (HIL) was provided by protective relays, power meters, ethernet switches, remote terminal units, synchronized timing network clock, DLT devices, workstations, and servers. This report includes the design, installation, and assessment of the electrical substation-grid testbed that was similar to an operational electrical substation, integrating the power system protection, communication, and control systems. The results for the electrical substation-grid testbed were based on:• verifying the analog signals for protective relays and power meters, • observing the synchronized time source frame at devices, • authenticating the GOOSE (IEC 61850) and DNP messages from power meters and protective relays, and • verifying the trip conditions of protective relays at fault tests with the power system fault event detection, using DLT devices. For future work, the electrical substation-grid testbed with protective relays and power meters, using DLT and synchronized time source from DarkNet, will be used to study the impact of cyber-events at inside and outside substation devices. Advanced algorithms for detecting cyber-events produced by non-desired protective relay settings will be studied, to improve the detection and reliability of protection, control, and communication systems at power grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗