FY-25 Progress on Computational Modeling of the Water Based NSTF
This report summarizes the system level modeling using RELAP5-3D of the Natural Convection Shutdown Heat Removal Test Facility (NSTF) completed in FY25. This year’s work focuses on a new tank configuration where the inlet of the tank was lowered in elevation by 45”. The stability boundaries of the NSTF are thoroughly studied and stability maps are constructed based on the stability and the oscillation patterns of the system. Five distinct operational modes are identified, namely single-phase liquid, uniform double peak oscillations, uniform sinusoidal oscillations, stable two-phase flow, and non-uniform oscillations. Next, the riser inlet throttling case of experimental test Run-104 is simulated with the RELAP5 model where good agreement is obtained between the model and the experimental data. The simulation also highlights the effects of backflow of water from the tank to the upper region of the chimney. Additionally, the decay heat removal test of Run-99 is simulated with the RELAP5 model. Comparison is carried out between this run and a similar run with the mid-tank inlet of Run-74 performed in FY22. With the lower tank inlet, the RELAP5 model is able to predict the experimental data more accurately than the previous mid tank inlet configuration. The discrepancy in model prediction accuracy highlights the non-symmetrical spatial effects in the tank that would otherwise be more easily captured with higher fidelity models. Lastly, two exploratory studies are conducted to investigate the behaviors of the NSTF when 1) heating is provided to the downcomer and 2) a bypass channel is added between the horizontal chimney section to the downcomer.