State-Constrained Grid-Forming Inverter Control for Robust Operation of AC Microgrids

The control of grid-forming inverters has become an important problem to achieve high efficiency, reliability, and resilience of the future power grid. The distributed control that utilizes a sparse communication network has been proposed for AC microgrids, in which each DG only has access to the information of a small number of its neighboring DGs, reducing the computational complexity and improving the resiliency to faults and unknown parameters. However, these approaches have not provided a clear analysis of the coupling between active/reactive power injections and the voltage magnitude/frequency or a distributed updating law with a solid theoretical foundation. Additionally, in the existing approaches, tracking the references from the secondary control may violate operational constraints.

Xu, Ying↗

Comparative Study of DC and AC Microgrids in Commercial Buildings Across Different Climates and Operating Profiles

Bosch has developed and demonstrated a novel direct current (DC) microgrid system that maximizes the efficiency of locally generated photovoltaic energy while offering high reliability, safety, redundancy, and reduced cost compared to equivalent alternating current (AC) systems. Several demonstration projects validating the system feasibility and expected efficiency gains have been completed and additional ones are in progress. This paper gives an overview of the Bosch DC microgrid system and presents key results from a large simulation study done to estimate the energy savings of the Bosch DC microgrid over conventional AC systems. The study examined the system performance in locations across the United States for several commercial building types and operating profiles. It found that the Bosch DC microgrid uses generated PV energy 6%-8% more efficiently than traditional AC systems.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Hamiltonian methods of modeling and control of AC microgrids with spinning machines and inverters

This study presents a novel approach to the modeling and control of AC microgrids that contain spinning machines, power electronic inverters and energy storage devices. The inverters in the system can adjust their frequencies and power angles very quickly, so the modeling focuses on establishing a common reference frequency and angle in the microgrid based on the spinning machines. From this dynamic model, nonlinear Hamiltonian surface shaping and power flow control method is applied and shown to stabilize. From this approach the energy flow in the system is used to show the energy storage device requirements and limitations for the system. This paper first describes the model for a single bus AC microgrid with a Hamiltonian control, then extends this model and control to a more general class of multiple bus AC microgrids. Finally, simulation results demonstrate the efficacy of the approach in stabilizing and optimization of the microgrid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Quantitative Trade-Off in Distributed Secondary Control for Autonomous AC Microgrids

In this paper, we propose to quantify the trade-off between voltage regulation and reactive power sharing in autonomous AC microgrids with distributed secondary control. It is known that voltage regulation and reactive power sharing in droop-controlled autonomous AC microgrids are two conflicting control objectives that present a natural trade-off between voltage regulation towards the voltage magnitude reference and reactive power sharing accuracy. This trade-off is commonly shown qualitatively without sufficient quantification. In this work, to quantify the trade-off between the two objectives, we focus on distributed secondary control and utilize regression and polynomial surface fitting to identify the requisite parameter area to satisfy the predefined error bands for voltage magnitude regulation and reactive power sharing. Extensive case studies are presented to validate the proposed method.

autonomous AC microgrids↗

Cyber-Resilient Automatic Generation Control for Systems of AC Microgrids

In this paper we propose a co-design of the secondary frequency regulation in systems of AC microgrids and its cyber security solutions. We term the secondary frequency regulator a Micro-Automatic Generation Control (μ AGC) for highlighting its same functionality as the AGC in bulk power systems. We identify sensory challenges and cyber threats facing the μ AGC. To address the sensory challenges, we introduce a new microgrid model by exploiting the rank-one deficiency property of microgrid dynamics. This model is used to pose an optimal μ AGC control problem that is easily implemented, because it does not require fast frequency measurements. An end-to-end cyber security solution to the False Data Injection (FDI) attack detection and mitigation is developed for the proposed μ AGC. The front-end barrier of applying off-the-shelf algorithms for cyber attack detection is removed by introducing a data-driven modeling approach. Finally, we propose an observer-based corrective control for an islanded microgrid and a collaborative mitigation scheme in systems of AC microgrids. We demonstrate a collaborative role of systems of microgrids during cyber attacks. Furthermore, the performance of the proposed cyber-resilient μ AGC is tested in a system of two networked microgrids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Droop-Free Distributed Control for AC Microgrids

In this chapter, droop-free distributed control for AC microgrids is discussed. The hierarchical structure of microgrid control is first introduced. Secondary level controls both with and without droop are discussed. Then two droop-free distributed controls are presented: one achieves average voltage regulation and perfect power sharing, and the other one achieves average voltage regulation, voltage variance regulation, and relaxed reactive power sharing. For the latter droop-free control, the relaxed reactive power sharing is achieved through a special distributed generator (DG) that will not participate in reactive power sharing.

Mohiuddin, Sheik Mohammad↗

Low-Frequency Stability Analysis of Inverter-Based Islanded Multiple-Bus AC Microgrids Based on Terminal Characteristics

For system planning of three-phase inverter-based islanded ac microgrids, the low frequency instability issue caused by interactions of inverter droop controllers is a major concern. When internal control information of procured commercial inverters is unknown, impedance-based small-signal stability criteria facilitate prediction of resonances in medium and high frequency ranges, but they usually assume the grid fundamental frequency as constant and thus they are incapable of analyzing the low-frequency oscillation of the fundamental frequency in islanded microgrids. Aiming at solving this issue, this paper proposes two stability analysis methods based on terminal characteristics of inverters and passive connection network including the dynamics of the fundamental frequency for analysis of low-frequency stability in islanded multiple-bus microgrids. Based on the Component Connection Method (CCM) to systematically separate inverters from the passive connection network, a general approach is developed to model the microgrid as a multiple-input-multiple-output (MIMO) negative feedback system in the common system d-q reference frame. By applying the generalized Nyquist stability criterion (GNC) to the return-ratio and return-difference matrices of the MIMO system model, the low-frequency stability related to the fundamental frequency can be analyzed using the measured terminal characteristics of inverters. Finally, analysis and simulation of a 37-bus microgrid verify the effectiveness of the proposed stability analysis methods.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Trust-Based Detection and Mitigation of Cyber Attacks in Distributed Cooperative Control of Islanded AC Microgrids

In this study, we address the challenge of detecting and mitigating cyber attacks in the distributed cooperative control of islanded AC microgrids, with a particular focus on detecting False Data Injection Attacks (FDIAs), a significant threat to the Smart Grid (SG). The SG integrates traditional power systems with communication networks, creating a complex system with numerous vulnerable links, making it a prime target for cyber attacks. These attacks can lead to the disclosure of private data, control network failures, and even blackouts. Unlike machine learning-based approaches that require extensive datasets and mathematical models dependent on accurate system modeling, our method is free from such dependencies. To enhance the microgrid’s resilience against these threats, we propose a resilient control algorithm by introducing a novel trustworthiness parameter into the traditional cooperative control algorithm. Our method evaluates the trustworthiness of distributed energy resources (DERs) based on their voltage measurements and exchanged information, using Kullback-Leibler (KL) divergence to dynamically adjust control actions. We validated our approach through simulations on both the IEEE-34 bus feeder system with eight DERs and a larger microgrid with twenty-two DERs. The results demonstrated a detection accuracy of around 100%, with millisecond range mitigation time, ensuring rapid system recovery. Additionally, our method improved system stability by up to almost 100% under attack scenarios, showcasing its effectiveness in promptly detecting attacks and maintaining system resilience. These findings highlight the potential of our approach to enhance the security and stability of microgrid systems in the face of cyber threats.

Computer Science↗

Virtual Agents-Based Attack-Resilient Distributed Control for Islanded AC Microgrid

Due to its dependence on a communication network, distributed secondary control of microgrids is susceptible to denial-of-service (DoS) attacks in channel shutdown mode, which may negatively impact the network connectivity and thus deteriorate the coordination and power sharing among distributed generators (DGs). Honeypot is a common method for cyber deception by introducing fake targets. However, in the context of microgrid, the misleading information spread by honeypots will also impact the system performance. This paper proposes an attack-resilient distributed control for AC microgrids utilizing virtual agents (VAs) to counteract both DoS edge and node attacks. The VAs are designed to not impact the system’s steady state during normal operation but to share information among neighboring real agents and serve as dummy targets for DoS attacks. The control with VAs is implemented by a primal-dual gradient based distributed algorithm to efficiently obtain a practical solution for voltage/frequency regulation and power sharing. The simulation results on a 4-DG test system and a modified IEEE 34-bus system show that 1) VAs do not impact the normal functionality of the test system, and 2) deploying VAs can enhance the resilience of the microgrid control against DoS edge and node attacks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Experiences and Lessons from Field Demonstration of Grid-forming Inverter in An AC Microgrid

The validation of GFM control strategies through simulation and hardware demonstration is important before their large-scale deployments in the real grid. Considering the importance of testing and validation, several works have explored the GFM inverter’s capability to blackstart a microgrid, synchronize and share loads, and interact with various types of generation sources and loads present in the grid. Herein, this paper complements the existing works by presenting the results and analysis of a field demonstration in an actual AC microgrid. The capability of a three-level neutral point clamped (NPC) GFM inverter equipped with a recursive feedback type of non-linear device level control to operate with PV source on its DC input and off-the-shelf PVGFL inverters and EV chargers of different kinds on the AC side is explored. The analysis and conclusions drawn would inform the readers to make better decisions during the field demonstration process.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluation of AC Microgrid Controllers

The evaluation of microgrid controllers is a critical component in de-risking the installation of microgrids in the field. This presentation discusses the evaluation of microgrid controllers in a lab setup.

AC microgrids↗

Distributed Secondary Control of Grid-Forming Inverters and AC Microgrids: Impacts of Voltage Feedback Choices

In this paper, the operational choices in distributed secondary control are examined, and their impacts on grid-forming (GFM) inverters and grid operation are investigated. In particular, the effects of feedback voltage choices, either average voltage feedback (AVF) or terminal voltage feedback (TVF), are studied with respect to reactive power sharing, voltage regulation, and grid-forming operation during black start. The secondary control used is a subgradient-based distributed cooperative control, and it provides the voltage, angle, and frequency references to the GFM inverters and their primary tracking controls. The overall control architecture employs multi-rate sampling such that the secondary control is slower than the primary control. The operational choices and their control performance are illustrated using a four-GFM-inverter microgrid in MATLAB/SIMULINK. Furthermore, the results show the effectiveness of the secondary controller, and several conclusions are drawn on the voltage feedback signals as the design choices.

24 POWER TRANSMISSION AND DISTRIBUTION↗