At least 19 records

Anomaly Identification of Synchronized Voltage Waveform for Situational Awareness of Low Inertia Systems

Inverter-based resources (IBRs) such as photovoltaics (PVs), wind turbines, and battery energy storage systems (BESSs) are widely deployed in low-carbon power systems. However, these resources typically do not provide the inertia needed for grid stability, resulting in a low-inertia power system. IBRs and lack of inertia have been known to cause anomalies such as waveform distortions and wideband oscillations in power systems due to the limited inertia level, leading to increased generation trips and load shedding. Here, to achieve effective anomaly identification, this paper proposes a synchro-waveform-based algorithm utilizing real-time synchronized voltage waveform measurements from waveform measurement units (WMUs). In the proposed method, different physical characteristics, as well as statistical features, are extracted from synchronized voltage waveform measurements to filter anomalies. Then, the anomaly identification approach based on the random forest is developed and deployed into the FNET/GridEye system considering trade-offs among accuracy, computational burden, and deployment cost. Moreover, four WMUs are specially designed and deployed on Kauai Island to receive instantaneous synchronized voltage waveform measurements. To verify the performance of the proposed algorithm, different experiments are carried out with collected field test data. The result demonstrates that the performance of the proposed synchro-waveform-based anomaly categorization algorithm can accurately identify anomalies 95.35% of the time, which has comparable performance among benchmarking algorithms.

Situational awareness↗

Revenue Analysis of Stationary and Transportable Battery Storage for Power Systems: A Market Participant Perspective

The power system faces a growing need for increased transmission capacity and reliability with the rising integration of renewable energy resources. To tackle this challenge, Battery Energy Storage Systems (BESSs) prove effective in enhancing grid capacity and relieving transmission congestion. This paper focuses on the PJM market, conducting a thorough revenue analysis to identify and characterize highly profitable nodes for BESS market participants. A comparison between stationary and transportable BESSs reveals that the transportable BESSs can generate higher potential revenue in energy and regulation markets. Based on these findings, we propose an optimal placement algorithm to support market participants in selecting strategic sites for BESS installation, validated with real PJM market data. This paper provides valuable insights for navigating market-based power system participants and promoting the effective integration of BESSs.

25 ENERGY STORAGE↗

Economic Analysis of Battery Energy Storage Systems Incorporating Uncertain Battery Model

A high-fidelity battery model is essential for precise economic analysis of battery energy storage systems (BESSs), but these models are computationally intensive. Heuristic models offer computational efficiency but compromise the accuracy of economic analysis results. We assess the impact of errors in heuristic battery models on economic analysis by utilizing open-circuit voltage (OCV) measurements from battery experiments.

Choi, Hyungjin [Sandia National Laboratories (SNL-↗

A control oriented comprehensive degradation model for battery energy storage system life prediction

In order to ensure that stationary battery energy storage systems (BESSs) provide reliable energy buffering, both for power quality and economic purposes, the degradation must be considered. Cell degradation involves various side reactions and is highly dependent on its operating conditions. To accurately track cell degradation and predict its impact on battery behavior, a comprehensive physics-based degradation model based on an electrolyte phase-enhanced single particle (SP) model is developed. Key degradation physics, namely solid electrolyte interphase (SEI) layer formation and growth, Li plating on the graphite anode, and Mn dissolution on cathode of nickel-cobalt-manganese oxide (NMC622) are considered. The model is validated against experimental capacity data. The results reveal that the deposition rate of both SEI layer and Li metal increase as the charge voltage increases. At the cathode side, the solvent oxidation rate determines the Mn dissolution rate. As a result, the volume fraction of NMC622 in the cathode continually decreases at a gradually increasing rate.

25 ENERGY STORAGE↗

Battery Energy Storage Systems: A Review of Energy Management Systems and Health Metrics

With increasing concerns about climate change, there is a transition from high-carbon-emitting fuels to green energy resources in various applications including household, commercial, transportation, and electric grid applications. Even though renewable energy resources are receiving traction for being carbon-neutral, their availability is intermittent. To address this issue to achieve extensive application, the integration of energy storage systems in conjunction with these resources is becoming a recommended practice. Additionally, in the transportation sector, the increased demand for EVs requires the development of energy storage systems that can deliver energy for rigorous driving cycles, with lithium-ion-based batteries emerging as the superior choice for energy storage due to their high power and energy densities, length of their life cycle, low self-discharge rates, and reasonable cost. As a result, battery energy storage systems (BESSs) are becoming a primary energy storage system. The high-performance demand on these BESS can have severe negative effects on their internal operations such as heating and catching on fire when operating in overcharge or undercharge states. Reduced efficiency and poor charge storage result in the battery operating at higher temperatures. To mitigate early battery degradation, battery management systems (BMSs) have been devised to enhance battery life and ensure normal operation under safe operating conditions. Some BMSs are capable of determining precise state estimations to ensure safe battery operation and reduce hazards. Precise estimation of battery health is computed by evaluating several metrics and is a central factor in effective battery management systems. In this scenario, the accurate estimation of the health indicators (HIs) of the battery becomes even more important within the framework of a BMS. This paper provides a comprehensive review and discussion of battery management systems and different health indicators for BESSs, with suitable classification based on key characteristics.

Nazaralizadeh, Solmaz (ORCID:0009000737004039)↗

Optimal Sizing and Operation of a Hybrid Clean Energy Center

In this paper, we consider the deployment of battery energy storage systems (BESSs) paired with photovoltaics (PV) to form a hybrid clean energy center (HCEC), where the BESS is equipped for two main purposes: i) reducing the volatility of PV output and ii) shifting energy to meet an export limit. We develop a linear dynamical model to characterize the output of an HCEC and express the volatility and export power as functions of the battery's dispatch operations. We also propose an optimal sizing method via second-order cone programming (SOCP) to maximize the net benefits of the HCEC. Numerical studies are performed to illustrate and validate the proposed method.

Battery energy storage systems, photovoltaics, sec↗

Detection of False Data Injection Attacks in Battery Stacks Using Input Noise-Aware Nonlinear State Estimation and Cumulative Sum Algorithms

Grid-scale battery energy storage systems (BESSs) are vulnerable to false data injection attacks (FDIAs), which could be used to disrupt state of charge (SoC) estimation. Inaccurate SoC estimation has negative impacts on system availability, reliability, safety, and the cost of operation. In this article a combination of a Cumulative Sum (CUSUM) algorithm and an improved input noise-aware extended Kalman filter (INAEKF) is proposed for the detection and identification of FDIAs in the voltage and current sensors of a battery stack. The series-connected stack is represented by equivalent circuit models, the SoC is modeled with a charge reservoir model and the states are estimated using the INAEKF. Further, the root mean squared error of the states’ estimation by the modified INAEKF was found to be superior to the traditional EKF. By employing the INAEKF, this article addresses the research gap that many state estimators make asymmetrical assumptions about the noise corrupting the system. Additionally, the INAEKF estimates the input allowing for the identification of FDIA, which many alternative methods are unable to achieve. The proposed algorithm was able to detect attacks in the voltage and current sensors in 99.16% of test cases, with no false positives. Utilizing the INAEKF compared to the standard EKF allowed for the identification of FDIA in the input of the system in 98.43% of test cases.

25 ENERGY STORAGE↗

A Comprehensive Method to Mitigate Forced Oscillations in Large Interconnected Power Grids

Multiple severe forced oscillation events have recently been observed across the North American interconnections and around the world. These forced oscillations have caused power swings, limited power transfer capability, damaged equipment, and persisted indefinitely until the driving source was located and removed. This paper proposes a comprehensive method to mitigate forced oscillations. Once a forced oscillation is detected, a new source location algorithm can be used to locate the source based on the oscillation mode angle without requiring system topology information. If the source cannot be quickly located and removed, a control strategy can be activated to modulate the active power of utility-scale inverterbased battery energy storage systems (BESSs) to reduce the energy of forced oscillations to a safe level and allow sufficient time for locating the exact source. The proposed source location algorithm is validated using measurements collected during the January 11, 2019 forced oscillation event in North America and other actual grid events, while the proposed control strategy is verified using the Eastern Interconnection dynamic model under the replicated January 11, 2019 forced oscillation event. The simulation results demonstrated that the proposed source location algorithm can accurately identify the forced oscillation source, and the proposed control strategy can significantly reduce forced oscillation energy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Predictive-Maintenance Practices: For Operational Safety of Battery Energy Storage Systems

Changes in the Demand Profile and a growing role for renewable and distributed generation are leading to rapid evolution in the electric grid. These changes are beginning to considerably strain the transmission and distribution infrastructure. Utilities are increasingly recognizing that the integration of energy storage in the grid infrastructure will help manage intermittency and improve grid reliability. This recognition, coupled with the proliferation of state-level renewable portfolio standards and rapidly declining lithium-ion (Li-ion) battery costs, has led to a surge in the deployment of battery energy storage systems (BESSs). Additionally, although BESSs represented less than 1% of grid-scale energy storage in the United States in 2019, they are the preferred technology to meet growing demand because they are modular, scalable, and easy to deploy across diverse use cases and geographic locations.

25 ENERGY STORAGE↗

A scalable planning framework of energy storage systems under frequency dynamics constraints

As the penetration of renewables increases in power systems, the declining system inertia can cause frequency stability issues. Battery energy storage systems (BESSs) respond fast and therefore can relieve the low inertia difficulty but need to be appropriately sized considering the associated cost. This paper presents a novel stochastic optimization model for economically planning BESS capacity while considering the spatial–temporal correlation of wind generation and generator outages under frequency stability constraints, which include the rate-of-change of frequency (RoCoF), frequency nadir (FN), and quasi-steady-state (QSS) frequency. A set of new FN constraints that can be easily linearized is developed. To account for renewable uncertainties, a realistic uncertainty modeling approach, Random Field, is adopted to generate wind generation scenarios by considering both spatial and temporal evolutions of wind speed profiles. The ESS sizing is formulated as a mixed-integer linear programming problem and solved by using a scalable decomposition-and-coordination approach, Surrogate Absolute Value Lagrangian Relaxation (SAVLR). To further improve the scalability and reduce computational burdens, a rolling-horizon-based update is developed and incorporated into SAVLR for providing a practical solution to the long-term planning of very large-scale power systems. Finally, a modified IEEE 118-bus system and the Polish system are used to validate the effectiveness and scalability of the model and solution methodology.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Incorporating Operational Uncertainties into the Dispatch of an Integrated Solar and Storage System

The economic assessment of hybrid energy systems (HES) pairing battery energy storage systems (BESSs) and photovoltaics (PV) is highly important for advancing their deployment in power systems. This paper presents an innovative assessment framework, including an optimal control policy for dispatch under uncertainty and procedures for exploring control parameters that maximize economic benefits. The proposed dispatch policy consists of two steps using system forecast information. The first step is to determine whether a BESS will be used within an operational scheduling time frame based on the probability of events and their thresholds. Once the dispatch of BESS is triggered, a model predictive control (MPC) is carried out in the second step for scheduling using the expected value of system information. By exercising this policy with different thresholds, one can explore the trade-offs between short-term benefits and battery lifetime, and identify an optimal threshold that maximizes the total economic benefits within the battery lifetime. An evaluation study in a real-world HES project is presented to illustrate the proposed framework. Compared with traditional optimal dispatch algorithms, the proposed method can significantly improve the economic benefits of an HES scheduled under forecast uncertainties.

Ma, Xu↗

An economic assessment of behind-the-meter photovoltaics paired with batteries on the Hawaiian Islands.

Due to natural variability and uncertainty, the ever-increasing penetration of solar generation in Hawaii presents challenges to power grid operators to maintain reliable system operation. Demand response (DR) has the potential to be a cost-effective tool for Hawaii to reach its aggressive renewable energy goals while maintaining the reliability of power grids. The Hawaii Public Utilities Commission has approved the Hawaiian Electric Company's revised portfolio of DR programs. The companies have released a grid services purchase agreement and subscribed an initial tranche of load into their DR programs. This paper presents innovative analytical methods and comprehensive economic assessment for distributed photovoltaics (PV) paired with battery energy storage systems (BESSs) for two new DR programs, including fast frequency response and capacity grid service. Optimal dispatch and sizing methods are proposed for the paired system considering different tariff schedules and PV compensation programs across five islands. It was found that while the best resource configuration and potential economic benefits vary with tariff structure, a BESS paired with PV can be optimally dispatched to generate multiple value streams simultaneously. Compensation from DR programs is an important value stream to help increase the cost-effectiveness of the integrated system.

Battery energy storage system↗

Modeling distributed energy resource aggregations in security constrained unit commitment and economic dispatch

The Federal Energy Regulatory Commission (FERC) recently issued Order 2222, which requires all wholesale electricity markets in the US to allow distributed energy resources (DERs) to participate in the market as aggregated resources. These DER aggregations may be composed of many individual resources that are offered and dispatched by the market as a single entity. We present here a model of a distributed energy resource aggregator (DERA) that is scheduled by a market operator’s security constrained unit commitment (SCUC) and security constrained economic dispatch (SCED). The DERA model includes constraints for battery energy storage systems (BESSs), demand response resources (DRRs), and a simple distributed energy resource (DER). This paper describes a model for each resource type and presents two methods for the DERA to generate market offer curves: a profit-maximizing optimization to compute cost curves and a direct cost algorithm to determine dispatch costs for each resource and combine into cost curves. Once all participating DERAs are scheduled in SCUC/SCED, the model is then modified to dispatch individual DERs to maximize profit or minimize schedule deviation of the DERAs. A simulation of a representative day illustrates the DERA offers, the scheduled generation, and the DERA dispatch. Findings show the potential for unavoidable schedule deviations due to internal DER constraints and due to economic incentives to deviate from the SCUC/SCED schedules. This highlights the importance of DERA offer construction on market efficiency and system reliability. Novel aspects of our approach include: (1) We consider the asymmetry of price incentives impacting DERAs from the wholesale market compared to those impacting consumers from the retail market, as imposed by current regulations and laws. (2) We model aggregate consumer response through statistically parameterizable utility functions rather than a potentially impractical approach of modeling each individual consumer. (3) We show how to use the DERA operational dispatch model to create offers into the wholesale electricity market. (4) We show how DERAs may fail to meet their scheduled dispatch because the market offer format may not permit them to fully express their operational features such as intertemporal costs and constraints to the market.

aggregations↗

Regional Power System Black Start with Run-of-river Hydropower Plant and Battery Energy Storage

Battery energy storage systems (BESSs) are an important asset for power systems with high integration levels of renewable energy, and they can be controlled to provide various critical services to the power grid. This paper presents the real-world experience of using a megawatt-scale BESS with grid-following (GFL) and grid-forming (GFM) controls and a run-of-river (ROR) hydropower plant to restore a regional power system. To demonstrate this, we carry out power-hardware-in-the-loop experiments integrating an actual GFL- or GFM-controlled BESS and a load bank. Both the simulation and experimental results presented in this paper show the different roles of GFL- or GFM-controlled BESS in power system black starts. The results provide further insight for system operators on how GFL- or GFM-controlled BESS can enhance grid stability and how an ROR hydropower plant can be converted into a black-start-capable unit with the support of a small-capacity BESS. The results show that an ROR hydropower plant combined with a BESS has the potential of becoming one of enabling elements to perform bottom-up black-start schemes as opposed to conventional bottom-down method, thus enhancing the system resiliency and robustness.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modeling and Optimization Methods for Controlling and Sizing Grid-connected Energy Storage: A Review

Purpose of Review Energy storage is capable of providing a variety of services and solving a multitude of issues in today's rapidly evolving electric power grid. This paper reviews recent research on modeling and optimization methods for optimally controlling and sizing grid-connected battery energy storage systems (BESSs). Open issues and promising research directions are discussed. Recent Findings Recent studies on BESS dispatch, evaluation, and sizing focus on advanced modeling and optimization methods to maximize stacked value streams from multiple services. BESS models have been improved to better represent operational characteristics or capture degradation effects. Different solution methods and optimization techniques have been proposed to improve the benefits and cost-effectiveness of BESSs, using deterministic approaches prevalently but with impressive progress in capturing and addressing uncertainties. Summary Recent progress in BESS scheduling and sizing better supports planning and operational decision-making in different use cases, which is highly important to advance the deployment of BESSs. Additional research is required to properly model the trade-off between short-term benefits and service life with multiple degradation effects explicitly considered in the decision-making process. Advanced methods are to be developed for effectively determining optimal BESS sizes that maximize overall benefits within a varying lifetime considering diversified system, conditions as well as uncertainties at planning and operational stages.

Wu, Di↗

On the role of Battery Energy Storage Systems in the day-ahead Contingency-Constrained Unit Commitment problem under renewable penetration

The integration of variable Renewable Energy Sources (vRES) to alleviate greenhouse gas emissions has introduced significant challenges for power systems operations. These challenges include high levels of uncertainty due to the intermittence associated with vRES and therefore impose the need to devise a reliable and cost-effective day-ahead unit commitment and power and reserves scheduling for real-time operations. Also, this increasing penetration of vRES requires higher ramping capabilities from units originally designed for other purposes (e.g., base-load generation), which might be exacerbated during contingency states. Hence, in this work, we propose a methodology to address the day-ahead Contingency-Constrained Unit Commitment (CCUC) problem that leverages the participation of Battery Energy Storage Systems (BESSs) to address load-following and post-contingency management, therefore alleviating the ramping burden on conventional thermal generators. To do so, we formulate a three-level optimization problem that represents the decision-making process of obtaining the least-cost commitment, generation and reserves scheduling, while restricting the Conditional Value-at-Risk (CVaR) of the system imbalance at real-time operations to user-defined tolerance levels. In addition, we devise a computationally efficient solution approach for the proposed problem based on the Column-and Constraint Generation (CCG) algorithmic framework. Two numerical experiments are conducted to empirically illustrate the benefits of the proposed methodology. Key results indicate a reduction in real-time ramping needs and a better usage of the system resources, with a reduction in the overall system commitment levels and reserve scheduling costs when compared to a benchmark case in which storage is not available.

Moreira, Alexandre↗

A Frequency Control Method for Islanded Microgrids Using Energy Storage Systems

Islanded microgrids are vulnerable to frequency fluctuations due to the presence of low-inertia distributed energy resources (DERs). Moreover, implementation of both synchronous-based and inverter-based DERs with a significant difference in inertia leads to a power imbalance between generation and consumption during transients. This results in frequency variations which might have severe consequences such as blackouts. This paper develops a control scheme for battery energy storage systems (BESSs) to enhance the dynamic response of islanded microgrids by mitigating the frequency fluctuations. A piecewise linear-elliptic (PLE) droop characteristic is proposed and employed in BESS to achieve a faster power balance between generation and consumption during transients, resulting in enhanced frequency responses. Different case studies are carried out to validate the viability of the proposed approach in improving the dynamics of islanded microgrids.

Pilehvar, Mohsen S.↗

Energy-Storage Fed Smart Inverters for Mitigation of Voltage Fluctuations in Islanded Microgrids

The continuous integration of intermittent low-carbon energy resources makes islanded microgrids vulnerable to voltage fluctuations. Besides, different dynamic response of synchronous-based and inverter-based distributed generation (DG) units can result in an instantaneous power imbalance between supply and demand during transients. As a result, the ac-bus voltage of microgrid starts oscillating which might have severe consequences such as blackouts. This paper modifies the conventional control scheme of battery energy storage systems (BESSs) to participate in improving the dynamic behavior of islanded microgrids by mitigating the voltage fluctuations. A piecewise linear-elliptic (PLE) droop is proposed and employed in BESS to achieve an enhanced voltage profile by injecting/absorbing reactive power during transients. In this way, the conventional inverter implemented in BESS turns into a smart inverter to cope with fast transients. Using the proposed approach in this paper, any linear droop curve with a specified coefficient can be replaced by a PLE droop curve. Compared with linear droop, an enhanced dynamic response is achieved by utilizing the proposed PLE droop. Case study results are presented using PSCAD/EMTDC to demonstrate the superiority of the proposed approach in improving the dynamic behavior of islanded microgrids.

Pilehvar, Mohsen S.↗