Capillary-Enhanced Two-Phase Micro-Cooler Using Copper-Inverse-Opal Wick with Silicon Microchannel Manifold for High-Heat-Flux Cooling Application

In this work, we demonstrate a two-phase capillary-fed boiling micro-cooler that consists of a ~ 25-..mu..m-thick copper inverse opal (CIO) porous wicking structure for high-heat-flux boiling and a silicon 3D-manifold for distributed liquid delivery and vapor extraction across a 0.5 cm x 0.5 cm heated area. At low inlet water mass flow rates of 1.5 to 1.9 g(min)-1, the micro-cooler displays nearly two-phase boiling with exit vapor quality ~ 1 and a high critical heat flux (CHF) of 253 to 320 W cm-2 with low superheat of ~ 10 degrees C resulting in a thermal resistance of boiling ~ 0.025 cm2 degrees C W-1 or heat transfer coefficient of 0.4 MW m-2 degrees C-1. For higher flow rates of 5, 10, and 15 g(min)-1, the micro-cooler exhibits a hybrid single-phase and two-phase cooling regime where the contribution of the sensible heat (single-phase) cooling is linearly added to that of the two-phase cooling. For the highest flow rate of 15 g(min)-1, the CHF is increased to ~ 500 W cm-2 resulting in an overall thermal resistance of ~ 0.18 cm2 degrees C W-1. However, the two-phase heat transfer effectiveness, which estimates the utilization level of the inlet mass flow rate for two-phase boiling, is reduced to ~ 0.11. To achieve the best cooling system performances, the micro-cooler must operate entirely within the two-phase boiling regime (exit vapor quality or two-phase heat transfer effectiveness ~ 1). Ideally, the "coolant" should be delivered near its saturation temperature (~ 100 degrees C for water), which provides significant advantages for the energy-efficient operation of data centers and power electronics. We present detailed analysis with Infrared and high speed camera images at various inlet flow rates and heat fluxes to understand complex heat transfer in the micro-cooler. Furthermore, a conjugate thermofluidic simulation model, which incorporates the physics of capillary-fed boiling in a porous copper layer, agrees well with the experimental data.

capillary-enhanced boiling↗

Integrated Molten Salt Reactor Modeling Capabilities in NEAMS Thermal Hydraulics Tools

The DOE neams program supports a full range of computational thermal fluids analysis capabilities and code developments for a broad range of advanced reactor concepts. The research and development approach under the thermal fluids technical area synergistically combines three length and time scales in a hierarchical multi-scale approach. To enable multi-scale thermal fluids capability using these codes, a key joint effort has been underway to develop an integrated system- and engineering-scale thermal fluids analysis capability, through integration of SAM and Pronghorn codes, both based on the MOOSE framework. This report summarizes recent advances in developing an integrated system- and engineering-scale modeling capability for the msr concept, which has gained significant interest in recent years. A consistent framework was established by coupling Pronghorn and SAM through the Saline interface, with thermophysical properties provided by the Molten Salt Thermal Property Database (MSTDB-TP). Further improvements were made to the coupling schemes and domain-overlapping strategies, enhancing the stability and robustness of multi-code simulations. Verification and validation efforts demonstrate the accuracy of this integration across a range of benchmark problems, including one-dimensional heated pipe flows, three-dimensional natural convection loops with evolving isotopic compositions, and \gls{msre} demonstration cases. Within Pronghorn, new capabilities were introduced to model corrosion and noble-metal plating phenomena, supported by an extended thermal-hydraulics framework and refined turbulence treatments. To capture two-phase flow behavior, a multiphase Euler–Euler model was implemented in Pronghorn, including advanced closure relations, high-resolution advection techniques, and capillary force reconstruction. Preliminary verification cases confirm the fidelity of the approach, while planned validation efforts target canonical multiphase benchmarks and application to msr components such as the msre pump bowl. Finally, updates to SAM’s msr mass transfer modeling were extended to consider noble gas migration into porous structures like graphite. The point kinetics model was updated to include reactivity feedback contributions from any defined species, such as xenon. The gas transport model was expanded for applicability to gas mixtures, bubble efflux phenomena, and species transport between liquid and gas phases. A selection of multi-scale Sherwood number correlations from MOSCATO/NekRS and multi-phase correlations from literature have been added for improved accuracy in calculating mass transfer coefficients. A companion effort on developing system-level redox corrosion has also been incorporated into SAM. Collectively, these enhancements strengthen the predictive capability of SAM and Pronghorn for simulating MSR thermal-hydraulics, corrosion, multiphase behavior, and fission-product transport, providing a more complete toolset for design, safety analysis, and licensing support of next-generation \gls{msr}s.

42 - ENGINEERING↗

Porous mesh manifold for enhanced boiling performance

High-performance electronics are continuously demanding cooling of higher heat fluxes. Phase-change cooling, including pool boiling, is a useful approach to address this challenge; however, competition between liquid and vapor flows generally limit the heat fluxes that can be dissipated. A range of strategies to control these flows have been investigated previously, including capillary guides. Here a manifold structure formed from a metallic mesh is investigated to control the disposition of liquid and vapor phases above a pool fed boiling surface enhanced with porous structures. Copper mesh forms defined liquid flow paths, using capillary action to guide and distribute liquid evenly over the heated surface, along with open channels to facilitate vapor escape. The mesh provides a novel structure for liquid guidance that imposes low resistance to liquid flow while occluding a minimal area of heated surface underneath. The manifold performance is characterized in boiling fed by a pool of water above a laser-textured aluminum nitride heat dissipation surface with pin–fin structures having heights of 110 µm and spacing of 30 µm with a heated area of 5 mm x 5 mm. A maximum heat flux of 490 W/cm 2 is reached with the manifold in the pool fed configuration, representing an increase of more than 65% over the porous pin fin surface alone. The maximum stable superheat observed for the manifold of 36K is 14K higher than that for the porous surface without the manifold. The factors limiting performance of the manifold are analyzed. High superheat is attributed to partial flooding of the boiling surface as suggested by the reduction in superheat using external suction. Similar systems and structures for enhanced two-phase cooling are compared.

37 INORGANIC, ORGANIC, PHYSICAL, AND ANALYTICAL CH↗

Non-dimensional performance and safety parameters for heat pipes

The use of heat pipes in safety-critical systems such as nuclear microreactors dictates the development of generalized, practical, scalable performance and safety parameters. Traditional dimensional metrics, while informative, lack the universality required for comparative analysis across varying designs and operating regimes. Here, this work introduces a comprehensive set of non-dimensional parameters to characterize heat pipe performance and safety, including capillary performance, effective thermal conductivity, response time, exergetic efficiency, allowable temperature gradients, allowable rate of temperature change, priming coefficients, and factor of safety. A reference heat pipe design representative of microreactor applications was analyzed via the developed parameters using both traditional analytical models and Sockeye simulations under transient and steady-state conditions. Sodium, potassium, and water were evaluated as working fluids to demonstrate the applicability of the framework across a broad temperature range. The proposed non-dimensional parameters effectively captured key thermal-hydraulic behaviors and safety concerns, as was demonstrated via Sockeye simulations. This framework supports the development of design optimization strategies, operational protocols, and safety assurance practices for advanced reactor systems and other high-reliability applications.

42 - ENGINEERING↗