Approaches for Autonomous Peer to Peer Communication: For Resilient Community Microgrids

The final phase of the Islandable Communications task of the SECURE project consisted of integrating the islandable communications network into a microgrid simulation at NREL. Initially integration was planned for a microgrid implemented as a mix of simulation and physical hardware. As the project evolved, the microgrid became fully simulated. The simulation environment was structured to break out the communication paths that would pass over a communication network in a field demonstration. The Islandable Communication network was integrated into the simulation environment, allowing both a commercial cellular carrier and a Private LTE network to be evaluated. The microgrid simulation showed differences in performance and behavior when operating over the wireless networks (compared to operating over wired Ethernet in the lab). These differences point to further research opportunities to better understand how microgrid communication carried over real-world or impaired networks affects the microgrid system behavior.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Robust Communication-Free Protection Scheme for Islanded Microgrids with Relay Logic and Hardware-in-the-Loop Validation

This paper presents the Imbalance Square Factor (ISF) detection algorithm, an effective, computationally lightweight method for detecting faults in inverter-based microgrids. ISF provides a high magnitude at the time of the fault, which allows for fast detection and coordination between primary and backup relays. The imbalance squared factor, calculated using local voltage and currents, is used for fault detection and coordination among three relays. ISF is validated in hardware-in-the-loop (HIL) implementation inside commercial-grade relay logic (SEL-751). The HIL validation shows that ISF can coordinate primary, secondary, and tertiary relays in the 13-bus system in islanded operation.

Ferrari Maglia, Max [ORNL]↗

Solar Energy CommUnity Resiliency (Final Technical Report)

Final Technical Report for DE-EE0009336 Solar Energy CommUnity Resiliency (SECURE) The Solar Energy CommUnity Resiliency (SECURE) project aimed to support development of resilient community microgrids to improve grid reliability and maintain power during times of crisis. The SECURE project approached this objective by addressing key technical and business challenges impeding implementation of resilient community microgrids. To achieve the goals of this project, we pursued several specific objectives through comprehensive design and requirements development.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Multi-Segment Decentralized Control Strategies for Renewables-Rich Microgrids in Extreme Conditions

Microgrids provide a promising approach to accommodating various distributed energy resources (DERs), while requiring significant communication infrastructures that may be affected by extreme conditions such as natural disasters and cyber-attacks. In this paper, a fully decentralized control strategy without the need for communication is proposed for islanded microgrids with high renewables penetration. First, special multi-segment power/frequency characteristic curves are designed, so that different DERs can be automatically coordinated in a prioritized manner such as renewables first to maintain power balance while DER frequencies are regulated at their reference values. Second, piecewise linear served load versus frequency models are designed to prioritize loads according to their significance, so that only noncritical loads will be curtailed as needed while critical loads are supplied without any interruptions during power deficiency. The proposed strategy can effectively deal with various normal and extreme system conditions including 100% renewables penetration, loads and renewables variations, power deficiencies requiring load curtailments, disconnection of existing DERs, connection of new DERs as well as network sectionalization and reconfiguration. As a result, the proposed control strategy is validated in the real-time digital simulator (RTDS) model of the IIT Campus Microgrid to demonstrate its effectiveness in enhancing the resiliency of renewables-rich microgrids in extreme conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Model-based Cyber-attack Detection for Voltage Source Converters in Island Microgrids

With the upgrading of communication and control in microgrids, cyber threats on the power converters are increasing. Here, in this paper, a novel model-based cyber-attack detection methodology is proposed for each voltage source converter in microgrids. The Harmonics State Space Matrix (H-Matrix) is used to build the closed-loop transfer function, providing model-based estimation with the grid voltage and control reference. Then, the space phase model (SPM) is used to calculate residual to detect cyber-attacks in voltage source converter (VSC). As controller and converter parameters are included in the H-matrix, the proposed method also could detect cyber-attacks when voltage fluctuation occurs in the grid. To verify the feasibility of the proposed method, several attacks targeting VSC in an islanded microgrid are simulated in MATLAB. Simulation and detection results are introduced to demonstrate the resilience and feasibility of the proposed method.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Bi-Level Adaptive Storage Expansion Strategy for Microgrids Using Deep Reinforcement Learning

Battery energy storage (BES) is a versatile resource for the secure and economic operation of microgrids (MGs). Prevailing stochastic optimization-based approaches for BES expansion planning for MGs are computationally complicated. This work proposes a data-driven bi-level multi-period BES expansion planning framework to determine the siting, sizing, and timing of BES installations. The proposed planning framework unifies deep reinforcement learning (DRL) and linear programming, thereby decoupling the determinations for the integer and continuous decision variables in two time scales, respectively. In the upper level, a rainbow DRL agent with quantile regression is trained to provide dynamic planning policies to accommodate stochastic renewable energy resources (RESs), load, and battery price changes efficiently. Further, the lower level computes the optimal operation of MGs with frequency constraints to hedge the islanding contingency. The two levels communicate with one another by exchanging storage configuration and operating expenses in order to accomplish the shared goal of minimizing investment and operation costs. Comparative case studies on an MG are carried out to demonstrate the superiority of the proposed DRL-based solution to the mixed-integer linear programming counterpart on efficiency, scalability, and adaptability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Study of microgrid resilience through co-simulation of power system dynamics and communication systems

The interdependence of power and communication systems in smart grid technologies is acknowledged, but difficult to quantify. Communication systems can be essential to maintaining stability in microgrids that are islanded due to extreme events. Though many power system studies assume the presence of communication networks, detailed modeling of power and communication systems for dynamic studies of microgrids is rare. The work presented in this paper develops a framework for power and communication system co-simulation to study the impact of communications system on microgrid stability. An operational use case is examined where a battery energy storage system operates to offset the loss of generation in an islanded microgrid. The framework is evaluated for different communication technologies, network structures, and communication media.

Thekkumparambath Mana, Priya↗

Unleashing the Frequency: Multi-Megawatt Demonstration of 100% Renewable Power Systems with Decentralized Communication-Less Control Scheme

Power systems, which range in size from small microgrids to island systems to large regional grids, are typically managed by a central controller that requires complex communication methods and can be unreliable and pose cyber security risks in certain applications, especially when controlling a larger number of nodes. We propose an inherently robust, scalable method of integration using multiple energy storage systems and distributed energy resources, which does not require any means of dedicated communication. This method moves beyond the paradigm of controlling grid frequency at a fixed value (e.g., 60 Hz), instead allowing the frequency to fluctuate within certain limits (e.g., 59.6-60.4 Hz). With a greater operating range, the frequency can carry necessary information from energy storage systems to highly variable distributed energy resources like photovoltaics, wind, hydro, etc.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Virtual Agents-Based Attack-Resilient Distributed Control for Islanded AC Microgrid

Due to its dependence on a communication network, distributed secondary control of microgrids is susceptible to denial-of-service (DoS) attacks in channel shutdown mode, which may negatively impact the network connectivity and thus deteriorate the coordination and power sharing among distributed generators (DGs). Honeypot is a common method for cyber deception by introducing fake targets. However, in the context of microgrid, the misleading information spread by honeypots will also impact the system performance. This paper proposes an attack-resilient distributed control for AC microgrids utilizing virtual agents (VAs) to counteract both DoS edge and node attacks. The VAs are designed to not impact the system’s steady state during normal operation but to share information among neighboring real agents and serve as dummy targets for DoS attacks. The control with VAs is implemented by a primal-dual gradient based distributed algorithm to efficiently obtain a practical solution for voltage/frequency regulation and power sharing. The simulation results on a 4-DG test system and a modified IEEE 34-bus system show that 1) VAs do not impact the normal functionality of the test system, and 2) deploying VAs can enhance the resilience of the microgrid control against DoS edge and node attacks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Control Oriented Models for Co-Design: Technical Overview of MT HVDC, MVDC, and Solid State Transformer Building Blocks

The electric power system is shifting toward a power electronics–enabled grid, where converter based “building blocks” (e.g., high voltage direct current (HVDC) links, multi terminal HVDC (MT HVDC) networks, medium voltage DC (MVDC) links, and solid state transformers (SSTs)) provide fast, precise control of power flows, voltage, and frequency. This report develops and applies publicly shareable electromagnetic transient (EMT) and phasor models to examine how such building blocks can be composed and coordinated to support offshore wind integration, inter area transfers, feeder support, and resilience. Section 2 documents a modular multilevel converter (MMC)–based MT HVDC modeling framework and two use cases: a compact WSCC/IEEE 9 bus test system and a 240 bus “mini WECC” case with five offshore wind plants (OWFs). Phasor to EMT transfer, initialization, and sanity checks are summarized, and neutral demonstrations of normal and contingency operation are reported. Section 3 frames the problem of wind plant inertial frequency response (IFR): shaping energy release and recovery to improve nadir while avoiding aerodynamic stall; representative simulations illustrate the issues without disclosing proprietary control. Section 4 develops MVDC concepts through an IEEE 16 bus loop and an Olympic Peninsula case study that compares AC vs. MVDC corridors and shows how feeder headroom can be pooled via DC couplers. Section 5 surveys SST architectures and identifies a gap: scalable, communication free coordination of multiple SSTs for islanded feeder networks. Across the report, novel methods and configurations under separate publication and IP review are not disclosed; only topic oriented, replicable setups and non proprietary results are shown. These models and use cases are intended as foundations for future publications and co design studies on architecture, control, and coordination of PE enabled grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Critical values of cyber parameters in a dynamic microgrid system

An islanded microgrid can be used to serve critcal load as a resiliency source when a severe outage occurs. In an islanded mode, control of a microgrid relies on the communication system significantly. Hence, microgrids are cyberphysical systems and, therefore, the cyber system plays a crucial role in the performance of the cyber-power system. A microgrid control scheme is proposed for power dispatch and regulation based on the droop and proportional-integral (PI) feedback control. The proposed control strategy is validated for transient stability following dynamic events. To evaluate the impact of a networked control system on control performance, a cyber model is developed to represent data acquisition periods and communication delays. An analytical method is proposed to determine the critical values for the data reporting periods and communication delays. The analytical method based on a state space model of a networked control system is applicable for large-scale systems. A 2-dimensional stability region of a microgrid in the space of cyber parameters can be obtained by the proposed method, and the critical values of cyber parameters are determined based on the stability region. Simulation results validate that the design of a microgrid as a cyber-physical system needs to be guided by critical values for the data reporting period and communication delay to prevent system instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Defensive Islanding to Enhance the Resilience of Distribution Systems Against Cyber-Induced Failures

The extensive integration of communication, computation, and control technologies into cyber-physical power systems (CPPSs) has increased the vulnerabilities of CPPSs to cyberattacks. This calls for developing solutions that assess and reduce the impacts of cyber-induced failures on CPPSs. This paper proposes a defensive islanding strategy to isolate impacted parts of the CPPS and form self-sufficient islanded grids with an objective of minimum load curtailment. The defensive islanding aims to split a power system into smaller grids to improve its resilience against a potential extreme event. A clustering approach that leverages the hierarchical spectral clustering method is utilized for the optimal defensive islanding. The proposed approach captures the fragility behavior and loading conditions of power system components due to cyber-induced failures. A graphical-based coupling framework is used to map the impacts of cyber failures into operation of power system components. The proposed method is demonstrated on a modified 33-node distribution feeder system integrated with distributed energy resources. The amount of load curtailment and radiality constraints have been used to evaluate the performance of the proposed clustering strategies. The results show the capability of the proposed algorithm to create islands considering the cyber-induced failures for enhanced resilience.

cyber-induced failures↗

A Review of Distributed Secondary Control Architectures in Islanded-Inverter-Based Microgrids

The increasing energy demand, the shortage of energy resources, and the environmental challenges faced by conventional power-generation systems are some of the ongoing challenges faced by modern power systems. Therefore, many efforts have been made by the scientific community to develop comprehensive solutions to overcome these issues. For instance, current technological advances have allowed the integration of distributed generators into the power systems, promoting the use of microgrids to overcome these issues. However, the use of renewable distributed generators have introduced new challenges to the traditional control system schemes. To overcome these challenges, a hierarchical control approach has been proposed for distributed renewable sources. In other words, the control scheme have been divided into three hierarchical levels, primary, secondary, and tertiary, to overcome the new challenges present in modern power systems. Due to extensiveness of this topic, this overview is focused on secondary control systems, mainly for AC isolated microgrids. To improve the power quality of modern systems, several secondary control schemes have been proposed to overcome the well-known problem of frequency and voltage deviation. Some of these schemes have also introduced adequate active/reactive power sharing techniques to optimize the utilization of resources. Additionally, other secondary control schemes have also focused on reducing the communication load, to lower the network cost and adding robustness against communication problems. This article presents an insight of the different control techniques used to overcome power quality and communication problems. A comprehensive overview of distributed secondary control techniques for islanded microgrids is presented. In addition, the implementation of these techniques is explained in an orderly and sequential manner.

14 SOLAR ENERGY↗

Integrating a Microgrid Controller with a Local OpenADR Server

When military microgrids isolate themselves from the main electrical grid, they must locally balance electricity supply and demand. Since local generation may be limited, the current strategy is to shed all but the most critical loads by tripping smart circuit breakers, which must then be reset manually (e.g., ESTCP project EW-201350). This strategy is typically applied at the building level, meaning that entire buildings housing mission critical activities must be excluded from any load management, while those considered non-critical may lose service entirely. The remotely controlled switchgear needed to manage load in this way is very expensive ($\$30,000$-$\$50,000$ per building). While effective at shedding load, this strategy disrupts installation operation and risks damaging equipment during both disconnection and re-energization. With the goals of lowering costs, protecting equipment, and enhancing the agility of DoD microgrids, this report demonstrates the use of cybersecure automated demand response (ADR) technology to manage microgrid loads during grid-independent (a.k.a. "islanded") operation. This automated approach achieves load shedding and shifting through communication signals sent to equipment controllers rather than by cutting off the flow of electricity within the microgrid itself. Because it operates only on the base network, with no connection to external entities, this strategy avoids the main cybersecurity concern raised by past applications of ADR on military bases.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Security Enhancements for Distributed Energy Resource Systems Interconnected with Distribution Networks: Final Technical Report

The revised IEEE 1547 Standard defines new complex communication-adjustable voltage and frequency regulation and ride-through characteristics, while maintaining the general antiislanding requirement for unintentional islanding situations. Unintentional islanding is prohibited while intentional islanding is specifically allowed, thus effectively enabling microgrid operation mode. Further, IEEE 1547-2018 Standard introduces new requirements in terms of interoperability so that the DER plant/circuit segments may be seamlessly integrated with the utility networks but at the same time become vulnerable to a cyber-attack. Traditional cybersecurity measures including encryption, authentication and role-based access control may not be fully implementable to all communication protocols specified in the IEEE 1547 Standard. Therefore, in this project we have identified, researched, implemented and tested several cyberphysical approaches that rely mostly on the behavior of the DER circuit and may help with validating the incoming command and control action potentially coming through an insecure communications channel. Additionally, we have built semantic models and communications profiles for DER facilities and have implemented lightweight IEC 61850 based publisher-subscriber GOOSE messaging mechanism, with security extensions in terms of authentication and encryption. The project proposed information models for integration into UCA OpenFMB 2.0 profiles focusing on grid code compliance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid Resiliency using Hydro-based Microgrids During Wildfires

The primary objective of this project is to assess the techno-economic viability of hydropower resources with supplementary investments, including microgrid controllers, storage solutions, load banks, additional generation like diesel generators, communication links, and transmission infrastructure. The aim is to enable these systems to operate autonomously (in islanded mode) and ensure grid resiliency during and after wildfire events. The project seeks to establish a comprehensive framework for setting up hydropower-based microgrids, from risk estimation to final investment decisions. These microgrids can provide critical support during emergencies and offer additional grid stability and revenue opportunities during regular operations and other system contingencies.