Evaluation and optimization of flow boiling frictional pressure drop correlations using the data from traditional and next-generation refrigerants in a micro-fin tube
This study presents an experimental evaluation and optimization of flow boiling frictional pressure drop correlations for conventional and next-generation refrigerants in a horizontal micro-fin tube, with particular emphasis on the newly emerging refrigerant blends R-454C and R-455A, for which pressure-drop data in enhanced tubes remain limited. Experiments were conducted with R-410A, R-454C, R-455A, R-134a, R-1234yf, and R-1234ze(E) in a copper micro-fin tube with an inner diameter of 8.468 mm, over mass fluxes ranging from 100 to 300 kg/(m²·s) depending on the refrigerant, and evaporation temperatures of 7, 12, and 14 °C. Frictional pressure gradients were determined from measured total pressure drops after subtracting acceleration pressure drop, and the resulting database was used to assess four existing models: Kuo and Wang (1996), Cavallini et al. (1997), Goto et al. (2001), and Diani et al. (2014). The measured frictional pressure gradient increased with vapor quality and mass flux for all refrigerants and increased further at lower evaporation temperatures, with the overall trend strongly related to liquid viscosity. Among the four correlations, the Goto et al. (2001) model provided the best overall agreement with the measured data before optimization. To further improve prediction accuracy, the Kuo and Wang (1996) and Goto et al. (2001) models were optimized using the complete experimental database. After optimization, both models reduced the overall mean absolute deviation to below 15%, while the optimized Goto et al. (2001) model maintained the best and most consistent overall performance. The results provide new pressure-drop data for next-generation refrigerants and demonstrate that parameter optimization can significantly enhance the applicability of existing micro-fin-tube correlations.