Search NASA⌕ Search

SEARCH · Search NASA

Results for “Phase-locked-loop”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

The Cause of Insufficient Damping in Phase-Locked-Loop and Its Influence

Phase-locked loop (PLL) is a critical component that synchronizes grid-following (GFL) inverter-based resources (IBR) to the grid. Insufficient damping in PLL has been identified as a cause associated with real-world weak grid stability issues. This paper reveals that the second-order low-pass filter deployed in a sophisticated PLL structure can have negative influence on damping performance and lead to system instability when the grid is weak and power generation is low. Improving the PLL damping is illustrated as one of the mitigation approaches. The dynamic study is carried out in electromagnetic transient (EMT) simulation environment. In addition to EMT demonstration, a simplified analytical model of PLL is developed to represent a PLL with the sophisticated structure. The resulting overall analytical model of the entire system is then used for eigenvalue- based analysis to illustrate the influence of PLL on dynamic modes.

Wang, Zhengyu↗

Large Angle Deviation in Grid-Following IBRs Upon Grid Voltage Dip

In the 2021 Texas Odessa large-scale solar PV tripping events, phase-locked-loop (PLL) loss of synchronism is identified as a major cause of solar PV tripping. When solar PVs detected a large phase angle deviation (e.g., 10 degrees), tripping commands were initiated. Here, the large phase angle deviation was triggered by a transmission line fault 200 miles away, which in turn led to approximately 30% voltage drop in the 345-kV system. This paper offers a plausible reason why grid-following inverter-based resources (IBRs) may experience a large angle deviation upon grid voltage dip. Critical operating conditions contributing to such phenomena are identified via analysis and their effects are demonstrated using electromagnetic transient (EMT) simulation. Furthermore, the effect of converter control, e.g., grid-following control vs. grid-forming control, is examined. It is found from EMT simulation results that frequency and voltage control are helpful in mitigating angle deviation. Furthermore, linear block diagrams are derived to examine why frequency control can effectively suppress large angle deviation.

14 SOLAR ENERGY↗

A Novel Design for Switchable Grid-Following and Grid-Forming Control

This paper presents the design of a novel grid- forming (GFM) control structure adapted from a typical grid- following (GFL) control structure with minimal edits, thereby enabling a switchable control structure for voltage sourced converters (VSCs) to operate in either GFL or GFM mode by simply switching a flag manually. The VSC is shown to be able to operate in the GFL control mode synchronizing to the main grid through a phase-locked-loop (PLL) and operate as a GFM controller with power-based synchronization for both grid-connected and islanded conditions. To guarantee smooth operation, the control schemes and the mode switching logic have been carefully designed and examined via a series of experiments. Here, the experiment results show that the switchable control structure can fulfill the desired control and operation functions and enable smooth transition between control modes.

14 SOLAR ENERGY↗