DQ Admittance Model Extraction for IBRs via Gaussian Pulse Excitation
While $dq$ admittance models have shown to be very useful for stability analysis, extracting admittance models of inverter-based resources (IBRs) from the electromagnetic transient (EMT) simulation environment using frequency scans takes time. In this letter, a new perturbation method based on Gaussian pulses in combination with the system identification algorithms shows great promise for parametric $dq$ admittance model extraction. We present the $dq$ admittance model extracting method for a type-4 wind turbine. Challenges in implementing Gaussian pulse excitation are also pointed out. In conclusion, the extracted $dq$ admittance model via the new method shows to have a high matching degree with the measurements obtained from frequency scans.