Tests of a reduced-scale experimental model of a building solar heating-cooling system

An experimental solar heating and cooling system model has been built and operated, combining elements that are programmable (e.g., heating and cooling load of a building and collected solar energy) with experimental equipment. The experimental system model was based on the loads and components used in the Solar Building Test Facility (SBTF), which includes a 1394 sq m solar collector field at NASA Langley. These tests covered 5 continuous days under summer conditions. For the system model up to 55 percent of the simulated collected solar energy was used for the building load. This amount of solar energy supplied 35 percent of the building cooling load. Heat loss was significant. If tank heat loss were eliminated, which would make it similar to the actual SBTF, 75 percent of the collected solar energy would be used. This amount would supply approximately 50 percent of the building cooling load. A higher fraction of solar energy is possible with a more performance-optimized system.

Namkoong, D.↗

Experimental solar heating-cooling system model tests of a full-scale building system

An experimental solar heating and cooling system model has been built and operated, combining elements that are programmable - heating and/or cooling load of a building, collected solar energy - with experimental equipment. The system model was based on the loads and components used in the Solar Building Test Facility (SBTF) which includes a 1394 square meter solar collector field, at NASA-Langley. Operations covered 5 continuous days under summer conditions. For the system model, up to 55% of the simulated collected solar energy was used for the building load. This amount constituted 35% of the building cooling load. Heat loss was significant. If tank heat loss were eliminated, 75% of the collected solar energy would be used. This amount would supply approximately 50% of the building cooling load.

Namkoong, D.↗

The economics of solar powered absorption cooling

Analytic procedure evaluates cost of combining absorption-cycle chiller with solar-energy system in residential or commercial application. Procedure assumes that solar-energy system already exists to heat building and that cooling system must be added. Decision is whether to cool building with conventional vapor-compression-cycle chiller or to use solar-energy system to provide heat input to absorption chiller.

Bartlett, J. C.↗

Analysis of building heating and cooling

Energy Conservation Program (ECP) gives design engineer methodology and easy-to-use computer program for simulating hourly thermal characteristics over full year for individually characterized zones within building. Inexpensive system can be used to develop thermal model of building to aid selection of most suitable and economical heating and cooling system for building

Chai, V. W.↗

Solar heating and cooling system for an office building at Reedy Creek Utilities

The solar energy system installed in a two story office building at a utilities company, which provides utility service to Walt Disney World, is described. The solar energy system application is 100 percent heating, 80 percent cooling, and 100 percent hot water. The storage medium is water with a capacity of 10,000 gallons hot and 10,000 gallons chilled water. Performance to date has equaled or exceeded design criteria.

Source record↗

Building application of solar energy. Study no. 4: Scenarios for the utilization of solar energy in southern California buildings, change 1

Plausible future market scenarios for solar heating and cooling systems into buildings in the area served by the Southern California Edison Company. A range of plausible estimates for the number of solar systems which might be installed and the electrical energy which might be displaced by energy from these systems are provided. The effect on peak electrical load was not explicitly calculated but preliminary conclusions concerning peak load can be inferred from the estimates presented. Two markets are investigated: the single family market and the large power commercial market.

Davis, E. S.↗

Initial operation of a solar heating and cooling system in a full-scale solar building test facility

The Solar Building Test Facility (SBTF) was constructed to advance the technology for heating and cooling of office buildings with solar energy. Its purposes are to (1) test system components which include high-performing collectors, (2) test the performance of a complete solar heating and cooling system, (3) investigate component interactions, and (4) investigate durability, maintenance and reliability of components. The SBTF consists of a 50,000 square foot office building modified to accept solar heated water for operation of an absorption air conditioner and for the baseboard heating system. A 12,666 square foot solar collector field with a 30,000 gallon storage tank provides the solar heated water. A description of the system and the collectors selected is printed along with the objectives, test approach, expected system performance, and some preliminary results.

Knoll, R. H.↗

Design and operation of a solar heating and cooling system for a residential size building

The first year of operation of solar house is discussed. Selected design information, together with a brief system description is included. The house was equipped with an integrated solar heating and cooling system which uses fully automated state-of-the art. Evaluation of the data indicate that the solar house heating and cooling system is capable of supplying nearly 100 percent of the thermal energy required for heating and approximately 50 percent of the thermal energy required to operate the absorption cycle air conditioner.

Littles, J. W.↗

Initial operation of a solar heating and cooling system in a full-scale solar building test facility

The Solar Building Test Facility (SBTF) located at Hampton, Virginia became operational in early summer of 1976. This facility is a joint effort by NASA-Lewis and NASA-Langley to advance the technology for heating and cooling of office buildings with solar energy. Its purposes are to (1) test system components which include high-performing collectors, (2) test performance of complete solar heating and cooling system, (3) investigate component interactions and (4) investigate durability, maintenance and reliability of components. The SBTF consists of a 50,000 square foot office building modified to accept solar heated water for operation of an absorption air conditioner and for the baseboard heating system. A 12,666 square foot solar collector field with a 30,000 gallon storage tank provides the solar heated water. A description of the system and the collectors selected is given here, along with the objectives, test approach, expected system performance and some preliminary results.

Knoll, R. H.↗

Assessment of solar-assisted gas-fired heat pump systems

As a possible application for the Goldstone Energy Project, the performance of a 10 ton heat pump unit using a hybrid solar gas energy source was evaluated in an effort to optimize the solar collector size. The heat pump system is designed to provide all the cooling and/or heating requirements of a selected office building. The system performance is to be augmented in the heating mode by utilizing the waste heat from the power cycle. A simplified system analysis is described to assess and compute interrrelationships of the engine, heat pump, and solar and building performance parameters, and to optimize the solar concentrator/building area ratio for a minimum total system cost. In addition, four alternative heating cooling systems, commonly used for building comfort, are described; their costs are compared, and are found to be less competitive with the gas solar heat pump system at the projected solar equipment costs.

Lansing, F. L.↗

Solar energy to heat and cool a new NASA Langley office building

A solar heating and cooling system will be installed at a new NASA office building. The objective of this project is to establish a full-scale working test-bed facility to investigate solar energy for heating and cooling buildings. The energy collected will provide between 80 and 100 percent of the heating and cooling requirements during the cool months and between one-half and two-thirds of the cooling requirements in the summer. Thermal energy storage will be provided to bridge the gap between cloudy and clear days.

Maag, W. L.↗

Public policy for solar heating and cooling

Recent analyses indicated that solar heating and cooling systems for residential buildings are nearly economically competitive with conventional fossil fuel or electric systems, the former having higher initial cost but a lower operating cost than the latter. The paper examines obstacles to the widespread acceptance and use of solar space conditioning systems and explores some general policies which could help to overcome them. The discussion covers such institutional barriers limiting the adoption of solar technologies as existing building codes, financing constraints, and organizational structure of the building industry. The potential impact of financial incentives is analyzed. It is noted that a tax incentive of 25% could speed the use of solar energy by 7 to 8 years and produce an 8% reduction in fossil fuel use by 1990. A preliminary incentive package which could be helpful in promoting solar energy both at federal and state levels is proposed, and the necessary incentive level is analysed.

Hirshberg, A. S.↗

Subcontracted activities related to TES for building heating and cooling

The subcontract program elements related to thermal energy storage for building heating and cooling systems are outlined. The following factors are included: subcontracts in the utility load management application area; life and stability testing of packaged low cost energy storage materials; and development of thermal energy storage systems for residential space cooling. Resistance storage heater component development, demonstration of storage heater systems for residential applications, and simulation and evaluation of latent heat thermal energy storage (heat pump systems) are also discussed. Application of thermal energy storage for solar application and twin cities district heating are covered including an application analysis and technology assessment of thermal energy storage.

Martin, J.↗

Automated Simulation For Analysis And Design

Design Assistant Workstation (DAWN) software being developed to facilitate simulation of qualitative and quantitative aspects of behavior of life-support system in spacecraft, chemical-processing plant, heating and cooling system of large building, or any of variety of systems including interacting process streams and processes. Used to analyze alternative design scenarios or specific designs of such systems. Expert system will automate part of design analysis: reason independently by simulating design scenarios and return to designer with overall evaluations and recommendations.

Cantwell, E.↗

Design, fabrication, testing, and delivery of a solar energy collector system for residential heating and cooling

A low cost flat plate solar energy collector was designed for the heating and cooling of residential buildings. The system meets specified performance requirements, at the desired system operating levels, for a useful life of 15 to 20 years, at minimum cost and uses state-of-the-art materials and technology. The rationale for the design method was based on identifying possible material candidates for various collector components and then selecting the components which best meet the solar collector design requirements. The criteria used to eliminate certain materials were: performance and durability test results, cost analysis, and prior solar collector fabrication experience.

Holland, T. H.↗

The design of a solar energy collection system to augment heating and cooling for a commercial office building

Analytical studies supported by experimental testing indicate that solar energy can be utilized to heat and cool commercial buildings. In a 50,000 square foot one-story office building at the Langley Research Center, 15,000 square feet of solar collectors are designed to provide the energy required to supply 79 percent of the building heating needs and 52 percent of its cooling needs. The experience gained from the space program is providing the technology base for this project. Included are some of the analytical studies made to make the building design changes necessary to utilize solar energy, the basic solar collector design, collector efficiencies, and the integrated system design.

Basford, R. C.↗

Solar-Heated and Cooled Office Building--Columbus, Ohio

Final report documents solar-energy system installed in office building to provide space heating, space cooling and domestic hot water. Collectors mounted on roof track Sun and concentrate rays on fluid-circulating tubes. Collected energy is distributed to hot-water-fired absorption chiller and space-heating and domestic-hot-water preheating systems.

Source record↗

Solar energy system installed at the North Georgia APDC office building

A hydronic, automatic drain-down solar heating and cooling system is described. The system provides solar heat exchange from a 2,001 square foot effective collector area and supplies 65-70 percent of the building's cooling demand, 90-95 percent of the heating demand, and domestic hot water. The acceptance test plan and results, system operation and maintenance, and predicted system performance are presented.

Source record↗