Search NASA⌕ Search

SEARCH · Search NASA

Results for “coordinated voltage control”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Coordination of Energy Storage and Distributed Generation for Voltage Control and Peak-valley Filling

The increasing penetration of distributed energy resources (DERs) in distribution network (DN) poses challenges on voltage control. In addition, the growing integration of DERs also reshapes the traditional load profile. To comprehensively address the voltage control and peak-valley filling in DN, this paper proposes a model predictive control (MPC) based optimization framework. The proposed method can achieve coordinated voltage control and peak-valley filling by adjusting the reactive power output from distributed generations (DGs) and the charging/discharging of energy storage systems (ESS). The performance of the proposed method is demonstrated by simulations on a modified IEEE-123 bus system.

Zhang, Zhengfa [University of Tennessee, Knoxville↗

Distributionally Robust Decentralized Volt-Var Control With Network Reconfiguration

Here, this paper presents a decentralized volt-var optimization (VVO) and network reconfiguration strategy to address the challenges arising from the growing integration of distributed energy resources, particularly photovoltaic (PV) generation units, in active distribution networks. To reconcile control measures with different time resolutions and empower local control centers to handle intermittency locally, the proposed approach leverages a two-stage distributionally robust optimization; decisions on slow-responding control measures and set points that link neighboring subnetworks are made in advance while considering all plausible distributions of uncertain PV outputs. We present a decomposition algorithm with an acceleration scheme for solving the proposed model. Numerical experiments on the IEEE 123 bus distribution system are given to demonstrate its outstanding out-of-sample performance and computational efficiency, which suggests that the proposed method can effectively localize uncertainty via risk-informed proactive timely decisions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

EXERGETIC: De-Risking Next-Generation Resilient Geothermal Hybrids via At-Scale Evaluation Using Virtual Emulation Digital Twin Environment for Efficient Operation

The DOE-GTO-funded project, award number 5.1.2.12, entitled "EXERGETIC - De-risking Next Generation Resilient Geothermal Hybrids via at-Scale Evaluation Using a Virtual Emulation Digital Twin Environment for Efficient Operation," advances the solution to these challenges by developing and validating a geothermal co-emulation environment implemented at the National Laboratory of the Rockies (NLR)'s Advanced Research on Integrated Energy Systems (ARIES) platform. This framework enables the de-risking of next-generation geothermal and geothermal hybrid systems through high-fidelity modeling, real-time digital emulation, advanced control strategies, and techno-economic assessment. The project focused on geothermal hybrid configurations that integrate geothermal power plants with concentrated solar power and underground thermal energy storage, enabling enhanced efficiency, flexibility, and grid support capabilities. The main goal of this project was the development of a geothermal digital co-emulation environment to demonstrate the technical and economic value of geothermal hybrid systems and their contribution to grid stability and flexibility. The EXERGETIC framework combined physics-based models, controls, and real assets at ARIES, including digital real-time simulators (DRTS), a 20-MW-scale controllable grid interface (CGI), and a 2-MW conventional generator. Detailed transient models were developed for the key subsystems of a hybrid geothermal plant, including parabolic trough solar collectors, reservoir thermal energy storage (RTES), and a binary Organic Rankine Cycle (ORC) power plant. The ORC model explicitly captured thermal inertia and off-design operation and integrated control strategies to dynamically respond to electric load profiles. The models were validated against published experimental and numerical studies, demonstrating strong agreement and confirming the accuracy and robustness of the modeling approach. The resulting digital twin represents geothermal-solar-storage systems at multiple scales (1 MW to 100 MW) and enables realistic emulation of grid-connected operation. The control architecture allows the geothermal resource to provide stable baseload generation, while solar and stored thermal energy supply flexible, dispatchable support during periods of high demand or variable grid conditions. A key contribution of the EXERGETIC project is the demonstration that geothermal hybrid systems can be designed to be active grid assets rather than passive baseload generators. Using the ARIES platform, the digital twin was evaluated under multiple grid scenarios, including load following, voltage support at the distribution level, and frequency response at the transmission level. Results show that hybrid geothermal systems can respond effectively to dynamic grid conditions, providing inertia-like behavior, primary frequency support, and voltage regulation through coordinated control. In addition to the performance and grid services capability analysis of geothermal and hybrid geothermal systems, the EXERGETIC project also focused on scalability and techno-economic analysis of geothermal hybrid plants. In particular, for the scalability analysis, machine-learning (ML)-based surrogate models were trained using data generated from the geothermal digital twin under different grid-connected scenarios and plant capacities. These ML models demonstrated strong interpolation and extrapolation capabilities across plant sizes, accurately reproducing both steady-state and transient responses with very low errors. Regarding the techno-economic analysis, plant performance results were integrated with cost models for hybrid geothermal systems, and the levelized cost of electricity (LCOE) was used as the main economic metric to evaluate system performance across a range of system capacities, solar shares, solar multiples, and storage durations. Results indicate that economies of scale significantly reduce geothermal LCOE as plant capacity increases, with large-scale systems (25-100 MW) achieving substantially lower costs than small plants. Hybridization with solar thermal energy and storage further improves economic performance by increasing capacity utilization and enabling flexible dispatch. In addition, thermal storage plays a critical role in reducing LCOE by maximizing geothermal, solar, and stored energy resources. In summary, the results from this project demonstrate that geothermal hybrid systems represent a promising alternative for increasing the energy conversion efficiency of geothermal technologies, contributing to the preservation of geothermal resources, and supporting the transition of geothermal plants from traditional baseload resources into flexible, resilient, and cost-competitive energy conversion technologies.

15 GEOTHERMAL ENERGY↗

Data-Driven Mean-Corrected Recursive Estimation-Based Optimal DER Dispatch for Distribution System Voltage Control

Recent advances in smart inverters offer opportunities to mitigate adverse grid impacts caused by high penetrations of distributed photovoltaics (PV) in distribution grids, such as voltage violations. Here, this paper proposes a novel measurement-driven optimal power flow (OPF)-based distributed energy resource management system (DERMS) voltage regulation via recursive sensitivity estimation informed coordinated control of distributed PV inverters. The proposed approach leverages available grid and controllable DER measurements, eliminating reliance on system model information while being adaptive and robust to volatile operating conditions. A mean-corrected recursive ridge regression (MCRRR) algorithm is proposed for sensitivity estimation, continuously refining the sensitivity model through a closed-form solution. It effectively manages varying grid operating conditions, such as changes in power injections and topology reconfiguration, to facilitate a time-varying update of the Load Sensitivity Factors (LSF). The proposed approach is formulated as a linear programming (LP) problem and is thus scalable to larger-scale distribution systems. Its effectiveness and efficiency are demonstrated on a realistic distribution feeder with high PV penetrations in Southern California, USA.

14 SOLAR ENERGY↗

POWER ELECTRONICS GRID TIED SYSTEM FINAL REPORT

Across the country, electric utilities are grappling with the persistent hurdles of integrating Distributed Energy Resources (DERs). Managing these assets safely and effectively is a complex endeavor, complicated by varying ownership structures, management philosophies, and the diversity of the technologies themselves. Consequently, the industry has seen a proliferation of bespoke system designs, control strategies, and communication frameworks—forcing utilities to spend significant time and resources developing one-off integration solutions. This project addressed these integration hurdles through a scalable demonstration of intelligent devices designed to coordinate and control diverse resources in low-voltage applications. This concept minimized the need for complex integration by transforming the separate DERs into a dispatchable virtual power plant (VPP) with integrated resiliency functions (called a Node). By collaborating with a utility partner, the project focused on developing rapidly implementable use cases that bridged the gap between theoretical control and real-world deployment

99 GENERAL AND MISCELLANEOUS↗

Artificial Intelligence-Driven Management of Sustainable Energy Resources: Visibility, Operation, and Control

The rapid global transition toward sustainable energy resources (SERs) is reshaping how modern power systems are observed, optimized, and controlled. While SERs have significantly advanced decarbonization, their weather dependence, variability, and inverter-dominated characteristics challenge traditional, centralized, and deterministic grid operation. At the same time, the proliferation of high-resolution data from inverters, smart meters, and sensors offers unprecedented visibility into system dynamics. Yet, it also exceeds the analytical capability of conventional model-based approaches. Artificial intelligence (AI) provides a new foundation for addressing these challenges by bridging physical laws with data-driven learning, enabling accurate state awareness, adaptive operation, and coordinated control across distributed assets. This article examines how AI transforms the management of SER-rich power systems along three critical dimensions: 1) enhancing visibility by inferring behind-the-meter (BTM) activities, assessing SER flexibility, and reconstructing system states from sparse or noisy measurements; 2) improving operation through AI-enhanced SER service provision, volt/var control (VVC), and dynamic operating envelopes (DOE) for efficiency and security; and 3) advancing control by embedding learning-based intelligence into inverter coordination, voltage and frequency regulation, and long-term dispatch. Together, these developments reveal how AI can convert the variability of SERs from an operational challenge into a source of flexibility, resilience, and intelligence, paving the way toward sustainable, adaptive, and self-optimizing power systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Improving photovoltaic hosting capacity of distribution networks with coordinated inverter control: A case study of the EPRI J1 feeder

Abstract Adding photovoltaic (PV) systems in distribution networks, while desirable for reducing the carbon footprint, can lead to voltage violations under high solar‐low load conditions. The inability of traditional volt‐VAr control in eliminating all the violations is also well‐known. This article presents a novel coordinated inverter control methodology that leverages system‐wide situational awareness to significantly improve hosting capacity (HC). The methodology employs a real‐time voltage‐reactive power (VQ) sensitivity matrix in an iterative linear optimizer to calculate the minimum reactive power intervention from PV inverters needed for mitigating over‐voltage without resorting to active power curtailing or requiring step voltage regulator setting changes. The algorithm is validated using the EPRI J1 feeder under an extensive set of realistic use cases and is shown to provide 3x improvement in HC under all scenarios.

Dalal, Dhaval [School of Electrical, Computer, and↗

An Innovative Energy Management System for Microgrids with Multiple Grid-Forming Inverters

As increasingly more grid-forming (GFM) inverter-based resources replace traditional fossil-fueled synchronous generators as the GFM sources in microgrids, the existing microgrid energy management systems (EMS) need to be updated to control and coordinate multiple GFM inverters that consider system control objectives under different microgrid connection states. For each state, we formulate an optimization problem and apply a real-time feedback-based control algorithm; altogether, the control algorithms seamlessly connect the states into a generic microgrid EMS that controls the nodal voltages and frequencies, becomes a virtual power plant (VPP) when connected to the main grid, and coordinates power sharing responsibility among GFM sources when islanded. We showcase the EMS on a real-world simulation of a microgrid under the different states to demonstrate its operational effectiveness.

energy management systems↗

Unified Universal Control and Coordination of Inverter-Based Resources, and Validation for a PV + Battery Hybrid Plant

As renewable energy deployment grows, hybrid power plants (HPPs) combining photovoltaic (PV) and battery systems must evolve to offer both energy and grid stability services. These systems typically include a mix of grid-following (GFL) and grid-forming (GFM) inverters, presenting unique coordination and control challenges. This Department of Energy–funded project developed and validated a Unified Universal Control and Coordination (UUCC) framework for such PV + battery hybrid plants, enabling seamless and stable operation, including ultrafast black start, autonomous synchronization, and robust frequency and voltage regulation, under different grid conditions. The project significantly advanced the understanding of inverter-based resource (IBR) control by developing and validating three complementary system-level approaches for hybrid GFL/GFM operation: 1. A combined Virtual Resistance (VR)-based GFL and Virtual Oscillator Control (VOC)-based GFM method, where each inverter type is governed by a specialized control strategy. Together, these achieve stable, fast-response coordination, eliminating inrush current and enabling smooth black start and grid synchronization across a wide range of grid strengths. 2. A Deadbeat-based UUCC strategy, which uses discrete-time, switching-cycle-level control for both GFL and GFM inverters. This approach replaces traditional PI/PLL control with a control parameter-free, high-bandwidth framework that supports stable LVRT and instantaneous synchronization under all conditions. 3. A benchmark comparison with Siemens’ commercial GFM microgrid controller, which provided a fast baseline platform. The commercial approach decoupled v & f control was implemented on a commercial microgrid controller.The baseline commercial benchmark helped highlight superior transient response and black start performance offered by the deadbeat and VOC approaches. These technical contributions offer substantial improvements over conventional inverter control schemes, which often rely on slow phase-locked loop (PLL)-based synchronization, require careful control parameters tuning, and prone to unstable in weak grids with GFL inverters and in stiff grid with GFM inverters therefore challenging for hybrid GFL+GFM under all grid conditions. The deadbeat-based UUCC framework enables simpler, faster, and more robust operation of hybrid IBR systems using wide-bandgap (WBG) devices such as SiC power semiconductors. The rapid expansion of hybrid distributed energy resources (DERs), including residential and commercial PV-BESS installations such as Tesla Powerwall, PV with vehicle-to-grid (V2G) capability, and other integrated configurations, presents complex operational challenges for medium-voltage radial distribution feeders. These networks are subject to frequent disturbances such as faults, switching operations, rapid reclosing sequences, and feeder reconfigurations, all of which introduce dynamic stress on IBRs. In addition, planned feeder segmentation and deliberate islanding for resilience will require DERs that can autonomously perform blackstart, establish voltage and frequency references, and resynchronize with the main grid. The advanced deadbeat-based UUCC control and blackstart functionalities developed in this project directly address these requirements, enabling decentralized and autonomous operation of inverter-dominated DERs in distribution systems under a wide range of fault and reconfiguration scenarios. From a public benefit perspective, these innovations enable more reliable and cost-effective integration of renewable energy into distribution networks. The ability to autonomously black start and stabilize grids under varying grid conditions support accelerates recovery from outages and support decentralized resilient energy systems. By reducing system complexity and improving performance, this project lays critical groundwork for future inverter-dominated power grids that are clean, reliable, and accessible to all.

14 SOLAR ENERGY↗

Mitigating Data Center Impact on Grid Stability: A Coordinated Control Strategy Using Verrus StabiliGrid Architecture

Large data centers, which now represent a significant and growing share of the total U.S. grid load, can inadvertently destabilize the electrical grid when they disconnect simultaneously during brief voltage disturbances. The July 10, 2024, Eastern Interconnection incident, in which a sub-100-millisecond transmission fault triggered the cascading loss of approximately 1,500 MW of data center load, illustrates this vulnerability. While commercial battery energy storage systems (BESS) deployed in data centers provide device-level fault ride-through per IEEE 1547, they lack coordination with facility protection logic and uninterruptible power supplies (UPS), limiting their effectiveness as grid-stabilizing assets. This report presents the Verrus StabiliGrid architecture, a coordinated control framework that integrates BESS, UPS, and point-of-interconnection (POI) protection settings to enable data centers to ride through both undervoltage and overvoltage grid contingencies without disconnecting. The four-step strategy encompasses: (1) high-resolution power quality monitoring to detect the grid state during events such as undervoltage, overvoltage, underfrequency, and overfrequency; (2) POI protection settings that allow for extended ride-through and grid-connected operation during grid contingencies; (3) grid state-driven autonomous dispatch of assets to improve grid resilience by reducing power draw during undervoltage or absorbing more power during overvoltage events; and (4) coordinated post-recovery dispatch of data center assets to restore firm load to pre-contingency levels. Validated through controller-hardware-in-the-loop (C-HIL) simulations at the National Laboratory of the Rockies, results show grid import restoration to pre-fault levels within 100 milliseconds of voltage recovery. This work advances the ability of data centers to transition from passive, disturbance-sensitive loads to active participants in grid stability, a capability increasingly required by emerging NERC and ERCOT regulatory frameworks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

An Innovative Energy Management System for Microgrids with Multiple Grid-Forming Inverters

As increasingly more grid-forming (GFM) inverter-based resources replace traditional fossil-fueled synchronous generators as the GFM sources in microgrids, the existing microgrid energy management systems (EMS) need to be updated to control and coordinate multiple GFM inverters that consider system control objectives under different microgrid connection states.For each state, we formulate an optimization problem and apply a real-time feedback-based control algorithm; altogether, the control algorithms seamlessly connect the states into a generic microgrid EMS that controls the nodal voltages and frequencies, becomes a virtual power plant (VPP) when connected to the main grid, and coordinates power sharing responsibility among GFM sources when islanded. We showcase the EMS on a real-world simulation of a microgrid under the different states to demonstrate its operational effectiveness.

energy management system↗

Cyber‐Resilient Distributed Energy Resource Control Algorithms for Smart Distribution Grids

ABSTRACT This paper focuses on the development of cyber‐resilient gradient‐based optimisation algorithms and theoretical proof for grid‐interactive distributed energy resource (DER) control to enable two grid services of virtual power plants (VPPs) dispatch and grid voltage regulation, considering the communication and security impacts. Firstly, the combined DER dispatch and voltage regulation as a real‐time gradient‐based optimisation problem is recapped. Thereafter, we consider a probabilistic traffic model to characterise packet delays and loss in a communication network, and study how the delays enter the process of information exchange among the grid measurement units, local DER controllers and the grid control centre that execute this control algorithm in a coordinated manner. Then, a strategy combining delay thresholds and message update rules is proposed to immunity the asynchrony resulting from the communications traffic and it avoids possible numerical instabilities and sensitivities of the power tracking and voltage regulation capabilities, resulting as cyber‐resilient DER control algorithms. Additionally, their convergence is theoretically proved. Effectiveness of proposed cyber‐resilient algorithms has been validated on the IEEE 37‐bus system in terms of convergence, VPP tracking and voltage regulation performance for smart distribution systems with high penetration of DERs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Peer-to-peer communication control for resilient operations of networked cyberphysical systems

This report includes two main accomplishments of the peer-to-peer communication control for resilient operation of networked microgrids project in FY24, which include a scheme for cyberattack-aware coordination of networked microgrids for supporting voltages of bulk power systems and a scheme for price signal-based operations of EV-rich networked microgrids with mixed ownership. First, the cyberattack-aware scheme enables networked microgrids to distributedly determine the amount of reactive power injection to support the voltage of bulk power system (BPS) in a fair manner. In this scheme, a risk-informed algorithm is presented to generate the peer-to- peer (P2P) communication graph with minimal risk of attack on communication links. To deal with cyberattacks on MG controllers, the resilient consensus algorithm (CA) is utilized for MG controllers to robustly estimate the total reactive power headroom, from which the MGs can accurately provide the needed amount of reactive power injection for supporting the voltage of BPS. The CA implementation and performance within the P2P communication framework are demonstrated on the IEEE 39-bus system with 6 microgrids contained in the distribution feeder under different cyberattack scenarios. Second, the price-based scheme enables the usage of the real-time price signal for the operations of electric vehicle (EV)-rich networked-microgrids with mixed ownership, in which not all the microgrids can communicate with the distribution system operator (DSO). In this scheme, a max consensus is introduced to enable the real-time price signal to be propagated from the DSO to all the microgrids, from which each microgrid controller will manage the DERs to balance the load demand and the power injection from the EV charging stations within its microgrid. Numerical results over one day with 288 slots of 5-minute intervals on the modified 123-node test feeder including 3 microgrids with high penetration of EV are presented to evaluate how the price signal affects the operations of networked microgrids under different charging strategies of the EV charging stations. The result indicates that our proposed EVCS (dis)charging strategy, which leverages the flexibility of EVs to support the grid through discharging during peak demand, proves to be a cost-effective solution that reduces operational costs while improving the social welfare of EV charging.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Secondary Control Framework for Microgrid Interoperability With Vendor-Agnostic Grid-Forming Units: Design, Implementation, and Demonstration via Large-Scale Hardware Setup

The reliable operation of islanded microgrids increasingly depends on secondary controls that restore voltage and frequency to nominal values and ensure accurate active and reactive power sharing. Centralized secondary control architectures achieve high accuracy through global coordination at the cost of single-point failures and limited scalability compared with decentralized/distributed approaches. But a critical gap remains in addressing the interoperability and vendor-agnostic operation of secondary controls in real-world microgrids where heterogeneous diesel generator(s) and grid-forming (GFM) inverter(s) from multiple manufacturers always coexist. Practical and vendor-agnostic interoperability guidelines for the secondary control architecture of microgrids with multiple GFM units have not yet been developed; therefore, this paper proposes an interoperable and vendor-agnostic secondary control framework that operates seamlessly across GFM units from different vendors without relying on proprietary controls and protocols, hardware, or lock-ins. The framework leverages existing communication infrastructures (e.g., Modbus TCP/IP) to enable cost-effective deployment while addressing practical challenges, such as packet loss and quantization errors. Mitigation strategies-including data averaging, situational event-triggered control, and finite-iteration execution-are introduced to enhance reliability under real-world conditions. A generalized modeling and design framework is also presented, supported by robustness analysis to demonstrate independence from vendor-specific implementations. The proposed framework is validated through a large-scale hardware demonstration using a 3-$\phi$, 480-V, 60-Hz, 713-kVA laboratory hardware microgrid involving a heterogeneous diesel generator and multiple GFM inverters, showcasing its effectiveness in achieving stable voltage and frequency restoration and accurate power sharing under practical constraints. The results highlight the framework's potential as a scalable and practical solution for next-generation microgrids requiring openness, standard framework, and interoperability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Enabling Evaluation of a Southern Company Distribution Feeder on NREL ADMS Test Bed: Cooperative Research and Development (Final Report)

The objective of this project is to enable evaluation of a Southern Company distribution feeder on the Advanced Distribution Management System (ADMS) test bed. The long-term goal is to evaluate a federated distributed energy resource (DER) management solution that aggregates DERs through either direct control, transactive control or an aggregator to provide bulk services while observing distribution system voltage and power constraints. The DER aggregation needs to be coordinated with an ADMS that is responsible for reliable power delivery across the distribution systems. This project takes the first step towards enabling such evaluation by deploying an ADMS from Oracle (Southern Company's ADMS supplier) with a Southern Company feeder at NREL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Safe Deep Reinforcement Learning for Active Distribution System Model Predictive Control with EVs and DERs

The temporal and spatial mismatch between PV generation and electric vehicle (EV) charging and discharging may cause voltage violations in active distribution networks. Despite the widespread use of deep reinforcement learning (DRL) in power system optimization and control, it lacks guarantees on constraint satisfaction during both training and deployment. This paper proposes a Lagrangian-based safe DRL approach for model predictive control (MPC) of active distribution systems with large-scale integration of PVs, EVs, and energy storage systems (ESSs). A Transformer-LSTM time-series model is proposed to forecast EV charging demand, which is then formulated as a constraint to ensure charging requirements are met. Using this prediction, a Lagrangian-based safe soft actor-critic (SAC) framework is developed for real-time control in a three-phase unbalanced distribution system, enforcing voltage safety constraints while optimizing the cumulative net reward. By integrating the forecasting model with multi-period constraints, the proposed framework jointly coordinates PV systems, EV charging and discharging, and ESS scheduling within the MPC horizon. Numerical experiments on a modified IEEE 123-bus system with real-world data show that, under a high PV penetration scenario, the proposed method increases the net reward by 30.74% and reduces average voltage violations from 0.0011 p.u. to 0.0002 p.u. compared with standard SAC. Compared with the optimal power flow (OPF) approach, it achieves similar voltage security while yielding lower line losses. It also maintains real-time control capability, reducing operation latency to 53.21 ms per 15-minute control interval. The proposed method remains effective under varying PV/EV penetrations and load conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Control Oriented Models for Co-Design: Technical Overview of MT HVDC, MVDC, and Solid State Transformer Building Blocks

The electric power system is shifting toward a power electronics–enabled grid, where converter based “building blocks” (e.g., high voltage direct current (HVDC) links, multi terminal HVDC (MT HVDC) networks, medium voltage DC (MVDC) links, and solid state transformers (SSTs)) provide fast, precise control of power flows, voltage, and frequency. This report develops and applies publicly shareable electromagnetic transient (EMT) and phasor models to examine how such building blocks can be composed and coordinated to support offshore wind integration, inter area transfers, feeder support, and resilience. Section 2 documents a modular multilevel converter (MMC)–based MT HVDC modeling framework and two use cases: a compact WSCC/IEEE 9 bus test system and a 240 bus “mini WECC” case with five offshore wind plants (OWFs). Phasor to EMT transfer, initialization, and sanity checks are summarized, and neutral demonstrations of normal and contingency operation are reported. Section 3 frames the problem of wind plant inertial frequency response (IFR): shaping energy release and recovery to improve nadir while avoiding aerodynamic stall; representative simulations illustrate the issues without disclosing proprietary control. Section 4 develops MVDC concepts through an IEEE 16 bus loop and an Olympic Peninsula case study that compares AC vs. MVDC corridors and shows how feeder headroom can be pooled via DC couplers. Section 5 surveys SST architectures and identifies a gap: scalable, communication free coordination of multiple SSTs for islanded feeder networks. Across the report, novel methods and configurations under separate publication and IP review are not disclosed; only topic oriented, replicable setups and non proprietary results are shown. These models and use cases are intended as foundations for future publications and co design studies on architecture, control, and coordination of PE enabled grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Interoperable, Inverter - Based Distributed Energy Resources Enable 100% Renewable and Resilient Utility Microgrids

As microgrids transition away from use of conventional generating resources and increasingly rely on renewable resources towards decarbonization goals, it is crucial to evaluate the capability inverter-based resources to provide microgrid stability and resilience. Particularly, microgrids with a high contribution of intermittent solar photo voltaic generation and higher load variability present unique challenges requiring fast voltage and frequency support. At the San Diego Gas & Electric Company(R) (SDG&E(R)) Borrego Springs Microgrid, a battery inverter was upgraded with grid-forming (GFM) capability to serve as island leader, transitioning responsibility away from diesel generators. An interoperable microgrid control scheme was developed, coordinating GFM and grid-following (GFL) inverters. Hardware-in-the-loop (HIL) simulations using relevant power and controller HIL interfaces between real-time simulators and field equipment are being conducted to de-risk field deployment.

battery energy storage↗