Event-Type Identification in Power Grids Using a Spectral Correlation Function-Aided Convolutional Neural Network
Not Available
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
Not Available
Fault diagnostics are extremely important to decide proper actions toward fault isolation and system restoration. The growing integration of inverter-based distributed energy resources imposes strong influences on fault detection using traditional overcurrent relays. This paper utilizes emerging graph learning techniques to build new temporal recurrent graph neural network models for fault diagnostics. The temporal recurrent graph neural network structures can extract the spatial-temporal features from data of voltage measurement units installed at the critical buses. From these features, fault event detection, fault type/phase classification, and fault location are performed. Compared with previous works, the proposed temporal recurrent graph neural networks provide a better generalization for fault diagnostics. Moreover, the proposed scheme retrieves the voltage signals instead of current signals so that there is no need to install relays at all lines of the distribution system. Therefore, the proposed scheme is generalizable and not limited by the number of relays installed. The effectiveness of the proposed method is comprehensively evaluated on the Potsdam microgrid and IEEE 123-node system in comparison with other neural network structures.
Classification of power system event data is a growing need, particularly where non-protective relaying-based sensors are used to monitor grid performance. Given the high burden of obtaining event data with appropriate labeling, an unsupervised approach is highly valuable. This approach enables using event data without labeling, which is far easier to obtain. This paper presents an unsupervised learning method to classify and label transients observed in the distribution grid. A Convolutional Variational Autoencoder (CVAE) was developed for this purpose. We demonstrate the efficacy of our approach using the transient data generated from the simulations. The simulation data is used to train the CVAE that identifies different faults as different clusters in the latent space. The clusters are then used as the foundation model to categorize the real-world data.
This paper presents a 1-D convolutional and graph convolutional networks for fault detection in microgrids. The combination of 1-D convolutional neural networks (1D-CNN) and graph convolutional networks (GCN) helps extract both spatial-temporal correlations from the voltage measurements in microgrids. The fault detection scheme includes fault event detection, fault type and phase classification, and fault location. There are five neural network model training to handle these tasks. Transfer learning and fine-tuning are applied to reduce training efforts. The combined 1-D convolutional and graph convolutional networks (1D-CGCN) is compared with the traditional ANN structure on the Potsdam 13-bus microgrid dataset. The accuracy of 99.5%, 98.4%, 99.2%, and 95.5% are achieved in fault event detection, fault type classification, fault phase identification, and fault location respectively. The detailed confusion matrices of fault type and fault phase classification are provided for validation.
Danovo Energy Solution's presented its paper named: Feature-Based PMU Event Classification under Variable PMU Participation and Overlapping Events at the 2026 Georgia Tech Fault & Disturbance Analysis Conference. The full paper can be found at OSTI ID# 3169150 Paper Abstract—Phasor Measurement Units (PMUs) stream time synchronized, high-resolution measurements from the grid, enabling data-driven techniques for event detection and classification. Accurate event classification improves grid reliability and stability. Events can be detected by varying numbers of PMUs and exhibit different durations depending on the event type. This variability challenges standard classifiers that require uniform input sizes. Moreover, multiple events may coincide, which increases classification complexity. Standard classifiers assign each instance to the class with the highest predicted probability, whereas overlapping events may exhibit comparable probabilities across multiple classes. In this study, to handle data size variability, we extract a wide range of time–frequency domain features from all available PMUs for each event into a fixed-length vector, facilitating the application of standard machine learning classifiers, including Random Forest, XGBoost, LightGBM, Support Vector Machine, and Multilayer Perceptron. To account for overlapping events, a probabilistic post-processing step is applied. For a given data instance, if multiple predicted class probabilities exceed 30% and the differences between them are less than 10%, the event is assigned to multiple classes. Experiments using real-world PMU data demonstrate that the Random Forest and XGBoost models achieve the highest accuracy, while the proposed post-processing method yields perfect classification performance on external unseen test sets.
This paper is the basis for a presentation help at the 2026 Georgia Tech Fault & Disturbance Analysis Conference, which can be found at OSTI # 3168287 Paper Abstract—Phasor Measurement Units (PMUs) stream time synchronized, high-resolution measurements from the grid, enabling data-driven techniques for event detection and classification. Accurate event classification improves grid reliability and stability. Events can be detected by varying numbers of PMUs and exhibit different durations depending on the event type. This variability challenges standard classifiers that require uniform input sizes. Moreover, multiple events may coincide, which increases classification complexity. Standard classifiers assign each instance to the class with the highest predicted probability, whereas overlapping events may exhibit comparable probabilities across multiple classes. In this study, to handle data size variability, we extract a wide range of time–frequency domain features from all available PMUs for each event into a fixed-length vector, facilitating the application of standard machine learning classifiers, including Random Forest, XGBoost, LightGBM, Support Vector Machine, and Multilayer Perceptron. To account for overlapping events, a probabilistic post-processing step is applied. For a given data instance, if multiple predicted class probabilities exceed 30% and the differences between them are less than 10%, the event is assigned to multiple classes. Experiments using real-world PMU data demonstrate that the Random Forest and XGBoost models achieve the highest accuracy, while the proposed post-processing method yields perfect classification performance on external unseen test sets.
Power system protection devices have transitioned over the past few decades from mechanical to analog devices, then to solid state and finally digital. Relays and their associated critical network of equipment have significantly increased in complexity. Even internally, relays have gained significant intricacy, with relatively simple overcurrent or differential functions now being assisted by a myriad of other functions. This is necessary as the grid becomes more complex, but it brings increased difficulty in monitoring and upkeep. Misoperation caused by improper relay settings or malicious actions is a constant challenge faced by all utilities. These improper settings can be difficult to identify and may require exhaustive post-mortem analysis, typically after a major outage event has already occurred. A mechanism is needed for monitoring the behavior of protection systems to validate that they act and perform as expected. This work presents a concept for a machine learning (ML) system capable of validating the performance of protection systems by classifying anomalous events and characterizing protection system responses based solely on available current and voltage measurements. As a first step in its development, an experimental dataset is generated, and a random forest model is implemented with high accuracy in distinguishing four power system scenarios.
Power system protection devices have transitioned over the past few decades from mechanical to analog devices, then to solid state and finally digital. Relays and their associated critical network of equipment have significantly increased in complexity. Even internally, relays have gained significant intricacy, with relatively simple overcurrent or differential functions now being assisted by a myriad of other functions. This is necessary as the grid becomes more complex, but it brings increased difficulty in monitoring and upkeep. Misoperation caused by accidental improper relay settings or deliberate malicious actions is a constant challenge faced by all utilities. These improper settings can be difficult to identify and may require exhaustive post-mortem analysis, typically after a major outage event has already occurred. A mechanism is needed for monitoring the behavior of protection systems to validate that their performance falls within expectations. Relays that fail to isolate a fault or trip when there is no system disturbance can be flagged for settings review in situations where this behavior may not have been noticed due to manual restoration or backup protection operations. This work presents a concept for a machine learning (ML) system capable of validating the performance of protection systems by identifying fault events and characterizing protection system responses based solely on available current and voltage measurements. As a first step in its development, an experimental dataset is generated, and a random forest model is implemented with high accuracy in distinguishing four power system scenarios.
As power system protection devices continue the widespread transition from analog to digital, they become increasingly intricate. The internal functions and communication between critical grid components must now be significantly more complex to keep up with the demands of the modern smart grid. This brings increased difficulty in maintenance and monitoring, making it harder to identify potential misoperation, power anomalies, and cyber threats. Such issues are often only pinpointed after an exhaustive and costly post-mortem analysis, when a major outage or damage has already occurred. A solution is needed for validating protection systems as they operate, independently evaluating grid state and confirming whether the protection system is behaving accordingly. As opposed to incident response, this acts as a constant verification mechanism that raises a flag when subtler issues are noticed, catching them earlier and preventing larger incidents. This work presents the implementation of such a system, expanding on the prototype developed by the authors in a previous paper. This is accomplished with a machine learning (ML) system capable of validating the performance of protection systems by classifying anomalous events and characterizing protection system responses based solely on available current and voltage measurements. Additionally, this system is contextualized within a larger, modular Master State awareness Overseer (MSO) framework, responsible for monitoring, analyzing, and managing an electric grid.
Characterization of induced microseismicity at a carbon dioxide (CO 2 ) storage site is critical for preserving reservoir integrity and mitigating seismic hazards. We apply a multilevel machine learning (ML) approach that combines the nonnegative matrix factorization and hidden Markov model to extract spectral representations of microseismic events and cluster them to identify seismic patterns at the Illinois Basin-Decatur Project. Unlike traditional waveform correlation methods, this approach leverages spectral characteristics of first arrivals to improve event classification and detect previously undetected planes of weakness. By integrating ML-based clustering with focal mechanism analysis, we resolve small-scale fault structures that are below the detection limits of conventional seismic imaging. Our findings reveal temporal bursts of microseismicity associated with brittle failure, providing insights into the spatio-temporal evolution of fault reactivation during CO 2 injection. This approach enhances seismic monitoring capabilities at CO 2 injection sites by improving fault characterization beyond the resolution of standard geophysical surveys.
Smart grid technology enhances our comprehension and reliability of the power grid, leveraging Phasor Measurement Unit (PMU) data—time-synchronized, high-frequency measurements gathered across the US power grid. This paper employs machine learning techniques to effectively analyze the vast PMU data in Wide Area Monitoring Systems (WAMS) for power grid event detection and classification. Analyzing several months of real-world PMU data, the paper focuses on machine learning for fast, precise event detection and classification, corroborated by utility event logs. Practical challenges like feature extraction, dimensionality reduction, and model selection are addressed. A novel feature yielding improved results is discovered, and a supplementary algorithm for detecting small power grid faults is developed. The final algorithm is validated using a month-long real PMU data set, demonstrating its capability in accurately identifying power grid events in near real-time.
This paper presents a convolutional neural network (CNN) developed to identify voltage events in photovoltaic (PV) inverters. The CNN is trained on synthetic data generated using the IEEE 13-bus distribution feeder model and evaluated on field measured data collected from Energy Northwest’s Horn Rapids Solar, Storage, and Training (HRSST) facility. The study focuses on two common voltage events: faults and voltage sags. The CNN is configured to analyze voltage and current waveforms from three-phase PV systems, demonstrating excellent accuracy during training. Field data from the HRSST facility is employed to assess its real-world performance, where the CNN achieves perfect identification of faults and voltage sags in a sample of nine events. This work highlights the potential of the proposed method to enhance PV protection schemes, providing a robust foundation for improved voltage event detection and grid reliability.
We survey how AI/ML is being deployed across Jefferson Lab's experimental and accelerator programs. In EPSCI, Hydra applies computer vision to automate real-time data-quality monitoring across all four experimental halls, replacing manual inspection of hundreds to thousands of histograms per shift. AIEC (AI Experiment Controls) uses ML to stabilize drift chamber gains and is now part of standard CEBAF production running, while AI Optimized Polarization (AIOP) targets autonomous control of polarized targets and photon beam angular alignment. In CASA, cavity fault classification models identify faulted cavities and trip types from waveform data with ~85% and ~78% agreement to labeled data, respectively, and are deployed in production; a separate effort applies LLMs and hybrid search to make the CEBAF operations logbook AI-ready. QCD-focused work includes transformer- and GAN-based generative models for particle-level event simulation, with distributed GAN training scaling studies on Polaris. Additional efforts span ML-on-FPGA for the EIC and a new Data Science Department coordinating anomaly detection, uncertainty quantification, and HPC-scalable ML lab-wide. Collectively, these projects illustrate AI's growing role in improving efficiency across JLab's nuclear physics mission.
This report addresses the requirements of Milestone M3.4 AI capability to identify and predict maintenance events. Development of digital twins (DT) for molten salt reactor (MSR) components is crucial for reducing operating and maintenance costs (O&M) and ensuring commercial viability of these reactors. Our focus is on development of DT for MSR primary system heat exchanger (HX), a critical component, the fault in which can reduce operating efficiency and force reactor shutdown. We are investigating the feasibility of a conceptual DT of HX consisting of internal distributed temperature sensing with fiber optics and machine learning (ML) algorithms to detect and localize faults. To determine the optimal approach to detection and localization of channel plugging, we benchmark seven different ML models: Logistic Regression, K-Nearest Neighbors (KNN), Gaussian Naïve Bayes, Support Vector Machines (SVM), Decision Tree Classifier, Random Forest Tree Classifier, and Feed-Forward Neural Network. ML algorithms are benchmarked using synthetic HX plugging data generated with computational fluid dynamics COMSOL software, with added brown noise to represent experimental noise. We show that the best performance is obtained with the Decision Tree classifier.
Individual seismic catalogs can contain multiscale observations from fault level to global scales and associated waveforms from discrete events reflect crustal structure across many different scales and locations. Seismic network aperture, geographic location, and observation distance may not provide informative guidance or intuition on how different catalogs will behave across models trained under different conditions. We rely on uncertainty to provide guardrails for when to trust model decisions, but understanding when our uncertainty is trustworthy is an open challenge. Here, in this work, we explore Bayesian approximation methods for assigning predictive uncertainty in seismic event classification problems. We find that computationally expensive Bayesian approximations do not outperform simple ensemble methods. We also find that when exploiting multiple seismic event catalogs, joint training with data from all the catalogs combined with Bayesian approximations and supervised training for classification can obscure bias and result in less robust uncertainty while also not providing substantial performance benefits compared to training individual models for each catalog.