Response to Questionnaire of Grid Control Architecture Description Document: Mission Innovation, Innovation Challenge 1. Task 5 – New Grid Control Architectures. Subtask 5.1 – Collection of Available New Grid Control Architectures

As part of Task 5 (New Grid Control Architectures) of Mission Innovation, Innovation Challenge 1, a questionnaire was provided to all countries participating in the project. In this document, PNNL has responded to the questionnaire with information regarding new grid control architectures being proposed or developed in the US. Ron Melton sent the report to all participants.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modified Virtual Oscillator Based Operation of Grid Forming Converters with Single Voltage Sensor

Virtual oscillator based control architecture for grid forming converter with inner current control loop for additional objective accomplishments is proposed in this paper. In general, virtual oscillator is based on Lienard type of oscillator equation with a cubic nonlinearity. Virtual oscillator alone cannot accommodate unbalanced or harmonic mitigation while operating converters in grid forming mode. Therefore, to accomplish better tracking performance, incorporating the provision for nonlinear and/or unbalanced loads, an inner current control loop is utilized which is based upon Lyapunov energy function type control architecture due to its advantages. To reduce the overall cost of implementation and ensure proper phase difference in the generated voltages, the implemented virtual oscillator operates with only one voltage feedback from the point of common coupling as presented in this paper. To verify the effectiveness of the proposed approach, the overall system has been modeled in MATTLAB/Simulink and PLECS domain and case studies showing the successful production of low harmonic load voltages under nonideal loading condition along with other important results are presented in this paper.

dual second order generalized integrator↗

A hybrid architecture for volt-var control in active distribution grids

Modern active distribution grids are characterized by the increasing penetration of distributed energy resources (DERs). The proper coordination and scheduling of a large numbers of these small-scale and spatially distributed DERs is necessary, and warrants the use of novel distributed approaches. In this paper, we propose a hybrid volt-var control architecture for the distribution grid, which leverages existing centralized and local approaches to planning, decision making, and control, and augments it with distributed optimization and distributed control for DER management. First, we propose a convex model to describe the power physics of distribution grids of meshed topology and unbalanced structure, based on current injection and McCormick Envelopes. Second, we employ the distributed proximal atomic coordination (PAC) algorithm to coordinate DERs to provide voltage support. We implement volt-var optimization by optimally coordinating DERs including PV smart inverters and demand response. We present results using the IEEE-34 bus network, using real data from a distribution feeder in Hawaii, to model load and PV generation. Different levels of DER penetration and objective functions are simulated. Finally, our results show the need for the coordination of DERs to improve voltage profiles, even in networks with existing voltage control devices. Further, we show the need for flexible reactive power capabilities to achieve desired grid performance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Synchronization in electric power networks with inherent heterogeneity up to 100% inverter-based renewable generation

The synchronized operation of power generators is the foundation of electric power network stability and a key to the prevention of undesired power outages and blackouts. Here, we derive the conditions that guarantee synchronization in power networks with inherent generator heterogeneity when subjected to small perturbations, and perform a parametric sensitivity analysis to understand synchronization with varied types of generators. As inverter-based resources, which are the primary interfacing technology for many renewable sources of energy, have supplanted synchronous generators in ever growing numbers, the center of attention on associated integration challenges have resided primarily on the role of declining system inertia. Our results instead highlight the critical role of generator damping in achieving a stable state of synchronization. Additionally, we report the feasibility of operating interconnected electric grids with up to 100% power contribution from inverter-based renewable generation technologies. Our study has important implications as it sets the basis for the development of advanced control architectures and grid optimization methods that ensure synchronization and further pave the path towards the decarbonization of the electric power sector.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Mitigating Data Center Impact on Grid Stability: A Coordinated Control Strategy Using Verrus StabiliGrid Architecture

Large data centers, which now represent a significant and growing share of the total U.S. grid load, can inadvertently destabilize the electrical grid when they disconnect simultaneously during brief voltage disturbances. The July 10, 2024, Eastern Interconnection incident, in which a sub-100-millisecond transmission fault triggered the cascading loss of approximately 1,500 MW of data center load, illustrates this vulnerability. While commercial battery energy storage systems (BESS) deployed in data centers provide device-level fault ride-through per IEEE 1547, they lack coordination with facility protection logic and uninterruptible power supplies (UPS), limiting their effectiveness as grid-stabilizing assets. This report presents the Verrus StabiliGrid architecture, a coordinated control framework that integrates BESS, UPS, and point-of-interconnection (POI) protection settings to enable data centers to ride through both undervoltage and overvoltage grid contingencies without disconnecting. The four-step strategy encompasses: (1) high-resolution power quality monitoring to detect the grid state during events such as undervoltage, overvoltage, underfrequency, and overfrequency; (2) POI protection settings that allow for extended ride-through and grid-connected operation during grid contingencies; (3) grid state-driven autonomous dispatch of assets to improve grid resilience by reducing power draw during undervoltage or absorbing more power during overvoltage events; and (4) coordinated post-recovery dispatch of data center assets to restore firm load to pre-contingency levels. Validated through controller-hardware-in-the-loop (C-HIL) simulations at the National Laboratory of the Rockies, results show grid import restoration to pre-fault levels within 100 milliseconds of voltage recovery. This work advances the ability of data centers to transition from passive, disturbance-sensitive loads to active participants in grid stability, a capability increasingly required by emerging NERC and ERCOT regulatory frameworks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Robust Decentralized Secondary Control Scheme for Inverter-based Power Networks

Inverter-dominated microgrids are quickly becoming a key building block of future power systems. They rely on centralized controllers that can provide reliability and resiliency in extreme events. Nonetheless, communication failures due to cyber-physical attacks or natural disasters can make autonomous operation of islanded microgrids challenging. This paper examines a unified decentralized secondary control scheme that is robust to inverter clock synchronization errors and can be seamlessly applied to grid-following or grid-forming control architectures. The proposed scheme overcomes the well-known stability problem that arises from parallel operation of local integral controllers. Theoretical guarantees for stability are provided along with criteria to appropriately tune the secondary control gains to achieve good frequency regulation performance while ensuring fair power sharing. The efficacy of our approach is demonstrated through simulations on a 5-bus microgrid with four grid-forming inverters.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modified Virtual Oscillator-Based Operation of Grid-Forming Converters with Single Voltage Sensor: Preprint

This paper proposes a virtual oscillator-based control architecture for a grid-forming converter with an inner current control loop. In general, the virtual oscillator is based on a Lienard type of oscillator equation with a cubic nonlinearity. A virtual oscillator alone cannot accommodate unbalanced or harmonic mitigation while operating converters in grid-forming mode. Therefore, to accomplish better tracking performance, incorporating the provision for nonlinear and/or unbalanced loads, an inner current control loop is utilized that is based on the Lyapunov energy function type control architecture. To reduce the overall cost of implementation and ensure proper phase difference in the generated voltages, the implemented virtual oscillator operates with only one voltage feedback from the point of common coupling. To verify the effectiveness of the proposed approach, the overall system has been modeled in MATTLAB/Simulink and PLECS domain. This paper also presents case studies showing the successful production of low harmonic load voltages under nonideal loading conditions, along with other important results.

dual second order generalized integrator↗

Hierarchical Control of Grid-Connected Hydrogen Electrolyzer Providing Grid Services

This paper presents the operational modes and control architecture of the grid-connected hydrogen electrolyzer systems for the provision of frequency and voltage supports. The analysis is focused on the primary and secondary loops in the hierarchical control scheme. At the power converter inner control loop, the voltage- and current-control modes are analyzed. At the primary level, the droop and opposite droop control strategies to provide voltage and frequency support are described. Coordination between primary control and secondary, tertiary reserves is briefly discussed. The case studies and real-time hardware-in-the-loop simulation results are provided using Typhoon HIL to back the theoretical investigation.

ancillary services↗

Data-Enhanced Hierarchical Control to Improve Distribution Voltage with Extremely High PV Penetration

Dynamic, scalable, and interoperable control paradigms are required to enable efficient, secure, reliable, and resilient distribution grid operations with widespread grid integration of renewable energy resources. This paper presents our recent research on developing a novel, holistic, data-enhanced hierarchical control architecture that addresses the formidable challenges faced by emerging distribution grids with increasing penetrations of distributed energy resources. The proposed architecture integrates centralized monitoring and control with distributed grid-edge control and thus effectively deals with multi-spatiotemporal dynamics existing in the grid. Simulation results are provided to demonstrate the effectiveness of the proposed control architecture.

14 SOLAR ENERGY↗

Operation and Control of Soft Switching Solid State Transformer as a Virtual Synchronous Machine for Photovoltaic Application

Possibility for control and operation of a three-phase solid state soft switching transformer based as a virtual synchronous machine or synchronverter has been investigated in this paper. The soft switching solid state transformer is used as an interface between the ac grid and a photovoltaic power generation unit supported by a battery bank. The control architecture investigated in this paper is that of a synchronverter to achieve inertial support to the grid and local loads. The operation of the soft switching solid state transformer has also been investigated as a V S M during unbalanced/distorted grid voltage condition. Control objective to achieve oscillation free power transfer between the ports (photovoltaic, battery and grid) has been achieved. The presented architecture has been verified for several important case studies via numerical simulations based on MATLAB/Simulink domain.

grid current controller↗

Harnessing Virtual Power Plants Reliably: Enabling tools for increased observability, controllability, operation, and aggregation of distributed energy resources

Harnessing virtual power plants enhances the integration of distributed energy resources into utility grids for a sustainable energy future. Virtual power plants (VPPs) aggregate DERs to enhance resource adequacy and reduce emissions. U.S. utilities are exploring various technologies to manage DERs effectively. FERC Order 2222 allows DERs to participate in both wholesale and retail markets. Enhancing observability and controllability of behind-the-meter (BTM) DERs is essential for reliable grid operations. A hierarchical control architecture can improve coordination among residential energy resources. Field tests showed nearly 20% energy savings and 30% peak power reduction during grid events. Effective management of DERs requires enhanced situational awareness to prevent grid congestion. Integrating DER management systems (DERMS) with existing planning tools can improve operational security. Near-real-time grid models can validate optimal resource set points against resource uncertainty. Traditional uninterruptible power supplies (UPS) can be upgraded to support grid services and become part of VPPs. Upgrading UPS systems can reduce costs by 75% and unlock significant battery capacity. New battery management systems and grid-aware controllers are essential for optimizing UPS performance. Continued research and development are necessary to address challenges in integrating DERs into utility grids. Encouraging customer participation in pilot programs is vital for the evolution of VPPs. Here, the shift towards price-responsive DERs and VPPs is expected to enhance energy distribution efficiency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

EXERGETIC: De-Risking Next-Generation Resilient Geothermal Hybrids via At-Scale Evaluation Using Virtual Emulation Digital Twin Environment for Efficient Operation

The DOE-GTO-funded project, award number 5.1.2.12, entitled "EXERGETIC - De-risking Next Generation Resilient Geothermal Hybrids via at-Scale Evaluation Using a Virtual Emulation Digital Twin Environment for Efficient Operation," advances the solution to these challenges by developing and validating a geothermal co-emulation environment implemented at the National Laboratory of the Rockies (NLR)'s Advanced Research on Integrated Energy Systems (ARIES) platform. This framework enables the de-risking of next-generation geothermal and geothermal hybrid systems through high-fidelity modeling, real-time digital emulation, advanced control strategies, and techno-economic assessment. The project focused on geothermal hybrid configurations that integrate geothermal power plants with concentrated solar power and underground thermal energy storage, enabling enhanced efficiency, flexibility, and grid support capabilities. The main goal of this project was the development of a geothermal digital co-emulation environment to demonstrate the technical and economic value of geothermal hybrid systems and their contribution to grid stability and flexibility. The EXERGETIC framework combined physics-based models, controls, and real assets at ARIES, including digital real-time simulators (DRTS), a 20-MW-scale controllable grid interface (CGI), and a 2-MW conventional generator. Detailed transient models were developed for the key subsystems of a hybrid geothermal plant, including parabolic trough solar collectors, reservoir thermal energy storage (RTES), and a binary Organic Rankine Cycle (ORC) power plant. The ORC model explicitly captured thermal inertia and off-design operation and integrated control strategies to dynamically respond to electric load profiles. The models were validated against published experimental and numerical studies, demonstrating strong agreement and confirming the accuracy and robustness of the modeling approach. The resulting digital twin represents geothermal-solar-storage systems at multiple scales (1 MW to 100 MW) and enables realistic emulation of grid-connected operation. The control architecture allows the geothermal resource to provide stable baseload generation, while solar and stored thermal energy supply flexible, dispatchable support during periods of high demand or variable grid conditions. A key contribution of the EXERGETIC project is the demonstration that geothermal hybrid systems can be designed to be active grid assets rather than passive baseload generators. Using the ARIES platform, the digital twin was evaluated under multiple grid scenarios, including load following, voltage support at the distribution level, and frequency response at the transmission level. Results show that hybrid geothermal systems can respond effectively to dynamic grid conditions, providing inertia-like behavior, primary frequency support, and voltage regulation through coordinated control. In addition to the performance and grid services capability analysis of geothermal and hybrid geothermal systems, the EXERGETIC project also focused on scalability and techno-economic analysis of geothermal hybrid plants. In particular, for the scalability analysis, machine-learning (ML)-based surrogate models were trained using data generated from the geothermal digital twin under different grid-connected scenarios and plant capacities. These ML models demonstrated strong interpolation and extrapolation capabilities across plant sizes, accurately reproducing both steady-state and transient responses with very low errors. Regarding the techno-economic analysis, plant performance results were integrated with cost models for hybrid geothermal systems, and the levelized cost of electricity (LCOE) was used as the main economic metric to evaluate system performance across a range of system capacities, solar shares, solar multiples, and storage durations. Results indicate that economies of scale significantly reduce geothermal LCOE as plant capacity increases, with large-scale systems (25-100 MW) achieving substantially lower costs than small plants. Hybridization with solar thermal energy and storage further improves economic performance by increasing capacity utilization and enabling flexible dispatch. In addition, thermal storage plays a critical role in reducing LCOE by maximizing geothermal, solar, and stored energy resources. In summary, the results from this project demonstrate that geothermal hybrid systems represent a promising alternative for increasing the energy conversion efficiency of geothermal technologies, contributing to the preservation of geothermal resources, and supporting the transition of geothermal plants from traditional baseload resources into flexible, resilient, and cost-competitive energy conversion technologies.