Performance Guaranteed Inertia Emulation forDiesel-Wind System Feed Microgrid via ModelReference Control

In this paper, a model reference control based inertia emulation strategy is proposed. Desired inertia can be precisely emulated through this control strategy so that guaranteed performance is ensured. A typical frequency response model with parametrical inertia is set to be the reference model. A measurement at a specific location delivers the information of disturbance acting on the diesel-wind system to the referencemodel. The objective is for the speed of the diesel-wind system to track the reference model. Since active power variation is dominantly governed by mechanical dynamics and modes, only mechanical dynamics and states, i.e., a swing-engine-governor system plus a reduced-order wind turbine generator, are involved in the feedback control design. The controller is implemented in a three-phase diesel-wind system feed microgrid. The results show exact synthetic inertia is emulated, leading to guaranteed performance and safety bounds.

Melin, Alexander M.↗

Performance Guaranteed Inertia Emulation for Diesel-Wind System Feed Microgrid via Model Reference Control

In this paper, a model reference control based inertia emulation strategy is proposed. Desired inertia can be precisely emulated through this control strategy so that guaranteed performance is ensured. A typical frequency response model with parametrical inertia is set to be the reference model. A measurement at a specific location delivers the information of disturbance acting on the diesel-wind system to the reference model. The objective is for the speed of the diesel-wind system to track the reference model. Since active power variation is dominantly governed by mechanical dynamics and modes, only mechanical dynamics and states, i.e., a swing-engine-governor system plus a reduced-order wind turbine generator, are involved in the feedback control design. The controller is implemented in a three-phase diesel-wind system feed microgrid. The results show exact synthetic inertia is emulated, leading to guaranteed performance and safety bounds.

Zhang, Yichen↗

Robust Output Feedback Control Design for Inertia Emulation by Wind Turbine Generators

Wind generation has gained widespread use as a renewable energy source. Most wind turbines and other renewables connected to the grid through converters result in a reduction in the natural inertial response to grid frequency changes. The doubly-fed induction generator (DFIG) can be controlled to compensate for this reduction and, in fact, provide faster response than traditional synchronous machines. This paper proposes to design observer based output feedback linear quadratic regulator (LQR) and H control laws to realize the inertia emulation function and deliver fast frequency support. Furthermore, the aim is to track the reference speed by a diesel synchronous generator (DSG) in order to reach the desired inertia. The control signal is computed based on a reduced order model using the balanced truncation technique. A comparison with selective modal analysis (SMA) and balanced truncation model reduction techniques is presented. Comprehensive results show the effective emulation of synthetic inertia by implementing the control laws on a nonlinear three- phase diesel-wind system. The proposed technique is analyzed for different short circuit ratio (SCR) scenarios.

17 WIND ENERGY↗

PV Generation Enhancement with a Virtual Inertia Emulator to Provide Inertial Response to the Grid

With high-penetration levels of renewable generating sources being integrated into the existing electric power grid, conventional generators are being replaced and grid inertial response is deteriorating. This technical challenge is more severe with photovoltaic (PV) generation than with wind generation because PV generation systems cannot provide inertial response unless special countermeasures are adopted. To enhance the inertial response, this paper proposes to synthesize a virtual inertia emulator (VIE) by using a battery energy storage system (BESS) and a three-phase grid-tied inverter to simulate a traditional generator such that the inertial response can be appropriately enhanced without sacrificing energy efficiency. Control systems for the VIE are presented in this paper, along with simulation results from PSCAD and MATLAB to validate the effectiveness of the proposed scheme.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Analysis of MTDC Inertia Emulation Impact on Connected AC Systems

The frequency decoupling effect of the voltage source converter (VSC)-based high voltage dc (HVDC) transmission makes frequency support unavailable between two ac subsystems interconnected by the HVDC link. Recently, several algorithms have been proposed and demonstrated to improve the ac system stability by implementing inertia emulation (IE) functions in the HVDC VSC stations. However, the capability of the VSC-HVDC to achieve the IE control is not clear. According to the previous research, the IE control strategy has been studied without concerning the impact of the practical control process, which will introduce some time delay into the IE realization. In this paper, a detailed multi-terminal HVDC VSC control module, including the phase-locked loop (PLL) and low pass filter (LPF), is considered in order to analyze the multi-terminal HVDC network impact on the IE performance. The analysis indicates that the frequency performance of the ac network with IE integrated HVDC transmission can be nearly as good as that directly connected with the ac subsystem which involves a high penetration of conventional generation units, except for the short time delay introduced by the VSC control modules. The effectiveness of IE performance will be compromised if the response delay is significant. The simulation results have verified the analysis.

Wang, Shuyao↗

Inertia Emulation Control using Demand Response via 5G Communications

Building energy equipment is moving rapidly towards Internet of Things (IoT)-driven devices to provide consumer connectivity and device management. These device-level interfaces along with 5G communications will be leveraged to develop control architectures to engage a large number of monitoring and control devices and provide real-time and reliable energy services. Emerging 5G networks have high potential to provide the communication technology for demand response, with fast transfer speed, high reliability, and high number of connections. Guaranteed inertial response to limit frequency fluctuations is one of the main challenges in modern power systems due to the increased penetration of renewable generation, and it is largely affected by communication delays and packet losses. This paper analyzes inertial response and rate of change of frequency in a power system model with inverter-interfaced air conditioners. The control loop considers time delays and packet losses to show the need to switch to 5G networks in future smart grids.

Morovati, Samaneh↗

Model-free control for frequency response support in microgrids utilizing wind turbines

Islanded microgrids integrated with renewable energy resources bring additional challenges to the primary frequency control due to their power-electronic interfaced generations. Developing an efficient control strategy for inertia emulation and frequency response support of microgrids is becoming an important issue. Wind turbine dynamics, however, will degrade the emulated inertial and primary responses with most traditional control strategies. On the other hand, compensation methods often require the knowledge of system models at the design stage and state estimation for feedback once deployed online. To overcome these challenges, this paper explores a model-free control (MFC) strategy to emulate the desired inertia and support the frequency response of a diesel-wind microgrid system. Additionally, the proposed MFC strategy utilizes a model reference concept to obtain guaranteed inertial response and improve the frequency response of microgrids. This work considers different control strategies with different operating points. The proposed controller is implemented and verified using the modified 33-bus full nonlinear model of the three-phase diesel-wind system in Simulink. Simulation results demonstrate the improved frequency response by precisely emulating the desired inertia using the MFC strategy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Provision for Guaranteed Inertial Response in Diesel-Wind Systems via Model Reference Control

Frequency performance has been a crucial issue for islanded microgrids. On one hand, most distributed energy resources (DER) are converter-interfaced and do not inherently respond to frequency variations. On the other hand, current inertia emulation approach cannot provide guaranteed response. In this paper, a model reference control based inertia emulation strategy is proposed for the diesel-wind systems. Desired inertia can be precisely emulated through the proposed strategy. A typical frequency response model with parametric inertia is set to be the reference model. A measurement at a specific location delivers the information about the disturbance acting on the diesel-wind system to the reference model. The objective is for the speed of the diesel generator to track the reference so that the desired inertial response is realized. In addition, polytopic parameter uncertainty will be considered. The control strategy is configured in different ways according to different operating points. The parameters of the reference model are scheduled to ensure adequate frequency response under a pre-defined worst case. The controller is implemented in a nonlinear three-phase diesel-wind system fed microgrid using the Simulink software platform. Lastly, the results show exact synthetic inertia is emulated and adequate frequency response is achieved.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Design and Evaluation of a Model-Free Frequency Control Strategy in Islanded Microgrids with Power-Hardware-in-the-Loop Testing

The deterioration of inertial and primary frequency response of islanded microgrids has been a crucial issue for the proper operation of such microgrids. Several approaches, including inertia emulation strategies, have been proposed to improve the primary frequency response. However, the demonstrations of most inertia emulation research works are based on simulation-only testing which hinder their applicability in the field. In this paper, a novel model-free control (MFC) strategy for frequency response support in a diesel-wind microgrid system is presented, and it is tested for evaluation using a power-hardware-in-the-Ioop (PHIL) platform. The PHIL testing is one step closer to field testing since it allows real-time verification and accounts for the nonlinear grid dynamics, noise, and time delays that are usually ignored in simulation-only environments. The proposed MFC strategy is fully distributed, has low computational requirements, and can be easily implemented in resource constrained devices such as smart inverters. A PHIL microgrid platform consisting of two type-3 wind turbine generators and one diesel generator is used to test the proposed MFC strategy.

Ferrari Maglia, Max↗

Approximating Trajectory Constraints With Machine Learning – Microgrid Islanding With Frequency Constraints

Here, we introduce deep earning aided constraint encoding to tackle the frequency-constraint microgrid scheduling problem. The nonlinear function between system operating condition and frequency nadir is approximated by using a neural network, which admits an exact mixed-integer formulation (MIP). This formulation is then integrated with the scheduling problem to encode the frequency constraint. With the stronger representation power of the neural network, the resulting commands can ensure adequate frequency response in a realistic setting in addition to islanding success. The proposed method is validated on a modified 33-node system. Successful islanding with a secure response is simulated under the scheduled commands using a detailed three-phase model in Simulink. The advantages of our model are particularly remarkable when the inertia emulation functions from wind turbine generators are considered.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distributed Frequency Divider for Power System Bus Frequency Online Estimation Considering Virtual Inertia From DFIGs

In this work, a distributed frequency divider is proposed to estimate power system bus frequency with a limited number of PMUs while considering the inertial contributions from double-fed induction generators (DFIGs). The key idea is to reformulate the original frequency divider by modeling the contributions of DFIGs with inertia emulation and external regional power system through Thevenin equivalents. The distributed frequency divider is general and able to estimate local bus frequencies in a distributed manner. Besides, only the knowledge of the rotor speeds of synchronous generator, boundary bus frequencies and terminal bus frequencies of DFIGs as well as the admittance matrix are required to estimate the frequencies at all buses. This is drastically different from existing approaches that require system observability by PMUs to monitor all bus frequencies. Numerical results carried out on the IEEE 39-bus and modified 118-bus power systems with DFIGs demonstrate and effectiveness and robustness of the proposed method.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Parametric Comparative Analysis between Virtual Synchronous Generator and Droop-based Inertia for Inverter-Based Microgrids

This paper presents a parametric comparative analysis between the virtual synchronous generator (VSG) method and the droop control method to emulate inertia in the voltage-source inverter (VSI). Droop controllers are commonly used to regulate sharing power in microgrids and distribute power generation proportionally among VSI’s depending on their rated power. Additionally, VSG has been used to regulate the Rate-of-Change-of-Frequency (RoCoF) of the microgrid using virtual inertia. Although both methods can be used to regulate the frequency variation, the influence of each method on the closed loop eigenvalues is not the same. In this work, the transient response of the frequency is analyzed for each method to determine their advantages and disadvantages regarding frequency regulation in microgrid applications. The results were verified by conducting experimental trials using VSI’s. These experiments demonstrated that VSG is more suitable for regulating RoCoF and frequency nadir than droop controllers since it provides inertial support and improves frequency response.

Campo-Ossa, Daniel D.↗

Frequency support comparison for vanadium and lithium-ion BESSs using a converter-based grid emulator

Battery energy storage systems (BESSs) are commonly used for frequency support services in power systems because they have fast response times and can frequently inject and absorb active power. Lithium-ion (Li-ion) BESSs dominate the grid energy storage market now, but Vanadium redox flow (VRB) BESSs are predicted to contend in future markets for large-scale storage systems. Previously, a Li-ion BESS emulator has been developed for a grid emulation system known as the Hardware Testbed (HTB), which consists of converters controlled to emulate different power system components. In this paper, we develop a VRB BESS emulator with a VRB-specific internal battery model and a power electronics interface similar to that of the Li-ion BESS emulator. Then, we compare the effectiveness of the VRB and Li-ion technologies for primary frequency regulation and inertia emulation applications. It is concluded that these two technologies are virtually indistinguishable from the power system's perspective when conducting these services over a short period of time.

Boles, Jessica↗

Coordinated frequency regulation among asynchronous AC grids with an MTDC system

With the increasing penetration level of renewable power, the power systems’ inertias are decreasing. To ensure that the frequency is above the threshold of the under frequency load shedding, one effective way is to share the spinning reserves among asynchronous AC grids through HVDC systems. In this paper, a coordinated frequency regulation scheme that enables spinning reserves sharing is proposed for such hybrid AC/DC grids. This scheme is a communication-free method that consists of the droop control, the inertia emulation control and the frequency safety control. The combined response of the three controls can increase not only the frequency nadir but also the settled frequency of the disturbed grid. In addition, the hysteresis comparators and the power injection limits are adopted in the frequency regulation scheme to reduce the coupling effect among AC grids. Thus, under small and harmless disturbance, the frequency regulation scheme will be inactive; the disturbance in strong AC grids would not affect the weak AC systems. The frequency regulation scheme coordinates well with the automatic generation control of the grids. Furthermore, the feasibility and effectiveness of the proposed frequency regulation scheme are verified through simulation studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Enhancing Power System Transient Stability by Virtual Synchronous Generator Control Using Wide-Area Measurements

Virtual synchronous generator control provides a potential solution to connect power electronics interfaced sources to the power system. With its flexible control, the emulated inertia may be adaptively changed to enhance system small-signal stability. However, previously proposed methods may have adverse impact to system transient stability. This paper proposes to improve the methods by using wide-area measurements, namely center of inertia frequency. Experimental results are presented to both demonstrate the limitations of previous control schemes, and the effectiveness of the proposed one. The practical implementation of this method is discussed.

Ma, Yiwei↗

Rapid Active Power Control of Photovoltaic Systems for Grid Frequency Support

As deployment of power electronic coupled generation such as photovoltaic (PV) systems increases, grid operators have shown increasing interest in calling on inverter-coupled generation to help mitigate frequency contingency events by rapidly surging active power into the grid. When responding to contingency events, the faster the active power is provided, the more effective it may be for arresting the frequency event. This paper proposes a predictive PV inverter control method for very fast and accurate control of active power. This rapid active power control method will increase the effectiveness of various higher-level controls designed to mitigate grid frequency contingency events, including fast power-frequency droop, inertia emulation, and fast frequency response, without the need for energy storage. The rapid active power control method, coupled with a maximum power point estimation method, is implemented in a prototype PV inverter connected to a PV array. The prototype inverter's response to various frequency events is experimentally confirmed to be fast (beginning within 2 line cycles and completing within 4.5 line cycles of a severe test event) and accurate (below 2% steady-state error).

14 SOLAR ENERGY↗

Power system inertia estimation: Review of methods and the impacts of converter-interfaced generations

Understanding and quantifying the inertia of power systems with the integration of converter-interfaced generation (CIG) plays an essential role in the safe transition to a future low-inertia scenario. Here we provide a comprehensive summary of inertia definitions for both synchronous generators and CIGs as well as their corresponding estimation methods. In particular, the estimation methods are categorized as model-based and measurement-based approaches considering both small and large disturbances. The advantages and disadvantages of different methods are carefully discussed. This paper also offers for the first time a framework to quantify the virtual inertia of CIGs at the component and aggregation levels, an open problem in the literature. Finally, future directions for inertia estimation are identified and discussed. This significantly benefits the design of appropriate control and protection schemes in achieving a more reliable, secure, and resilient power system.

42 ENGINEERING↗

Leveraging National Laboratory Assets to Address Stability Challenges due to Declining Grid Inertia Using Geographically Distributed Electrical–Thermal Co-Emulation

Due to increased penetration of low-inertia resources into the electric grid, challenges are increasing for maintaining wide-area system stability. Grid stability assessment requires a faithful representation of the multiple-physics interaction at the system level, and timescales of interaction varying in orders of magnitude, from microseconds to seconds to several minutes. Along with the simulation-based techniques, hardware-in-the-loop (HIL), controller HIL, and power HIL techniques have been developed to better understand the emergent behavior of the system with emerging technologies. US National Laboratories have played a vital role in research and development to understand the behavior of individual technologies and devices integrated to the electric grid. Each national laboratory forwards a technological and strategic initiative tied core and enabling capabilities. Due to strategic, efficiency, and economic reasons, not all the labs have assets to conduct research on all technologies concomitantly, so it becomes crucial to integrate the labs across geographies to understand the interplay of different technologies together at the system level. This approach avoids duplication of the assets at different lab facilities and helps understand the integrated system behavior of various technologies representative of actual grid conditions by connecting multiple national labs. This article talks about techniques of connecting three national laboratories to enable co-emulation of electrical–mechanical–thermal characteristics of devices and systems. Such an approach can be used to understand the dynamic and transient interaction of multi-physics in a system level, at-scale emulation using real-time simulation tools and techniques.

24 POWER TRANSMISSION AND DISTRIBUTION↗