Use of Grid-Forming Medium-Voltage Power Electronics Hub in a Microgrid Setting

This paper presents the application of a new design of a multiport, modular, medium-voltage power electronics hub (M3PE-HUB) in a microgrid setting. The M3PE-HUB system was modeled in a digital real-time simulator (DRTS) and integrated into the Banshee microgrid test system. This paper presents the preliminary DRTS simulation-based results of the M3PE-HUB system connected in a test microgrid system. Verification and validation of the M3PE-HUB architecture and controls in the test microgrid setting are the primary contributions of this work. The results of the operation during the islanding and resynchronization process indicate the feasibility of the proposed architecture in a microgrid setting. This paper also presents results for a system reconfiguration use case where the M3PE-HUB was used to reconfigure the system under a fault condition.

grid forming↗

Guest Editorial Special Section on Advanced Medium-Voltage Power Electronics for Grid Interactive Applications

Medium-voltage power electronics (MVPE) plays essential roles in power grid modernization and links the MV distribution grid with low-voltage consumers and prosumers. Various MVPE devices, such as solid-state transformers or circuit breakers, inverter-based resources, power flow controllers, etc., bring the benefits of voltage conversion and power regulation in small footprint, power quality and efficiency improvements, and enhancements of grid controllability, flexibility, stability, and resilience. The MVPE also makes it possible for sustainable energy systems, such as solar/wind farms and energy storage generating facilities, to directly access to MV grids without multistage conversions. With their intrinsic intelligence and communications, MVPE enables many new smart grid functions and applications, e.g., dc interconnections and electric vehicle charging, which were not envisioned by traditional power grids otherwise. In addition, the integration of physical power processing units with cyber components forms a cyber-physical system, which is essential for long-term sustainability, development, and environmental preservation. Nonetheless, technical challenges on MVPE device reliability, scalable and efficient converter topologies, control stability, large-scale modeling and simulation, to name a few, need to be addressed and advanced to the next level. In conclusion, this Special Section on Advanced MV Power Electronics for Grid Interactive Applications in IEEE Transactions on Power Electronics (TPEL) provides an insight on some of the recent advances in MVPE and emerging challenges and potential solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Use of Grid-Forming Medium-Voltage Power Electronics Hub in a Microgrid Setting: Preprint

This paper presents the application of a new design of a multiport, modular, medium-voltage power electronics hub (M3PE-HUB) in a microgrid setting. The M3PE-HUB system was modeled in a digital real-time simulator (DRTS) and integrated into the Banshee microgrid test system. This paper presents the preliminary DRTS simulation-based results of the M3PE- HUB system connected in a test microgrid system. Verification and validation of the M3PE-HUB architecture and controls in the test microgrid setting are the primary contributions of this work. The results of the operation during the islanding and resynchronization process indicate the feasibility of the proposed architecture in a microgrid setting. This paper also presents results for a system reconfiguration use case where the M3PE- HUB was used to reconfigure the system under a fault condition.

grid forming↗

Medium Voltage Power Electronics Enabling DER and Increasing Climate Resiliency

As renewables grow to meet both increased decarbonization and electrification goals, functionality such as grid-forming capability needs to be developed. Medium-voltage power electronic-enabled interfaces for renewables and as new devices within the grid themselves are an ideal platform for implementing these functionalities.

decarbonization↗

Benefits of high-voltage SiC-based power electronics in medium-voltage power-distribution grids

Medium-voltage (MV) power electronics equipment has been increasingly applied in distribution grids, and high-voltage (HV) silicon carbide (SiC) power semiconductors have attracted considerable attention in recent years. This paper first overviews the development and status of HV SiC power semiconductors. Then, MV power-converter applications in distribution grids are summarized and the benefits of HV SiC in these applications are presented. Microgrids, including conventional and asynchronous microgrids, that can fully demonstrate the benefits of HV SiC power semiconductors are selected to investigate the benefits of HV SiC in detail, including converter-level benefits and system-level benefits. Finally, an asynchronous microgrid power-conditioning system (PCS) prototype using a 10 kV SiC MOSFET is presented.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Control of Grid-Connected Multiport MV Power Electronics Energy Hub: Preprint

In this paper a new concept of multiport modular medium-voltage power electronics hub (M3PE-HUB) is introduced for future power grid. The goal for this project is to design, develop, and demonstrate foundational technologies and capabilities for multiport power electronics energy hubs that can serve as intelligent devices to coordinate and control several different sources and loads. In this paper, the architecture of the controller, the central controls, and its verification is presented.

controls↗

Thermal Modeling and Limitations for Power Electronics Embedded in Medium-Voltage Cables

As next-generation energy technologies gain traction and power demand increases, the existing electrical infrastructure faces significant stress, prompting innovative solutions to enhance the grid's capacity and lifespan. This work explores the possibility of embedding medium-voltage (MV) power electronics directly inline with the cable, and the resulting thermal challenges. Since the majority of power distribution cables installed in the U.S. are passively cooled, the work focuses primarily on passive cooling, with an emphasis on the limitations of axial heat spreading within the cable. To date, literature on axial spreading of high incident heat loads on cables and cable environments is limited, typically reporting cases with <10 W of incident heat load. This work will explore the considerations, limits, and tradeoffs of cable-embedded heat loads significantly larger than the cable losses. Both external and internal effects are modeled analytically in nondimensional terms via a Biot number analysis, allowing fundamental limits and tradeoffs to be derived. The work culminates in the design and experimental validation of a cable-embedded thermal system capable of passively dissipating 300 W of heat from a coaxial SiC mosfet switch module over a length of 20 cm, thus validating the possibility of MV cable-embedded power electronics from a thermal standpoint.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Enhancement-Mode GaN Monolithic Bidirectional Switch With Breakdown Voltage Over 3.3 kV

Here, this work demonstrates a GaN enhancement-mode monolithic bidirectional switch (MBDS) with breakdown voltage (BV) higher than 3.3 kV in both polarities. This MBDS is realized on a dual p-GaN gate high electron mobility transistor (HEMT) platform on sapphire substrate. It features a novel dual junction termination extension design for electric field management, which is built on the p-GaN layer in the gate stack and does not require epitaxial regrowth. The GaN MBDS exhibits symmetric on-state characteristics in both directions with a threshold voltage (V th ) of 0.6 V and a low specific on-resistance (R on,sp ) of 5.6 m Ω · cm2. This device presents the highest BV, as well as one of the best BV and R on,sp trade-offs, in all the reported MBDS devices. The R on,sp is lower than the performance limit of conventional BDS realized by two discrete devices. This 3.3 kV GaN MBDS opens the door for developing new circuit topologies and advancing system performance in medium-voltage power electronics.

42 ENGINEERING↗

Modular Coaxial Power Converter for High-Density Integration into Medium-Voltage Cables

This work proposes to combine the functionality benefits of power electronics with the power density benefits of medium-voltage cables to create a streamlined, high-density power electronics solution that seamlessly integrates with medium-voltage cables. Located at the ends of a medium- or high-voltage line, the proposed converter uses a cascade of coaxial power conversion cells to gradually step down the voltage, and excels in high step-down applications. By mimicking the coaxial geometry of medium-voltage cables, the converter preserves the axisymmetric electric field of the cable which, when combined with a solid insulating dielectric, provides a voltage scaling advantage over conventional planar and PCB-based converter solutions. Similar to medium voltage cables, the converter is fully passively cooled. A passive cooling strategy allows for combined installation with existing medium voltage cable systems without the added cost, maintenance needs, infrastructure, and reliability concerns associated with active cooling systems. The scalability of the modular structure in combination with the integration benefits provide a flexible power electronics system that can adapt to the evolving demands of the grid.

coaxial power conversion cells↗

Power Electronics as an Enabler of the Current and Future Grid: Control Instead of Copper

Power electronics are becoming more pervasive in the power system. Solar, wind and battery energy storage systems regularly connect to the grid using power electronic interfaces. Loads are also increasingly power electronic-based. These changes, coupled with the change in the power system's operating characteristics as more and more renewable energy is integrated into the power system, offer a challenge to power electronic and power system engineers alike - how do we design and operate the power system moving forward?

direct connect↗

ARC-SAFE: Accelerated Response semiconducting Contactors and Surge Attenuation For DC Electrical systems (Final Scientific/Technical Report)

The landscape of power transmission and distribution is quickly evolving as more power conversion is done through power electronics and transmitted or distributed at medium voltage direct current (MVDC). As power electronics tend to store less energy and be less resilient to faults than conventional power transformers, a reliable and fast protection against faults is critical to protect power electronics (PE) based infrastructure, especially for medium- and high-voltage applications. This motivates the development of PE based protection circuits to replace slower contemporary electromechanical breakers. In this project a novel PE based MVDC circuit breaker is developed; the new design is comprised of 1) a normally-on leg made of commercially-available, cascaded SiC junction field effect transistors (JFETs) with a passive balancing network, and 2) a normally-off leg based on an optically-triggered gallium nitride (GaN) photoconductive semiconductor switch (PCSS). The normally-off leg was designed to be quickly turned on, to divert current to an auxiliary dissipative circuit, as the normally-on leg is turned off. This approach, using solid-state devices, was selected for a high-performance, fast-switching operation for the DC circuit breaker as compared to approaches that use slower mechanical switches. To be practical, the circuit breaker must have low conduction loss (low Ron) in the normally-on leg and fast coordinated triggering of the normally-off leg to avoid damage from inductive flyback, which could be considerable for long lengths of cable.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Control, Fault Management, and Grid Support Functionality of an MV AC-DC Solid State Transformer based EV Extreme Fast Charging Station

Electric vehicles (EVs) have become increasingly popular in recent times while revolutionizing the consumer and commercial transportation market. The development of charging infrastructure has become one of the priorities for increasing the adoption of EVs. Extreme fast charging (XFC) technology can reduce the so-called ’range anxiety’ of consumers as they significantly reduce the charging time. With the advent of wide band-gap (WBG) power devices and improvement in power electronic converters, medium voltage (MV) solid state transformer (SST) based XFC system has the potential to replace the traditional XFC stations because of the lower footprint, ease of installation, enhanced control feature, and better system efficiency. The control system design is one of the critical aspects of the SST development process. Careful consideration and detailed analysis are required to find out suitable control method for the SST based on its topology among different centralized and decentralized control architectures. Also, the control parameters selection and potential improvement to the transient response of the controller ought to be investigated. Another major concern of the SST is different types of internal fault which reduces the overall reliability of the XFC system. As a result, designing a robust protection system is essential. Among different fault modes, open circuit switch faults have received significant attention as an active research area because of their likelihood and severe effects on converters. Therefore, the power stages used in the XFC system require functional and accurate open circuit switch fault management methods. An equally significant aspect of this SST based XFC is its compatibility in a microgrid where there is no synchronous generator present. When the grid is not available, the XFC SSTs can provide grid forming capability and continue supplying the critical loads in islanded mode. The transition between grid connected and islanded mode, especially the grid resynchronization process has to be carefully performed for the safety of the microgrid components. The challenges posed by the aforementioned issues have inspired the work done in this dissertation. Here, a 13.2 kV, 1 MVA, AC/DC SST for the XFC system is examined and a comparative analysis is conducted to select the control architecture based on feasibility of implementation and performance. A detailed control parameter design process is demonstrated considering the sensor dynamics and delay. The selected decentralized control method is augmented by introducing a novel sensor-less load current feedforward method to provide better voltage regulation at the DC bus during a change of load. Next, in the fault management section, a hierarchical failure mode effect analysis (FMEA) is proposed to enable a systematic design of the internal fault protection of the XFC SST as there are limited examples in the literature regarding the analysis of the safety and design of the protection of a power electronic converter system. Novel open circuit switch fault management methods for the converters in the system are presented. Finally, XFC SST based MV microgrid operations in grid connected mode and islanded mode are explored. A secondary control method for grid resynchronization is presented and a design process of control parameters is shown to ensure the stability of the secondary voltage and frequency regulation.

30 DIRECT ENERGY CONVERSION↗

Thermal Design Consideration of Medium Voltage High Frequency Transformers

This paper describes a thermal design using epoxy potting for high frequency transformer (HFT) for medium voltage high power electronic applications, namely emerging solid-state transformers. To address HFT’s thermal stress problem, thermal performance of the HFT with air and epoxy potting cooling method are both simulated by magnetothermal-fluid coupling method (MTFCM). The effectiveness of the simulation analysis is verified in a 100 kW DC-DC resonant converter. Influencing factors including distance between the high frequency transformer and the metal enclosure, epoxy thermal conductivity and heat sink placements are simulated and analyzed. Finally, an optimal cooling structure is proposed for future high power HFTs.

Wang, Haoming↗

New Modulation and Impact of Transformer Leakage Inductance on Current-Source Solid-State Transformer

This article presents a novel modulation scheme for device voltage stress mitigation and comprehensive analysis of the impact of transformer leakage inductance in a current-source solid-state transformer (SST). Different from dual active bridge (DAB) SST, the operation of the current-source SST is similar to that of a flyback converter. The device bridge on only one side of the transformer is active to store energy into or release energy from the magnetizing inductance which acts as a current-source dc link. Such flyback operation with reverse-blocking switches can lead to additional device voltage stress and incomplete zero-voltage switching (ZVS) on the current-source soft-switching solid-state transformer (S4T) under conventional modulation. A new modulation scheme is proposed to address this issue. Moreover, different from the DAB, the leakage inductance of the medium-frequency transformer (MFT) in the S4T is a parasitic element similar to that in a matrix SST and can cause additional device voltage stress. Though the resonant capacitors, originally added to achieve ZVS, can absorb and recycle the leakage energy in the S4T, these capacitors need to be increased with larger leakage inductances to limit the voltage stress. However, large resonant capacitors can result in more lost duty cycles and reduced efficiency. The impact of such leakage inductance on device voltage stress is analyzed comprehensively, which is critical to guide future research and design of the S4T. Experimental results from S4T prototypes for DC-DC, multiport AC-DC, and AC-AC conversion with 1:1 and 4:1 MFT comprehensively verify the proposed concepts. Lastly, a case study of a three-phase AC-AC S4T over a power range from 1 kVA to 100 kVA each module reveals that the MFT leakage inductance should be less than 1% of the magnetizing inductance for safe operation.