Search NASA⌕ Search

SEARCH · Search NASA

Results for “microgrid protection”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Real-Time Model-Adaptive Relaying Applied to Microgrid Protection

In microgrids, the short-circuit current magnitude is significantly limited by more than an order of magnitude due to the relatively small inverter-based resources. Commercially available protective devices for distribution cannot reliably protect a microgrid due to their dependence on the magnitude of the fault current. Moreover, overcurrent relays typically cannot function properly for a microgrid because they are incapable of detecting faults and/or performing the coordination between the relays in inverter-based microgrids operated in the islanded mode. This paper proposes a model-adaptive relay designed to adjust the relay curves based on the available generation and the network topology. The proposed method runs a real-time model of the microgrid, which gathers information from the network to calculate the available short-circuit current in the specified node. The fault current from the model is then used for the adaptive algorithm to calculate the relay settings, considering coordination with the downstream fuses and upstream reclosers. This work presents the validation of the proposed method in Hardware-in-the-Loop, in a hardware testbed as well as field deployed in a real microgrid in East-Tennessee.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Influence of Inverter-Based Resources on Microgrid Protection: Part 1: Microgrids in Radial Distribution Systems

Microgrids are being deployed at a rising rate, primarily as a means of increasing power system resilience. Commonly, a microgrid today includes at least some inverter-based resources (IBRs), and many microgrids have modes or conditions under which they are entirely energized by IBRs. Also, most microgrids today are deployed on radial distribution circuits, but it is conceivable that they could also be considered for deployment on secondary network systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid Forming Inverter With Increased Short-Circuit Contribution to Address Inverter-Based Microgrid Protection Challenges

Substantial differences in fault levels between grid-tied and islanded modes is one of the primary challenges of microgrid protection. During grid-tied mode, the bulk grid provides significant short-circuit, while during islanded operation the short-circuit magnitude is small due to inverter-based resources limiting their current output close to nominal ratings. Consequently, conventional distribution protection strategies based on overcurrent cannot reliably protect microgrids when operating in islanded mode. Fuses and circuit breakers are particularly affected because of their inverse characteristics. Presently, the absence of affordable solutions for protecting microgrids in islanded mode leads to microgrids shutting down during electrical faults. The contribution of this article is two-fold. The first innovation proposes specific hardware modifications to grid-forming inverters to increase their short-circuit current during electrical faults. The second innovation introduces a novel control strategy designed to preserve control stability margins even when the grid-filter saturates, ensuring sinusoidal output currents under normal and fault conditions. Through experimental results, the inverter with the proposed modifications can provide more than three-times its nominal current during electrical faults. For the prototype testbed, this was sufficient to enable the use of traditional legacy overcurrent protection, achieving the fuse-to-relay and relay-to-relay minimum coordination time for the line-to-ground, line-to-line to ground, and three-phase electrical faults.

42 ENGINEERING↗

End-to-end microgrid protection using distributed data-driven methods

This paper introduces an end-to-end microgrid protection framework that offers real-time system monitoring, fault-related decision making, and circuit breaker control. This is achieved through the design of distributed data-driven techniques based on the support vector machine method, where each relay is responsible for distributed data collection, fault detection, fault localization, and fault isolation. Local communication is established among neighboring relays, fostering cooperative fault localization and isolation. This decentralized design not only reduces the computational and communication requirements but also enables the adaptability of each relay under varying operational dynamics. The proposed end-to-end protection framework was validated using MATLAB/Simulink simulations on a 100% renewable microgrid, achieving an accuracy of 93.1% with response time of 0.0523 s, in protecting against a range of fault scenarios that are characterized by various types, locations, impedances, load conditions, photovoltaic power levels, and microgrid operating modes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Decentralized Microgrid Protection Through Relative Fault Direction Classification: Preprint

Protection in inverter-based resources (IBRs) dominated microgrids generally face significant challenges due to the low fault current and inconsistent fault behaviors from IBRs. Recently, machine learning-based approaches have attracted considerable attention to address these challenges. This paper introduces a novel decentralized protection strategy for microgrids. The proposed method decomposes the protection challenge into several distributed learning tasks, enabling individual relays to autonomously determine the direction of faults using a binary classification framework based on support vector machine (SVM) algorithms. Following the distributed fault direction estimation, classifier outcomes are shared among neighboring relays, facilitating a local decision-making process to ascertain the presence of faults within the neighborhood. Finally, a tripping signal is generated based on the classifier results of each relay to operate the circuit breaker. To test and validate this approach, a 100% renewable microgrid model is simulated in MATLAB/Simulink. In the numerical analysis, the application of SVM classifiers in our approach yields impressive results: an average relay classification accuracy of 98%, and a 96% accuracy in circuit breaker control. These findings highlight the potential of machine-learning-based approaches in enhancing the efficiency and reliability of microgrid protection systems.

decentralized algorithm↗

IoT-Enabled Traveling Wave Microgrid Protection

Traveling Wave Protection based on the Internet of Things (TWP-IoT) is developed to enable ultra-resilient microgrids. TWP-IoT adopts a directional traveling wave approach that utilizes the voltage and current modal components obtained from Discrete Hilbert Transform to identify the fault features via ultra-lightweight IoT hardware. Furthermore, the main contributions of this work include (1) a novel TWP-IoT for microgrid and distribution networks that can achieve the time-of-arrival fault detection and localization with composite wave impedance and conductance using Discrete Hilbert Transform, (2) a cost-effective smart IoT prototype with functionalities outperforming commercial relays, and (3) a real-time hardware-in-the-loop prototype based on RTDS that verifies the robustness and efficacy of TWP-IoT subject to a diverse set of working conditions. TWP-IoT is found to have excellent performance under a wide spectrum of internal and external fault conditions across a myriad of microgrid locations, which is unattainable by today’s TWP products.

24 POWER TRANSMISSION AND DISTRIBUTION↗

AI-enabled traveling wave protection for microgrids

Grid forming inverters provide voltage and frequency regulations for microgrids; in the meantime, new challenges are introduced for microgrid protections. For instance, inverters’ control strategies can affect protection behaviors, and low short-circuit ratios and bi-directional power flows also make protection operations complex. Protection schemes based on conventional principles such as overcurrent and distance relays do not always provide reliable, sensitive, or selective operations. Here, we devise a traveling wave protection approach for microgrids using a wavelet-driven deep neural network named WaveletKernelNet (WKN). Compared with conventional methods, the presented approach provides enhanced sensitivity, higher selectivity, and better identification of various faults in microgrids. Extensive case studies validate the efficacy and excellent performance of the devised approach.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Topology-Agnostic, Scalable, Self-Healing, and Cost-Aware Protection of Microgrids

Most microgrid protection schemes found in published literature suffer from a lack of generality in that they work well for the assumed topology, including type and placement of sources. Other generic protection schemes tend to be too complicated, too expensive, or both. To overcome these draw- backs, a topology-agnostic, scalable, and cost-aware protection based on fundamental principles that work in the presence of high penetration of inverter-based resources (IBRs) is developed and tested in this paper. Here, the protection system also implements stable automatic reconfiguration of the healthy sections of the system after clearance of fault, thus increasing resilience by self- healing. To achieve this ambitious goal, stable inverter models are developed that operate in unbalanced networks in grid-connected and islanded modes, even with 100% IBRs, share power without conflicting controls, and can ride through faults while limiting fault currents. The scheme is tested for primary and backup protection and reconfiguration on the IEEE 123-node feeder in grid-connected and islanded modes with 15 IBRs connected to the system.

42 ENGINEERING↗

Hierarchical Data-Driven Protection for Microgrid with 100% Renewable Penetration: Preprint

The accurate detection and isolation of faults is critical for the reliable operation of microgrids (MGs). Traditional protection approaches are even more challenged for 100% renewable MGs because inverter-based resources (IBRs) are the only sources for fault current which are usually low and unpredictable/non-uniform. This calls for new protection scheme that can identify IBR fault responses and detect faults in MGs. Data-driven based protection can learn the pattern of IBR fault responses and make the correct decision to identify faults. Therefore, this paper presents a data-driven approach for fault localization in island MGs. The approach builds a training dataset of comprehensive fault scenarios that can be used to learn fault characteristics from processed measurements. The localization task is modeled as a binary classification problem at each relay, which simplifies the learning process. Then, a hierarchical decision mechanism is used to identify the fault location. The proposed approach is assessed using an exemplary MG with several grid-forming (GFM) and grid-following (GFL) inverters, where accurate estimation of fault location is achieved. The data-driven based protection approach developed in this paper provides a generic framework and useful guidance for power system protection engineers to achieve reliable protection for MGs with 100% renewables.

artificial intelligence↗

Inverter Design with High Short-Circuit Fault Current Contribution to Enable Legacy Overcurrent Protection for Islanded Microgrids

The resiliency offered by a microgrid may be lost if the microgrid is not properly protected during short-circuit faults inside its boundaries. Many studies conclude that protecting microgrids in islanded mode is very challenging due to the limited short-circuit capability of distributed energy resources (DERs). The limited short-circuit capability of DERs typically inhibits the use of reliable and affordable overcurrent protective devices in microgrids. Although extensive research on microgrid protection is available in the literature, to date this research has not led to a cost-effective, commercially available relay that effectively tackles the challenges of microgrid protection. This work proposes hardware modifications to enhance the current contribution of an energy storage inverter with the objective of enabling the use of legacy overcurrent protection for islanded microgrids. This paper demonstrates through experimental results that few modifications are required in the inverter to significantly enhance its current contribution. In this study, a three-phase energy storage inverter was modified to provide three times its rated current during three-phase faults, which proved sufficient current for enough time to enable fuse-relay, and relay-to-relay coordination. The proposed modifications effectively increase the current contribution of the inverter, which is a promising advancement to allow the adoption of overcurrent protective devices for protecting microgrids.

Ferrari Maglia, Max↗

2022 Peer Review Project Summary: Advanced Protection for Microgrids and DER in Secondary Networks and Meshed Distribution Systems

Although there are increasing numbers of distributed energy resources (DERs) and microgrids being deployed, current IEEE and utility standards generally strictly limit their interconnection inside secondary networks. Secondary networks are low-voltage meshed (non-radial) distribution systems that create redundancy in the path from the main grid source to each load. This redundancy provides a high level of immunity to disruptions in the distribution system, and thus extremely high reliability of electric power service. There are two main types of secondary networks, called grid and spot secondary networks, both of which are used worldwide. In the future, primary networks in distribution systems that might include looped or meshed distribution systems at the primary-voltage (mediumvoltage) level may also become common as a means for improving distribution reliability and resilience. The objective of this multiyear project is to increase the adoption of microgrids in secondary networks and meshed distribution systems by developing novel protection schemes that allow for safe reliable operation of DERs in secondary networks. We will address these challenges by working with the appropriate stakeholders of secondary network operators, protection vendors, and standards committee. The outcomes of this project include: a) development and/or demonstration of candidate methods for enabling protection of secondary networks containing high levels of DER; b) development of modeling and testing tools for protection systems designed for use with secondary networks including DERs; and c) development of new industrial partnerships to facilitate widespread results dissemination and eventual commercialization of results as appropriate.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Advanced Protection for Microgrids and DER in Secondary Networks and Meshed Distribution Systems

Although there are increasing numbers of distributed energy resources (DERs) and microgrids being deployed, current IEEE and utility standards generally strictly limit their interconnection inside secondary networks. Secondary networks are low-voltage meshed (non-radial) distribution systems that create redundancy in the path from the main grid source to each load. This redundancy provides a high level of immunity to disruptions in the distribution system, and thus extremely high reliability of electric power service. There are two main types of secondary networks, called grid and spot secondary networks, both of which are used worldwide. In the future, primary networks in distribution systems that might include looped or meshed distribution systems at the primary-voltage (medium-voltage) level may also become common as a means for improving distribution reliability and resilience.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Digital Grid Twin–Direct Communication Scheme Test Bed for Assessing Relay-to-Relay Radio Antenna and Optical Fiber Performance and Misoperations

This study introduces a novel “Digital Grid Twin–Direct Communication Scheme” test bed. This advanced platform evaluates point-to-point communication between transmitter and receiver relays with optical fiber and radio omnidirectional antenna systems, implemented at the Advanced Protection lab in the Grid Research Innovation and Development Center at Oak Ridge National Laboratory. The increased diversity of energy sources has led to more protective relay misoperations. In North America, microgrid protection schemes now use point-to-point communication along distribution lines between relays to implement advanced logic in nonradial grids that include both high- and low-inertia generators. This trend challenges utilities to minimize misoperations while ensuring rapid fault clearance and accurate selectivity coordination between primary and backup relays. This study assesses relay-to-relay communication schemes by introducing an advanced testing platform based on a digital grid twin protection test bed using a synchronized time source system. The platform evaluates the communication system using radio antennas or optical fiber links by integrating protective relays that operate breakers within the digital twin and record relay events and communication signals. In the experiments, transmitter and receiver relays were configured with inverse time overcurrent and breaker trip detection logic to assess the total time of the communication protection schemes based on the sum of the relay protection element operating time, radio latency, propagation delay, baud rate delay, and relay processing time. These delays were derived from recorded relay events and communication signals from the interface of a real-time simulator set as a digital grid twin. The test bed successfully simulated various electrical faults along a distribution line while ensuring effective and reliable point-to-point communication between transmitter and receiver relays. The radio antenna communication system exhibited latency because of the radio. This latency depends on the baud rate setting and type of radio application; in general, the higher the baud rate, the lower the radio latency. The measured radio latency (for Mirrored Bits with an encryption card at 9,600 bps) was about 9–10 ms. Additionally, calculated propagation delay per mile for radio antennas and optical fiber was 5.36 µs/mi and 8.04 µs/mi, respectively. Optical fiber communication did not demonstrate radio latency. Instead, the protection element operating time depends mainly on the protection logic function set in the relay, and the relay processing time depends on the processing rate of the relay in samples per power system cycle.

24 POWER TRANSMISSION AND DISTRIBUTION↗