Loss Minimization With Optimal Power Dispatch in Multi-Frequency HVac Power Systems

Low-frequency high-voltage ac transmission scheme has recently been proposed as an alternative approach for bulk power transmission. This paper proposes a multi-period optimal power flow (OPF) for a multi-frequency HVac transmission system that interconnects both conventional 50/60-Hz and low-frequency grids using back-to-back converters with a centralized control scheme. The OPF objective is to minimize system losses by determining the optimal dispatch for generators, shunt capacitors, and converters. The OPF constraints include the operational constraints of all HVac grid and converter stations. The resulting mixed-integer nonlinear programing problem is solved using a proposed framework based on the predictor-corrector primal-dual interior-point method. The proposed OPF formulation and solution approach are verified using a multi-frequency HVac transmission system that is modified from the IEEE 57-bus system. Here, the results with the optimal dispatch from the proposed method during a simulated day show a significant loss reduction and an improved voltage regulation compared to those when an arbitrary dispatch is chosen.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Optimal Planning and Operation of Multi-Frequency HVac Transmission Systems

Low-frequency high-voltage alternating-current (LF-HVac) transmission scheme has been recently proposed as an alternative solution to conventional 50/60-Hz HVac and high-voltage direct-current (HVdc) schemes for bulk power transfer. This paper proposes an optimal planning and operation for loss minimization in a multi-frequency HVac transmission system. In such a system, conventional HVac and LF-HVac grids are interconnected using back-to-back (BTB) converters. The dependence of system MW losses on converter dispatch as well as the operating voltage and frequency in the LF-HVac is discussed and compared with that of HVdc transmission. Based on the results of the loss analysis, multi-objective optimization formulations for both planning and operation stages are proposed. The planning phase decides a suitable voltage level for the LF-HVac grid, while the operation phase determines the optimal operating frequency and power dispatch of BTB converters, generators, and shunt capacitors. A solution approach that effectively handles the variations of transmission line parameters with the rated voltage and operating frequency in the LF-HVac grid is proposed. The proposed solutions of the planning and operation stages are evaluated using a multi-frequency HVac system. The results show a significant loss reduction and improved voltage regulation during a 24-hour simulation.

Nguyen, Quan H.↗

SBIR Phase II Final Report - A Robust Wireless Communication System for Harsh Environments Including Nuclear Facilities

This is the Final Report for the DOE Phase II SBIR project “A Robust Wireless Communication System for Harsh Environments Including Nuclear Facilities.” The topics covered herein include technical progress made, progress against the planned milestones and deliverables, project outcomes, and a discussion on future expectations of deployment and impacts of the results of this work. In brief, all planned work for the project was successfully completed, on or ahead of schedule and on budget. The major accomplishment was the successful development of new sensor/communications systems with wideband (WB)/ultra-wideband (UWB) communications based on the software-defined-radio (SDR) technology to improve sensing and control in nuclear power plants and then a broad range of similar sensing applications. The impacts of these disciplines/focuses of this SBIR include: A new multi-frequency SDR-based architecture with WB/UWB communications integrated with sensors was developed, utilizing 310 MHz, 450 MHz, 915 MHz, and 5 GHz frequencies; Secure communications using Advanced Encryption Standard (AES) algorithm; Sensing possibilities not effectively addressed by previous technologies was addressed; and, The newly developed wireless sensor communications system can adapt its communications parameters to its operational environment for optimal performance. The performance of this system has been evaluated by systematic laboratory and field testing. The field testing was conducted at Massachusetts Institute of Technology (MIT)’s Nuclear Test Reactor, and the McClellan Nuclear center at the University of California Davis (UC Davis), as well as at Oak Ridge National Laboratory (ORNL). The success in this project resulted in DSI being awarded “The DOE’s 2018 SBIR/STTR Small Business of the Year”. This technology has attracted interest from The Rolls Royce company with ongoing discussions under NDA for potential strategic partnership between DSI and Rolls Royce in providing wireless sensor communications in nuclear facilities. Furthermore, the success of this project has attracted significant interest from the United Nations International Atomic Agency (IAEA) in Vienna, Austria, as well as other DOE and DOD offices. Currently, per request from IAEA, DOE’s office of International Safeguards has funded DSI to develop a WB/UWB wireless communication system for real-time transmission of images from IAEA’s safeguards cameras in various nuclear facilities. DSI also has received a Phase II and Phase II.5 SBIR awards from ARMY and NAVY for wireless communications capability for various DOD aircraft.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗

Extension of the Generic Multi-Frequency Modelling Method for Type 3 Wind Turbines

Reflecting potential non-linearities of converter-based systems, especially frequency and sequence couplings, is an ongoing challenge for linearized multi-frequency models. Besides, design details are required to develop such models, which either are the intellectual property of manufacturers or require experimental tests. The generic multi-frequency modelling method has been proposed to fill this gap; however, it is only developed for converter-connected systems, e.g., Type 4 Wind Turbines (WT). This paper proposes to extend the application of the generic multi-frequency modelling method for Type 3 WTs. In this way, a theory for patterns of the couplings in Type 3 WTs is proposed. Accordingly, a group of emissions and couplings are Rotor-Speed-Dependent (RSD). The RSD emissions and couplings are particular characteristics of Type 3 WTs, which should be addressed in the generic multi-frequency models. Additionally, the proposed theory is verified by unique-worldwide experimental perturbation tests on a 2 MVA Type 3 WT using a 7 MVA grid emulator. Accordingly, a limited number of RSD couplings and emissions are observed in the test results, mainly in low frequencies (below 1 kHz). Therefore, addressing the RSD couplings is practical and important to extend the generic multi-frequency modelling for Type 3 WTs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Generic Multi-Frequency Modelling of Converter-Connected Renewable Energy Generators Considering Frequency and Sequence Couplings

Frequency and sequence couplings can compromise the trustworthiness of multi-frequency models for converter-based systems. There have been effective attempts to address the couplings mainly by linearized averaged models. Only a few studies have been conducted on practical optimization of such models with enormous matrices and experimental results. This paper provides a generic theory for coupling patterns and proposes a multi-frequency modelling method to detect and address only the main couplings in the sequence domain for converter-connected renewable energy generators. The proposed generic model is based on empirical tests using small-signal perturbations and adopting Fourier transform on the switching converter response. The proposed theory and modelling methodology are verified using a 7MVA grid emulator for voltage perturbation tests on a 2MVA photo-voltaic converter. Accordingly, the couplings can exist in more generic forms, including multiples of perturbation and fundamental frequencies. To the best of our knowledge, the patterns with the multiples of the perturbation frequency have been overlooked in the literature. Furthermore, the mirror frequency concept is valid for all coupling patterns and is included in the proposed model. Besides, the proposed patterns and the environment noise levels have been practical criteria for selecting the main couplings.

frequency and sequence couplings↗