At least 19 records

Monitoring Degradation of Nuclear Cable Insulation Subjected To Sequential and Simultaneous Thermal and Radiation Aging

Predicting useful remaining life of cables in nuclear power plants is a topic of growing interest as plant continue to age. A typical electrical cable consists of polymeric materials, such as the cable jacket and insulation, which are susceptible to degradation due to exposure to both elevated temperatures and gamma irradiation over decades of service. In this work two insulation materials, crosslinked polyethylene (XLPE) and ethylene propylene diene (EPDM) elastomer, were characterized to quantify aging using total color difference and indenter modulus. Since the effects of thermal and gamma radiation are not additive but coupled, the effects of different aging scenarios including sequential and simultaneous aging were also evaluated. In the case of sequential aging, two aging scenarios were explored where the order in which thermal and gamma radiation received were altered. Total color difference of XLPE showed that sequentially aged insulation specimens, which received radiation first, degraded slightly more at maximum exposure than specimens which received thermal first. Similarly, in the case of EPDM, the extent of degradation evaluated using total color difference was found to be most severe in the case of sequentially aged insulation specimens which received radiation first. Indenter modulus was found to be insensitive to aging for XLPE but trended for EPDM. The largest variations were observed for the sequentially aged insulation specimens which received radiation first, similar to what was observed for total color difference.

Pallaka, Madhusudhan Reddy↗

Sequential versus Simultaneous Aging of EPDM Nuclear Cable Insulation Subjected to Elevated Temperature and Gamma Radiation

Electrical cables are integral to power, control, and instrumentation systems within nuclear power plants (NPPs). Exposure of cable systems within nuclear containment to elevated temperatures and gamma radiation during decades-long operation of NPPs can lead to degradation of cable polymeric insulation. Prediction of nuclear cable insulation degradation is complicated as thermal and radiation stress are not additive. In this work, we explore the relative effects of simultaneous and sequential thermal and gamma irradiation on the aging of ethylene-propylene-diene (EPDM) elastomer insulation to better understand realistic scenarios of cable insulation degradation. Cable insulation samples of EPDM were subjected to up to 320 kGy of gamma radiation at a dose rate of 300 Gy/hr in two heating scenarios: (1) simultaneously aged samples were heated at 150°C during irradiation and (2) sequentially aged samples were heated at 150°C for designated durations followed by corresponding periods of irradiation at ambient temperature. The mass, tensile elongation at break, and carbonyl index were assessed to quantify aging of the polymers. The simultaneous aging scenario was found to the more severe of the two for EPDM insulation degradation.

ethylene-propylene-diene elastomer, EPDM, nuclear ↗

Sequential versus Simultaneous Aging of XLPE Nuclear Cable Insulation Subjected to Elevated Temperature and Gamma Radiation

Electrical cables constitute a critical component of nuclear power generation. The aging behavior of electrical cable insulation under combined exposure to thermal and radiation stress is not additive, complicating lifetime prediction of cable performance based on sequential accelerated aging. In this work we explore the relative effects of simultaneous and sequential thermal and gamma radiation aging on cross-linked polyethylene (XLPE), which is commonly found in commercial nuclear power plants in the United States. Samples of XLPE were subjected to up to 320 kGy of gamma irradiation at a dose rate of 300 Gy/hr in two heating scenarios. In the first, simultaneously-aged samples were heated at 150°C during irradiation. In the second, sequentially aged samples were heated at 150°C for designated durations followed by corresponding periods of irradiation without heating. The mass, total color difference, and density were characterized to quantify aging of the insulation polymer. Sequential aging is hypothesized to be more damaging to XLPE insulation due to an increased trend in mass gain, total color difference, and density.

Cross-linked polyethylene, XLPE, nuclear cable, ac↗

Dose Rate Effects in the Aging of Nuclear Cable Insulation Subjected to Gamma Radiation

In nuclear power plants (NPPs), the aging of polymer-based electrical cable insulation must be effectively monitored to ensure the safe and reliable operation of NPPs. Gamma radiation is one of the main environmental stressors causing degradation of cable insulation. For a given total dose of absorbed gamma radiation, damage due to gamma irradiation may be dose rate dependent. The purpose of this work is to confirm whether a dose rate effect exists for the cable insulation made by crosslinked polyethylene (XLPE) and ethylene propylene rubber (EPR), quantify the relationship between degradation rate and dose rate, and explore the correlation of different measured properties. The dose rate effects at 1800 Gy/h, 200 Gy/h, and 100 Gy/h using 60Co gamma irradiation on cable aging was studied. Different types of cable insulation, including two XLPEs and one EPR, were irradiated at the different dose rates with a total dose around 300 kGy at 26 °C. The properties of unirradiated and irradiated samples were characterized by mass change, yellowness index, and other ongoing measurements. Dose rate effects were observed for mass change data of XLPE and EPR.

Li, Donghui↗

Principal Component Analysis of Nuclear Cable Insulation Subjected to Elevated Temperature and Gamma Radiation

In nuclear power plants (NPPs), the aging of electrical cable insulation occurs due to elevated temperature, ionizing radiation, and other environmental factors. To ensure the safe and efficient operation of NPPs, determination of key indicators of cable aging is critical to predict the remaining useful lifetime of electrical cable insulation. In this work, the effects of simultaneous and sequential thermal and gamma radiation on the aging of cross-linked polyethylene (XLPE) electrical cable insulation are investigated. The chemical changes of the insulation were monitored non-destructively through the use of Fourier transform infrared (FTIR) spectroscopy. The FTIR spectra were measured stepwise after predetermined exposure intervals, with a total irradiation dose up to 320 kGy at a dose rate of 300 Gy/hr in two exposure scenarios; simultaneously aged samples were heated at 150 °C during irradiation, while sequentially aged samples were heated at 150 °C for designated durations followed by corresponding times of irradiation at ambient temperature. A data-driven approach using principal component analysis (PCA) was developed to highlight changes in the carbonyl region of the infrared spectra of the aged samples due to oxidation and to differentiate oxidation rates under the simultaneous and sequential exposure conditions. Findings indicate that the sequential aging scenario may be more conservative than the simultaneous aging scenario for XLPE electrical cable insulation.

Li, Donghui↗

On the mechanism of radiation and thermal-induced degradation of the insulation cables in nuclear power plants-the presence of long-lived polyenyl C-centered radicals

Radiolytically and thermally produced long-lived polyenyl C-centered radicals in the nuclear power plants’ insulation cables are detected and measured after more than 45 months of aging since the irradiation and the thermal treatment. Electron Paramagnetic Resonance (EPR) results of the irradiated Cross-linked Polyethylene (XLPE) and Ethylene Propylene Rubber (EthProRu), used as primary insulation materials at Nuclear Power Plants (NPP), clearly demonstrate the presence of polyenyl radicals along with allyl and peroxyl radicals. The yields of these free radicals are dose-rate dependent. EPR results also show the presence of the long-lived polyenyl along with allyl and peroxyl free radicals in the thermally treated XLPE, and EthProRu. These free radicals can cause a major failure in the performance of these cables in NPPs. Besides, the results showed the enhancement in the oxidation reactions due to the migration of copper ions from the conductor to the bulk of the insulation. Further, this study also shows that the oxidation index (OI) and Elongation at Break (EAB) increases and decreases respectively at higher doses and temperatures.

73 NUCLEAR PHYSICS AND RADIATION PHYSICS↗

Application of Principal Component Analysis for the Monitoring of the Aging Process of Nuclear Electrical Cable Insulation

To ensure the safe operation of nuclear power plants (NPPs), it is critical to understand how NPP electrical cable insulation will degrade under different service environments. In this study, various nondestructive examination methods were selected to evaluate degradation of electrical cable insulation after aging. Elongation at break, indenter modulus, relaxation constant, mass change, total color difference, and carbonyl index were collected stepwise on cross-linked polyethylene (XLPE) cable insulations after predetermined exposure intervals. Three different insulation aging scenarios were investigated: 1) simultaneous irradiation and heating at 150°C, 2) heating at 150°C followed by corresponding times of irradiation at ambient temperature, and 3) irradiation at ambient temperature followed by heating at 150°C for the same duration. A constant dose rate of 300 Gy/hr was selected with a total gamma irradiation absorbed dose up to 320 kGy. To gain insight into the long-term performance of NPP electrical cable insulation, principal component analysis (PCA), a data-driven approach, was utilized to identify key indicators of cable insulation degradation. By reducing the dimensionality of the data while retaining degradation information, PCA was used to highlight the changes in the measured properties under gamma irradiation according to total absorbed dose and the different aging scenarios.

Li, Donghui↗

Quantifying Properties for a Mechanistic, Predictive Understanding of Aqueous Impact on Aging of Medium and Low Voltage AC and DC Cabling in Nuclear Power Plants

To address the gap in knowledge in understanding degradation in relevant service conditions, this project aimed to develop a mechanistic, predictive model of medium and low voltage cable failure based on the primary environmental degradation parameters of aqueous immersion time, temperature, and the oxidation extent. To do so, we took a two-fold approach toward evaluating degradation as related to the aqueous condition. First, we evaluated the chemical, mechanical, and electrical properties of polymers that comprise the cabling insulation under varied aqueous conditions at different temperatures. Secondly, we evaluated the performance of insulation materials under similar accelerated aging conditions in addition to the dielectric breakdown of the cabling under submersion conditions. Thermal oxidation and immersion of LDPE thin films were done using a Parr vessel and the extent of oxidation was monitored using the carbonyl index from ATR-FTIR spectrum, a ratio quantifying the carbonyl functionality produced on the LDPE film surface. Increasing the temperature, oxidation time, and oxygen pressure increased the water-vapor permeability and the carbonyl content. Thermogravimetric analysis of the films confirmed that there is indeed an initial weight loss of the smaller molecular weight molecules and volatiles. At higher temperatures, there is a secondary mass loss. Up to 70°C, the mass loss curves were similar until 80°C, when the aged films decreased at a much greater rate with respect to increasing temperature. This was seen in the 10, 50, 90% weight loss temperatures. The mechanical properties of sheet PP and HDPE as well as injection molded LDPE, HDPE, HDPP dog bones were plotted with respect to the time spent in the Parr vessel during thermal oxidation. For the sheet PP and HDPE, the UTS and the modulus of elasticity decreased while the elongation increased. The injection-molded LDPE, HDPE, and HDPP dog bones experienced a similar trend where the changes in the properties were within experimental uncertainty. This analysis of LDPE in dry and immersive oxygen-rich environments is an important baseline for future experiments looking at other degradation mechanisms. A predictive aging model for low-density polyethylene insulative cable housings was developed. This model revealed a combination of physical and chemical processes which lead to an increase in permeability and a decrease in strength of the insulator. In creating this predictive model, a gap of knowledge in the literature was revealed in two areas: understanding how the crystallinity of a polymer changes with time and visualizing the predicted pores formed through the insulator which leads to failure. Developing and using an adapted ATR-FTIR method, crystallinity was monitored and compared to bulk crystallinity found via DSC. Inhomogeneity in crystallinity changes were observed but the FTIR method but was found to be less reliable. Pore visualization was found utilizing electrical impedance spectroscopy saturated aged polyethylene films with synthesized citrate-capped gold nanoparticles, and chloroauric acid precursor. results indicate a decreasing impedance of the polyethylene films caused by the transport of ions through the film. SEM imaging was then performed for elemental analysis of the films and counter electrodes for the presence of ions. Chloride and gold ions were detected; however, no nanoparticles were found. This gives an estimated pore size of at least 0.3 nm through the aged film. Cyclic submergence of polyethylene and polypropylene in aqueous solutions of copper sulfate and Harrison’s solution were examined. It was discovered that aging in these mixed conditions and at 90°C did cause a small, yet significant increase to tensile strength for both unaged polyethylene and polypropylene. The PE and PP in cycled and submerged conditions did not have tensile strengths significantly different from dry-aged after 16 weeks. For both solutions, it was determined that capacitance increases with both water tree depth and cable temperature and is relatively independent of changing water tree AR. As for resistance, there is no apparent change between depth percentages of 10 and 80 for both solutions. This is because the water tree has not yet entered the conductor and thus there is no shorting current flowing through the tree yet. Between 80 and 100% water tree depth, it is observed that for both solutions there is a rapid decrease in resistance because the tree is now impacting the conductor shield and allowing shorting current to flow through it. The relationship between resistance and temperature was found to be inversed. As temperature increases, resistance decreases for both water tree solutions with distilled water having the most apparent difference across the range of temperatures simulated. With regards to water tree AR, resistance was found to be relatively independent at depth percentages of 10, 50, and 70, but there was some relationship at 100% depth for both solutions. At this depth, as water tree AR increased, resistance was found to also increase. Through the examination of voltage and electric field distribution plots, it was confirmed for EPR cables that increasing water tree depth leads to increasing distortion. The increase in shorting current at 100% depth for aqueous copper sulfate compared to distilled water was also visualized. Lastly, the relationship between shorting current and temperature for narrow water trees was visualized and validated using the distribution plots. This study has led to a better understanding of the effect of cable temperature, water tree solution, and geometry of the tree region on cable degradation. Furthermore, this study has documented simulation results of water tree degradation in EPR MV cables, which had been previously lacking in information. Future work in this area will add frequency into the mix and examine what effect it has on the rate of cable degradation as a result of water treeing. To compliment the work being carried by UMD on different polymer chemistries, harvested medium voltage (MV) cables were selected for accelerated aging study at ORNL. These medium voltage cables are representative of the vintages and materials that are currently in use at existing nuclear power plants (NPPs). These cables were immersed in water at 90°C and energized for a period of two years at elevated voltage. Partial discharge was measured during this period of time to track potential degradation. Unfortunately, due to the absence of failure, the extent of integration between the UMD techniques and the harvested MV insulation was limited. However, based on the findings and from the UMD research in the previous sections on polyethylene and polypropylene, follow-on characterization for harvested MV cable insulation should focus on sample preparation to take advantage of the UMD techniques to better understand mechanistic degradation in MV cable insulations. This would include: 1.) Utilization of solutions and impedance measurement insulation to track permeability in harvested and accelerated aging insulation samples, 2.) Adaptation of gold nanoparticle synthesis for electrical impedance spectroscopy with supporting SEM characterization to study pore formation in harvested and accelerated aged insulation samples, & 3.) ATR-FTIR crystallinity with multiple temperature dependent harvested MV cable insulation under different air and submerged accelerated aging. In addition, low voltage dielectric spectroscopy and high voltage dissipation factor, tan δ, could be implemented as a condition monitoring tool for harvested MV cable insulation in submerged environments.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Extension of Cable Electrical Assessment Techniques to Detect and Discriminate Radiation Aging on Cable Insulation Systems (Abstract)

The purpose of this study of the electrical responses of gamma radiation aged low voltage nuclear cables is to advance tools to determine cable condition (extent of damage) and identify degradation location along the cable length. The developed technology will provide nuclear plant operators with the options to focus cable repair, mitigation, or replacement efforts locally and avoid wholesale cable replacement.

42 ENGINEERING↗

Investigation of Inverse Temperature Effects During Thermal-Radiation Aging of Semicrystalline Cable Insulation

Inverse temperature effects were observed for semi-crystalline polymers subjected to combined thermal and irradiation aging. The mechanical durability of materials aged at low temperatures degrades with dose faster than at high temperatures. In this paper, two crosslinked polyethylene (XLPE) and two ethylene propylene rubber (EPR) type nuclear cable insulations were exposed to thermal-radiation aging at 100Gy/h up to 30Mrad and three temperatures (26°C, 50°C, 90°C). Their mass change and color change after aging were analyzed.

Ni, Yelin↗

Dose Rate Effects on Degradation of Nuclear Power Plant Electrical Cable Insulation at a Common Dose

The intent of this report is to address an identified knowledge gap in relating accelerated aging of nuclear electrical cables to service aging: dose rate effects (DRE). Here, DRE refer to gamma radiation-induced polymer degradation being a function of dose rate in addition to total absorbed dose. The concern raised is that historical qualification conducted at higher dose rates to simulate service lifetime may underestimate insulation degradation that occurs at lower dose rates in service. In the work described herein, common nuclear cable insulation materials—cross-linked polyethylene (XLPE) and ethylene propylene diene elastomer (EPDM)—were subjected to accelerated aging at ambient temperature (26°C) at different gamma dose rates of 100, 200 and 1800 Gy/h for select exposure durations to achieve constant total doses of 170, 210 and 300 kGy to evaluate DRE. First, the cable insulation material types investigated are described. Then, the accelerated aging experimental process involving gamma irradiation applied to the insulation specimens at room temperature and different dose rates is discussed. Then, the experimental characterization techniques used to perform this work are elucidated. These include elongation at break (EAB), mass change, yellowness index (YI), carbonyl index (CI), density, indenter modulus (IM), and relaxation constant (t). Theory of polymer degradation is discussed, and characterization results and discussion are provided. Finally, concluding remarks are made. The findings from this work and cited prior work reveal that DRE are material dependent, even between similar material categories (e.g., XLPE). In the case of the EPDM studied, degradation of ductility was observed to be greater at higher dose rate for the same total dose, indicating accelerated gamma aging to be more conservative than extended aging. Thus, conclusions regarding the conservatism of historical qualification likely require additional consideration for specific materials and conditions in question. The results of this study support the contention that, due to inherent limitations and uncertainties associated with prediction of cable remaining useful life from accelerated aging experiments, trending of installed cable insulation health status will be more practical and useful for safe and efficient cable aging management repair and replace decisions than lifetime prediction from historical qualification. The combination of material robustness demonstrated by the qualification process and ongoing monitoring of cable health status combine to provide confidence in continued safe use of existing nuclear cables. Additional research into effective and efficient condition monitoring methods for non-destructive evaluation of installed cables is needed to support aging cable management, including material studies to inform interpretation of measured results.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Development of Cable Aging Acceptance Criteria for Nuclear Facilities

The aging of nuclear power plant electrical cables has been the subject of substantial research and development (R&D) projects in the nuclear industry, national and international laboratories, universities, and vendor organizations for several years. More specifically, these R&D efforts were conducted to develop equipment and techniques for assessing age-related degradation of in-service cables in nuclear facilities including power plants, research reactors, waste facilities and fuel fabrication plants. In recent years, cable R&D efforts in the nuclear arena have also included work to develop new cables for the next generation of reactors. Over time, exposure to harsh environmental conditions such as elevated temperatures, radiation, and humidity in nuclear installations can result in age-related degradation and failure of cables. In the current fleet of nuclear reactors, there are thousands of miles of cabling installed in each plant and many of these cables are exposed to these harsh environmental conditions. For these cables, the jacket and insulation polymers harden and become brittle over time, making them more susceptible to crack formation and growth, moisture intrusion, and other mechanisms that can lead to cable failure. Moreover, the existing U.S. fleet of 98 nuclear reactors has an average operating age of 38 years. Many of these nuclear power plants have applied for and almost all have been granted regulatory approval for license renewals to operate for 60 years, 20 years beyond their original 40-year life. Further, subsequent license renewals (SLRs) are underway with a few commercial nuclear power sites already approved to operate up to 80 years. As these reactors pursue operating life extensions, utilities must find a way to address issues associated with age-related degradation of cables. Designers of small modular reactors are also in need of technologies to evaluate the performance of cables that will be installed in harsher environments (e.g. higher temperatures, radiation doses, dose rates, etc.) than those present in current-generation reactors. Today, a variety of cable condition monitoring (CM) techniques have been developed and successfully used in nuclear facilities. These techniques are used to identify age-related degradation and assess the condition of cables to determine if their performance characteristics have changed with age. However, objective criteria must be developed for these CM tests to help quantify cable condition and thereby develop repair and replacement schedules. With operating life extending to 80 years and more SLRs on the horizon, both nuclear facilities and regulators need an objective means to determine the aged condition of cables.

36 MATERIALS SCIENCE↗

Development of Cable Aging Acceptance Criteria for Nuclear Facilities

The aging of nuclear power plant electrical cables has been the subject of substantial research and development (R&D) projects in the nuclear industry, national and international laboratories, universities, and vendor organizations for several years. More specifically, these R&D efforts were conducted to develop equipment and techniques for assessing age-related degradation of in-service cables in nuclear facilities including power plants, research reactors, waste facilities and fuel fabrication plants. In recent years, cable R&D efforts in the nuclear arena have also included work to develop new cables for the next generation of reactors. Over time, exposure to harsh environmental conditions such as elevated temperatures, radiation, and humidity in nuclear installations can result in age-related degradation and failure of cables. In the current fleet of nuclear reactors, there are thousands of miles of cabling installed in each plant and many of these cables are exposed to these harsh environmental conditions. For these cables, the jacket and insulation polymers harden and become brittle over time, making them more susceptible to crack formation and growth, moisture intrusion, and other mechanisms that can lead to cable failure. Moreover, the existing U.S. fleet of 98 nuclear reactors has an average operating age of 38 years. Many of these nuclear power plants have applied for and almost all have been granted regulatory approval for license renewals to operate for 60 years, 20 years beyond their original 40-year life. Further, subsequent license renewals (SLRs) are underway with a few commercial nuclear power sites already approved to operate up to 80 years. As these reactors pursue operating life extensions, utilities must find a way to address issues associated with age-related degradation of cables. Designers of small modular reactors are also in need of technologies to evaluate the performance of cables that will be installed in harsher environments (e.g. higher temperatures, radiation doses, dose rates, etc.) than those present in current-generation reactors. Today, a variety of cable condition monitoring (CM) techniques have been developed and successfully used in nuclear facilities. These techniques are used to identify age-related degradation and assess the condition of cables to determine if their performance characteristics have changed with age. However, objective criteria must be developed for these CM tests to help quantify cable condition and thereby develop repair and replacement schedules. With operating life extending to 80 years and more SLRs on the horizon, both nuclear facilities and regulators need an objective means to determine the aged condition of cables.

36 MATERIALS SCIENCE↗

Evaluation of Oxygen Consumption as a Sensitive Measure of Electrical Cable Polymer Insulation Degradation

Polymers used as dielectric materials in nuclear grade electrical cables, such as cross-linked polyethylene (XLPE) and ethylene-propylene rubber (EPR), are long-lived and durable. Estimating the decades-long useful service life of polymers experimentally in a feasible timeframe of weeks or months requires greatly accelerated aging in the laboratory at elevated temperatures and/or gamma dose rates. Many limitations of accelerated aging, such as due to artefacts of the process including diffusion limited oxidation and dose rate effects, have been identified that can make accurate lifetime prediction at service conditions challenging. This can be due to differences in degradation mechanisms between rapid and extended aging or to the presence of induction periods during which early aging is undetectable using common metrics of polymer insulation characterization such as tensile elongation at break. Conceptually, an ideal measure of aging would track clearly and predictably with material changes throughout the lifecycle of the evolving material state from early aging through end of useful life. With such a metric accelerated aging could be performed at much milder conditions, conditions closer to those found in long term service, and end of life calculated from the early data. Oxygen consumption has previously been proposed as a sensitive measure of insulation polymer oxidation that might meet such desirable characteristics. In this work, nuclear cable insulation samples of the two most common types, XLPE and EPR, from two of the most sourced manufacturers, RSCC and The Okonite Company, were subjected to gamma irradiation at dose rates of 100, 200, and 300 Gy/hr for up to 42 days at 26°C. The aged samples were used to evaluate oxygen consumption as a sensitive measure of aging for these materials and these conditions. For comparison and validation, the aged samples were also characterized using the more conventional tests of mass change, density, carbonyl index, and yellowness index. For both materials, oxygen consumption during irradiation was found to track consistently with applied dose—oxygen consumption rate was linear with time. Mass change and carbonyl index were also clearly proportional to exposure dose. Yellowness index, a surface sensitive measure, was observed to increase linearly with dose at low exposure levels before plateauing. Sample density was not observed to change under the conditions explored. Oxygen consumption was found to be a particularly sensitive metric to measure the degradation of polymeric cable insulation exposed to radiation. Oxygen consumption was compared to Arrhenius and time-temperature-superposition methods for activation energy calculation using literature date and found to be a useful and viable alternative for lifetime prediction. The techniques developed in this work are anticipated to be valuable in the estimation of insulation aging rates under mild conditions approaching service conditions. Direction comparison of useful life prediction by oxygen consumption with prediction via Arrhenius methodology for thermal aging and existing methods for radiation and combined thermal/radiation aging would serve to further validate this promising approach and refine our understanding of material-specific aging rates.

36 MATERIALS SCIENCE↗