Spatial-Temporal Recurrent Graph Neural Networks for Fault Diagnostics in Power Distribution Systems

Fault diagnostics are extremely important to decide proper actions toward fault isolation and system restoration. The growing integration of inverter-based distributed energy resources imposes strong influences on fault detection using traditional overcurrent relays. This paper utilizes emerging graph learning techniques to build new temporal recurrent graph neural network models for fault diagnostics. The temporal recurrent graph neural network structures can extract the spatial-temporal features from data of voltage measurement units installed at the critical buses. From these features, fault event detection, fault type/phase classification, and fault location are performed. Compared with previous works, the proposed temporal recurrent graph neural networks provide a better generalization for fault diagnostics. Moreover, the proposed scheme retrieves the voltage signals instead of current signals so that there is no need to install relays at all lines of the distribution system. Therefore, the proposed scheme is generalizable and not limited by the number of relays installed. The effectiveness of the proposed method is comprehensively evaluated on the Potsdam microgrid and IEEE 123-node system in comparison with other neural network structures.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distribution power system fault control apparatus and method

A method includes detecting a fault in a grid coupled to a distribution power network, the distribution power network comprising a distribution feeder, a plurality of distributed energy resources (DERs) coupled to the distribution feeder and a reference point of applicability (RPA) associated with the plurality of DERs, and in response to detecting the fault, determining an error voltage at the RPA, converting the error voltage into an error signal, broadcasting the error signal to the plurality of DERs, and based on the error signal, reducing the error voltage at the RPA by injecting a plurality of currents from the plurality of DERs to the distribution feeder.

Cintuglu, Mehmet H.↗

Traveling Wave Energy Analysis of Faults on Power Distribution Systems

This paper explores the most important factors that define the Traveling Wave (TW) propagation on distribution systems. The factors considered in this work are: the distance to the fault location, the fault type, and the crossing of system elements (such as regulators, capacitor banks, laterals, and extra loads within the protection zones). This work uses a realistic, yet simplified, distribution system composed of two protection zones, in which, several combinations of the previously mentioned factors are considered. The simulated fault measurements undergo a signal processing stage in which, first, they are decomposed into independent modes using the Karrenbauer transform. Second, a time–frequency representation is obtained using the Stationary Wavelet Transform (SWT), dividing the signal into several frequency bands. Finally, the Parseval’s Energy (PE) theorem is applied to calculate the signal energy in each frequency band. A qualitative analysis is performed based on the previously calculated energies to outline which are the factors that most affect the TW energy during propagation. The results show that distance, the presence of regulators, either in the propagation path or upstream, and the type of fault are the main factors that affect TW propagation across the system, and therefore they should be considered for TW-based protection schemes for distribution systems.

Jiménez-Aparicio, Miguel (ORCID:000000016864461X)↗

Distributed Ledger Technology for Fault Tolerant Distribution Grid Operations

This paper explores the potential of distributed ledger technology (DLT) to improve fault-tolerant grid operations by leveraging its core features as an immutable, decentralized ledger, a distributed, consensus-based agreement process, and a distributed state-replication engine. Distribution power systems deliver electricity to millions of customers; however, they are susceptible to various threats that can result in customer interruptions. These include faults caused by adverse weather conditions, natural disasters, vegetation growth, equipment failure, and malicious attacks. To minimize the effects of these faults, fault-handling approaches rely on network knowledge to isolate affected areas and reconnect unaffected areas, reducing the number of affected customers while maintaining safety. Here, we present a trusted data-sharing architecture that enables independent, distributed actors to reconstruct the pre-fault system state by enabling distributed resources to make appropriate decisions with limited network/system information. Although the process requires some data sharing between switch-delimited areas, the approach limits the amount of private information shared, preserving customers' privacy and business-sensitive information. We include three use cases that form a foundation for third parties to develop functional solutions that can eventually be deployed in the field. The gross error detection method used within switch-delimited areas can identify sensor errors and accurately detect circuit breaker states. The evaluation of possible reconnection while preserving data ownership resulted in a voltage magnitude difference smaller than 0.001% from the OpenDSS power flow solution that has full system knowledge, which is below the expected power flow tolerance. The approach offers a promising opportunity for improving fault-tolerant distribution grid operations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Electrical Fault Detection, Power Quality, Distributed Energy Resource Use Cases, and Cyber Event Applications with the Cyber Grid Guard System Using Distributed Ledger Technology

Electrical utilities continue to deploy more intelligent electronic devices (IEDs) inside and outside electrical substation and are associated with distributed energy resources (DERs). The integrity and confidentiality of data from IEDs is crucial, and distributed ledger technology (DLT) could improve the resilience of microgrids by helping to make these data more secure. The most popular applications using blockchain technology for electrical utilities is in the field is based on energy trading. However, the dynamism of the penetration of customer owned DERs and the deployment of sensors with IEDs have led to the identification of new applications using DLT that are focused on other areas, such as monitoring, operation and management of the grid and its assets. In addition, the majority of studies on electrical grid applications with blockchain were validated with software simulations. Although general monitoring of power systems for using DLT could be evaluated in operational electric grids, other DLT research applications such as defense against cyber-attacks and/or electrical fault detection are not likely to be performed in a real infrastructure because of possible risks to the network/equipment security. This report summarizes the application of power system applications using distributed ledger technology (DLT), providing a secure DLT framework for collecting data from IEDs like power meters and protective relays inside and outside of an electrical substation and/or between two different electrical utilities. In this study, the use case scenarios were created and assessed for different power system application by using DLT. The electrical fault detection for faulted phases (1), power quality monitoring of phase voltage magnitudes, frequency levels and load power factor (2), DERs use case monitoring (3), and cyber-event applications (4) were performed in a test bed with a Cyber-Grid Guard (CGG) system using DLT. It had a real-time simulator with power meters and protective relays in-the-loop. The first section of this report presents a literature review of power system applications using blockchain at research level. The second section shows the theory and equations used on this report. The third section shows the description of the test bed, equipment, architecture, and electrical grid diagrams. The fourth section shows the experimental models and use case scenarios that were performed for the electrical fault detection, power quality, DERs use case, and cyber event applications with the CGG system using DLT. The fifth section shows the results collected from the tests based on comparing the time stamped events of the analog signals from the IEDs, DLT computer and real time simulator. The sixth section performed the discussion of the results for the use case scenarios. Finally, section seven presents the conclusions for this report were presented.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Influence of Inverter-Based Resources on Microgrid Protection: Part 1: Microgrids in Radial Distribution Systems

Microgrids are being deployed at a rising rate, primarily as a means of increasing power system resilience. Commonly, a microgrid today includes at least some inverter-based resources (IBRs), and many microgrids have modes or conditions under which they are entirely energized by IBRs. Also, most microgrids today are deployed on radial distribution circuits, but it is conceivable that they could also be considered for deployment on secondary network systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Assessment of the Phase-to-Ground Fault Apparent Admittance Method with Phase/Ground Boundaries to Detect Types of Electrical Faults for Protective Relays Using Signature Library and Simulated Events

Protective relays in electric power grids recognize the types of electrical faults in a few seconds. The most common detection method to detect the types of electrical faults is based on measuring the angle between the zero and negative sequence currents. However, it is not completely accurate because the phase to phase ground and phase to ground electrical faults could have the same detection conditions. Therefore, engineers need to plot the events after an electrical fault to observe the nature of the incidents in detail. In this study, the phase to ground fault apparent (PGFA) admittance method with phase/ground boundaries identified the types of electrical faults located in distribution power lines and feeders. This method was based on measuring the PGFA admittance magnitudes for the faulted and non-faulted phases, resulting in greater than zero and near zero, respectively. The PGFA admittance algorithm was built with MATLAB/ Simulink software and tested with signature library and grid simulation events. The PGFA method with phase/ground boundaries was evaluated with the confusion matrix. The measured and predicted values matched in more than 90% of the tests, and the PGFA admittance method with phase/ground boundaries presented an accuracy of 94.3% and a precision of 100%.

Piesciorovsky, Emilio↗

Assessment of the Phase-to-Ground Fault Apparent Admittance Method with Phase/Ground Boundaries to Detect Types of Electrical Faults for Protective Relays Using Signature Library and Simulated Events

Protective relays in electric power grids recognize the types of electrical faults in a few seconds. The most common detection method to detect the types of electrical faults is based on measuring the angle between the zero and negative sequence currents. However, it is not completely accurate because the phase-to-phase-ground and phase-to-ground electrical faults could have the same detection conditions. Therefore, engineers need to plot the events after an electrical fault to observe the nature of the incidents in detail. In this study, the phase-to-ground fault apparent (PGFA) admittance method with phase/ground boundaries identified the types of electrical faults located in distribution power lines and feeders. This method was based on measuring the PGFA admittance magnitudes for the faulted and nonfaulted phases, resulting in greater than zero and near zero, respectively. The PGFA admittance algorithm was built with MATLAB/Simulink software and tested with signature library and grid simulation events. The PGFA method with phase/ground boundaries was evaluated with the confusion matrix. The measured and predicted values matched in more than 90% of the tests, and the PGFA admittance method with phase/ground boundaries presented an accuracy of 94.3% and a precision of 100%.

42 ENGINEERING↗

Advanced Sensor Deployment for Distribution System State Estimation and Fault Identification

Distribution systems are currently facing steep operational challenges as a result of the rapidly increasing integration of renewables and other distributed energy resources (DERs) at both the primary and secondary circuit levels. Distribution utilities and system operators have traditionally had some visibility of their primary circuits using low-frequency supervisory control and data acquisition systems, and they have had very poor if not zero visibility of the secondary circuits where the presence of DERs is constantly increasing. Therefore, this paper presents simulation studies to demonstrate the benefits of an advanced, high-fidelity sensor technology, called as the Meta-Alert System (MAS), developed by Electrical Grid Monitoring, Ltd. (EGM), on the distribution grid. First, a reliable model of the EGM sensors is developed, and then two use cases, distribution system state estimation (DSSE) and fault identification are simulated to evaluate the performance of the MAS technology. Simulation results on the Electric Power Research Institute J1 feeder demonstrate that the MAS can effectively participate in system-level DSSE programs and can detect and locate faults faster than traditional distribution protection schemes.

distribution system↗

Guest Editorial: Planning and operation of resilient distribution system for integrated multi-energy

Resilience is the ability of power systems to prepare for and adapt to low-probability, high-impact incidents and withstand and recover rapidly from disruptions. With the ageing of electricity distribution infrastructure and increasing threats of weather-related incidents and natural disasters, the need to effectively enhance the resilience of the electricity distribution system has become urgent and has attracted worldwide attention. Although there are an increasing number of publications related to enhancing resilience strategies, resilience is an emerging concept in power systems. Existing practices are mostly focused on deploying distributed energy resources (DERs) and microgrids, hardening the existing infrastructures and building redundant capacities. However, from a broader perspective, resilience enhancement of power distribution system is a systematic engineering, involving long-term system planning and upgrading (e.g., deployment of smart grid technologies and intelligent switches), short-term proactive scheduling, real-time robust and resilient control of DERs, and post-event restoration and recovery strategies. Based on this point, this Special Issue in IET Energy System Integration focuses on soliciting the most recent and original technologies, scheduling and control strategies for improving the resilience of power distribution system. Eight papers are presented in this Special Issue, covering various aspects related to resilience enhancement of power distribution system, including fault-tolerant frequency measurement, robust scheduling of integrated electricity and district heating systems, robust control of DERs, efficient methods for safety verification as well as novel graph theory-based approach to restore the distribution systems after multiple simultaneous faults. A brief introduction of these 8 papers is provided below.

24 POWER TRANSMISSION AND DISTRIBUTION↗