Search NASA⌕ Search

SEARCH · Search NASA

Results for “retro-commissioning”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Retro-Commissioning Sensor Suitcase

This software package is the Graphic User Interface (GUI) software component for the Sensor Suitcase Retro-Commissioning project, which is a sensor and analysis system to support monitoring-based retro-commissioning of small commercial buildings, performed by non-experts. Small commercial buildings typically do not have the budgets or business economics to allow investing in energy efficiency enhancements the building retro-commissioning provides. In addition, they do not have in-house staff with expertise in building systems who can perform building retro-commissioning or identify energy efficiency improvement opportunities. The solution to this problem is to develop a turn-key hardware/software solution (the RCx Sensor Suitcase) that can be used by non-experts to automatically generate low and no-cost energy efficiency rec commendations that will improve building operating costs, occupant comfort and building energy performance. This is a joint project between Lawrence Berkeley National Laboratory, leading the development of the software and analysis elements, and Pacific Northwest National Laboratory (PNNL), leading the development of the hardware and sensor elements with an associated table-based configuration support tool. The project is funded by the U.S. Department of Energy. This software package was developed as a proof-of-concept prototype for the sensor suitcase software component. The software component was developed with a Microsoft Excel spreadsheet which reads the sensor data and calls a MATLAB DLL to analyze the sensor data.

Lin, Guanjing↗

Energy and Cost Savings of Retro-Commissioning and Retrofit Measures for Large Office Buildings

This paper evaluates the energy and cost savings of seven retro-commissioning measures and 29 retrofit measures applicable to most large office buildings. The baseline model is for a hypothetical building with characteristics of large office buildings constructed before 1980. Each retro-commissioning measure is evaluated against the original baseline in terms of its potential of energy and cost savings while each retrofit measure is evaluated against the commissioned building. All measures are evaluated in five locations (Miami, Las Vegas, Seattle, Chicago and Duluth) to understand the impact of weather conditions on energy and cost savings. The results show that implementation of the seven operation and maintenance measures as part of a retro-commissioning process can yield an average of about 22% of energy use reduction and 14% of energy cost reduction. Widening zone temperature deadband, lowering VAV terminal minimum air flow set points and lighting upgrades are effective retrofit measures to be considered.

Wang, Weimin↗

Scaling Retro-Commissioning to Small Commercial Buildings: A Turnkey Automated Hardware-Software Solution

In the United States, small commercial buildings represent 51% of total floor space of all commercial buildings and consume nearly 3 quadrillion Btu (3.2 quintillion joule) of site energy annually, presenting an enormous opportunity for energy savings. Retro-commissioning (RCx), the process through which professional energy service providers identify and correct operational problems, has proven to be a cost-effective means to achieve median energy savings of 16%. However, retro-commissioning is not typically conducted at scale throughout the commercial stock. Very few small commercial buildings are retro-commissioned because utility expenses are relatively modest, margins are tighter, and capital for improvements is limited. In addition, small buildings do not have in-house staff with the expertise to identify improvement opportunities. In response, a turnkey hardware-software solution was developed to enable cost-effective, monitoring-based RCx of small commercial buildings. This highly tailored solution enables non-commissioning providers to identify energy and comfort problems, as well as associated cost impacts and remedies. It also facilitates scale by offering energy service providers the means to streamline their existing processes and reduce costs by more than half. The turnkey RCx sensor suitcase consists of two primary components: a suitcase of sensors for short-term building data collection that guides users through the process of deploying and retrieving their data and a software application that automates analysis of sensor data, identifies problems and generates recommendations. This paper presents the design and testing of prototype models, including descriptions of the hardware design, analysis algorithms, performance testing, and plans for dissemination.

Lin, Guanjing↗

Retro-Commissioning Sensor Suitcase for Energy Efficiency

This project will enable Pacific Northwest National Laboratory (PNNL) and Lawrence Berkeley National Laboratory (LBNL) to work with industry partner, GreenPath Energy Solutions, joint developers of the Suitcase, to enhance the capabilities and usability of the Retro-Commissioning Sensor Suitcase (hereinafter the Sensor Suitcase or Suitcase), assisting GreenPath to take the Suitcase to market and rapidly expand their market share. The proposed project will specifically focus on 1) adding sensors types to extend the data collection capability and support more building and equipment performance metrics and identification of even more energy saving opportunities, 2) developing algorithms to identify recommendations for the new energy savings opportunities from item 1 and to prototype software modifications implementing them, 3) validating the use of vibration sensors to detect the operating state of a broader set of packaged HVAC equipment (additional capacities, different numbers of stages, etc.) than tested in initial development and modifying the state algorithm and software code, as needed, 4) improving cost-effectiveness in manufacturing the Sensor Suitcase, and 5) additional field testing of the technology in real buildings to more comprehensively validate Suitcase performance and to guide refinement of its capabilities. Project results will position GreenPath, and potential future licensees, to implement the new capabilities developed in this project in GreenPath’s RCx Building Suitcase, increasing its functionality and the savings resulting from its use. These enhancements will increase the value of the Suitcase to users and increase the potential market for its use and impacts in that impact.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Retro-Commissioning Sensor Suitcase for Energy Efficiency (CRADA Final Report)

The Sensor Suitcase project aimed to enable cost-effective, data-driven retro-commissioning (RCx) in small commercial buildings through a self-installable toolkit consisting of portable sensors and diagnostic software. Results showed that the Sensor Suitcase could identify common operational faults leading to 5–15% energy savings opportunities, with automated reports requiring minimal user interpretation. The project adhered closely to its Statement of Work (SOW) but evolved the reporting interface and sensor logging duration based on field feedback. The development and validation of diagnostics are documented in PNNL technical reports and internal analysis summaries.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Using Whole-Building Electric Load Data in Continuous or Retro-Commissioning

Whole-building electric load data can often reveal problems with building equipment or operations. In this paper, we present methods for analyzing 15-minute-interval electric load data. These methods allow building operators, energy managers, and commissioning agents to better understand a building's electricity consumption over time and to compare it to other buildings, helping them to 'ask the right questions' to discover opportunities for electricity waste elimination, energy efficiency, peak load management, and demand response. For example: Does the building use too much energy at night, or on hot days, or in the early evening? Knowing the answer to questions like these can help with retro-commissioning or continuous commissioning. The methods discussed here can also be used to assess how building energy performance varies with time. Comparing electric load before and after fixing equipment or changing operations can help verify that the fixes have the intended effect on energy consumption. Analysis methods discussed in this paper include: ways to graphically represent electric load data; the definition of various parameters that characterize facility electricity loads; and a regression-based electricity load model that accounts for both time of week and outdoor air temperature. The methods are illustrated by applying them to data from commercial buildings. We demonstrate the ability to recognize changes in building operation, and to quantify changes in energy performance. Some key findings are: 1) Plotting time series electric load data is useful for understanding electricity consumption patterns and changes to those patterns, but results may be misleading if data from different time intervals are not weather-normalized. 2) Parameter plots can highlight key features of electric load data and may be easier to interpret than plots of time series data themselves. 3) A time-of-week indicator variable (as compared to time-of-day and day-of-week indicator variables) improves the accuracy of regression models of electric load. 4) A piecewise linear and continuous outdoor air temperature dependence can be derived without the use of a change-point model (which would add complexity to the modeling algorithm) or assumptions about when structural changes occur (which could introduce inaccuracy). 5) A model that includes time-of-week and temperature dependence can be used for weather normalization and can determine whether the building is unusually temperature-sensitive, which can indicate problems with HVAC operation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Prevalence of typical operational problems and energy savings opportunities in U.S. commercial buildings

In the United States, as much as 30% of the 19 EJ that commercial buildings consume is considered excess. Much of the excess energy is due to the inability to manage building operations efficiently. Because almost 20% of the total primary energy consumption is associated with commercial buildings, significant energy reductions in this sector are needed to mitigate climate change. Therefore, many cities and states are mandating periodic “tune-ups” of these buildings to eliminate excess energy consumption. Although the benefits of tune-ups and retro-commissioning are clear, focusing these mandates to look for specific opportunities has been a challenge because of the lack of studies that document the prevalence of opportunities. Therefore, we analyzed building automation system data from 151 buildings across the United States to document common operational problems and opportunities to improve building operations. This analysis showed that opportunities to improve building operations exist in almost every building. These opportunities were not strongly correlated with building vintage or size, but were reflective of how the buildings are operated. The prevalence of the top 20 opportunities ranged between 74% and 23%, with 40% of these associated with air-handling units. The rest of the opportunities are associated with schedules, chilled and hot-water distribution, and zone controls. Of the 151 buildings, 69 of them implemented corrective actions of some or all opportunities that were identified. Implementation varied across the Re-tuning categories, with 60% for schedule opportunities, 50% for zone opportunities, over 40% for the air-handling unit and hot-water opportunities, and 35% of the chilled-water opportunities. There was wide variation in whole building energy savings, ranging from 0 to 50% and 0 to 18 $/m2 with median percent annual whole building savings of 12% and median normalized annual cost savings of $1.75/m2. In addition to documenting these key findings, the paper provides a list of opportunities that can be automatically and continuously identified and corrected and offers a list of those opportunities that should be the focus of the mandates.

Katipamula, Srinivas↗

Standard Energy Efficiency Data Platform

The SEED platform is expected to be a building energy performance data management tool that provides federal, state and local governments, building owners and operators with an easy, flexible and cost-effective method to collect information about groups of buildings, oversee compliance with energy disclosure laws and demonstrate the economic and environmental benefits of energy efficiency. It will allow users to leverage a local application to manage data disclosure and large data sets without the IT investment of developing custom applications. The first users of SEED will be agencies that need to collect, store, and report/share large data sets generated by benchmarking, energy auditing, retro-commissioning or retrofitting of many buildings. Similarly, building owners and operators will use SEED to manage their own energy data in a common format and centralized location. SEED users will also control the disclosure of their information for compliance requirements, recognition programs such as ENERGY STAR, or data sharing with the Buildings Performance Database and/or other third parties at their discretion.

Cheifetz, D.Magnus↗

Re-Envisioning RCx: Achieving Max Potential HVAC Controls Retrofits through Modernized BAS Hardware and Software

Most existing buildings have sub-optimal heating, ventilation, and air conditioning (HVAC) controls, resulting in wasted energy and occupant discomfort. Retro-commissioning (RCx) addresses many of these issues, but it is a lengthy and highly customized process. Limited capabilities of existing building automation system hardware restricts the scope of most RCx projects. Incentive programs consider building automation system (BAS) hardware retrofits to be high-capital investments and do not allow them in typical RCx programs. This paper describes work that the authors are leading to facilitate technical and market innovation in the BAS industry to unlock large savings in existing commercial buildings through deep retrofits of BAS hardware and software. California and New York research projects are demonstrating BAS retrofits leveraging the American Society of Heating, Refrigeration, and Air Conditioning Engineers’ (ASHRAE) new Guideline 36 high performance sequences of operation to achieve greater than 20 percent whole building energy savings, while saving costs and reducing risk through streamlined processes and standardization across BAS manufacturer product lines and across implementation practices. This paper describes market barriers that impede achieving deep savings from BAS retrofits in custom incentive and traditional RCx programs and presents a new maximum potential BAS retrofit model that addresses these barriers. The new model leverages the authors’ efforts in market enablement through open standards, BAS industry partnerships, and tools for cost-effective scaling that includes tools for project screening, savings calculations, and measurement and verification (M&V). This approach is widely applicable and will be ready for at-scale implementation within two years.

Paliaga, Gwelen↗

Policy, Permit, Perform: Using City Benchmarking Data and Building Construction Permit History to Identify Energy Performance Improvements

The City of Portland (City) and Multnomah County 2015 Climate Action Plan targets a 40 percent reduction in carbon emissions below 1990 levels by 2030. To reach this goal, the plan includes a key objective to reduce the total energy use of existing buildings by 25 percent. Buildings are responsible for one-half of carbon emissions in Portland, Oregon, U.S., and improving their performance is critical to achieving the City’s climate goals. As part of its climate action planning, the City passed an ordinance on April 22, 2015, requiring commercial buildings 20,000 ft2 and larger to benchmark and disclose annual energy performance metrics through ENERGY STAR® Portfolio Manager® (ESPM), including greenhouse gas emissions, building energy use intensity (EUI) and ENERGY STAR scores. Twenty-five cities in the U.S. have adopted similar policies requiring energy benchmarking. These policies are generating a treasure trove of data about the drivers of building performance, but practitioners are only beginning to link benchmarking data to other datasets to produce actionable insight into improving building performance. In 2016, the City received a financial assistance award from the U.S. Department of Energy (DOE) through the Cities Leading through Energy Analysis and Planning project (Award Number DE-0007737). Portland’s project evaluated the application of the DOE Building Energy Asset Score Tool and rating system developed by Pacific Northwest National Laboratory (PNNL) to commercial buildings that report to the City. The City used building construction permit history to develop Asset Scores for a set of office buildings that reported energy performance for 2015 – the first year the City mandated energy benchmarking and reporting for commercial buildings 50,000 ft2 and larger. The primary project objective was to link energy benchmarking data and commercial building permit data to analyze commercial buildings systems that present the best, specific opportunities to improve energy performance. Integrating these datasets from two City departments, the Bureau of Development Services and the Bureau of Planning and Sustainability, could expand Portland’s use of analytics to inform climate policy decisions and strategic targeting of financial incentives for building owners and managers who are best positioned to improve the performance of their buildings. The project began with the commercial benchmarking data received for 340 commercial buildings that submitted calendar year 2015 energy reports. The City retained Research Into Action and Energy 350 (RIA team) to evaluate this self-reported benchmarking data. Based on a survey of 53 building managers, the RIA team found that most respondents used the City’s compliance tools, including a How-to Guide and Help Desk, and found access to utility data to be straightforward. However, almost one-third of the respondents encountered challenges when estimating the gross floor area (GFA), and some experienced confusion regarding the input of property use types and details into ESPM. Based on the RIA team’s recommendations, the City refined its How-to Guide, created online answers to frequently asked questions, and hosted office hour sessions to help building managers accurately characterize their building’s physical characteristics and operations in ESPM. Concurrently with the RIA team’s evaluation, the City worked with PNNL to estimate DOE Asset Score Preview (Preview) scores for 181 of the 340 commercial buildings that submitted ESPM reports to the City. Asset Score Tool is a web-based tool developed by PNNL for DOE to evaluate and rate the as-built energy efficiency of a building. Asset Score Tool’s full analysis capability runs a detailed energy model based on building geometry, age, envelope, lighting and mechanical systems using standard operating assumptions to give the building a score, similar to a miles per gallon rating for a car. Preview, a simplified deployment of the full Asset Score Tool, provides a preliminary score range using only seven data points, six of which are readily available in the ESPM benchmarking data. Analysis of the combined Preview scores and the operational ESPM scores identified buildings with a high potential for energy improvements through either retro-commissioning and retuning of existing operations or capital investments into building systems. The City contracted Whole Building Solutions (WBS) to mine building permit history and develop full Asset Scores for a subset of 26 office buildings that were eligible for both ENERGY STAR scores and Asset Scores. WBS researched permits and building plans to identify mechanical, lighting and envelope systems and other building characteristics necessary to complete Asset Scores. This historical data was recorded using the web-based Asset Score Tool, which evaluates the as designed energy efficiency of existing buildings. Much of this City information was available online after 2010; however, WBS had to search through microfiche files and the City’s database to obtain permit and plan history prior to 2010. Although building geometry, mechanical system type and basic envelope information was consistently identifiable, WBS found permit data gaps that prevented complete and accurate Asset Scores for most of the office buildings. If the City decides to develop Asset Scores based on building permit information in the future, WBS recommended requiring lighting plans, control diagrams and as-built drawings that reflect how the buildings are actually constructed. In addition, WBS recommended uploading plans and permits from microfiche storage into a more comprehensive, searchable database consistent with the City’s current online permit information. To identify the actual lighting types, WBS and City staff conducted site visits of all 26 office buildings. As part of managing the flow of ESPM and Asset Score data for the project, Earth Advantage, a sub-recipient of the Cities-LEAP award, created a DOE Standard Energy Efficiency Data (SEED) (USDOE 2018) instance for the City and used Asset Score’s Application Programming Interface (API) (Asset Score 2018) capabilities to develop two new features in the SEED Platform™: (1) automated Asset Score Preview ranges calculated based on benchmarking data and the City’s estimate of number of building floors; and (2) storage of full Asset Score information. Leveraging the construction permit history and site visit information for the 26 office buildings, The Cadmus Group (Cadmus) analyzed benchmarking data and Asset Score information to identify opportunities and drivers to improve performance. Correlation and regression analysis of the combined dataset was completed to determine whether building operations or specific systems – mechanical, lighting or envelope – present the best opportunities to improve energy performance. The central outcome of this project was Cadmus’ detailed analysis of the richer dataset that was created by combining the City of Portland’s commercial building permit activity and building-specific energy performance information based on metrics from ESPM and Asset Score Tool. Some of their findings collaborate with well-known facts, such as buildings with less efficient lighting systems are good targets for efficiency improvements through lighting upgrades. This analysis also helped identify that individual heating, ventilation, and air conditioning (HVAC) equipment efficiency does not necessarily correlate with building performance. However, overall HVAC system performance, as measured with the Total System Performance Ratio (TSPR) metric, is a better indicator of building performance (Goel et al. 2014). As a metric, TSPR considers whole system performance that includes equipment efficiency and system controls, such as resets for static pressure and chilled water setpoints, which can be more effective and financially feasible options for improving building performance. Given the high cost associated with envelope retrofits, opportunities to upgrade envelope insulation are likely to be limited. However, buildings with single-pane and non-thermal break windows are good candidates for window replacements, such as upgrading to double-pane windows with thermal breaks. This research project determined that developing Asset Scores based on site visits is preferable to mining City building permit data. In addition, the use of benchmarking data to develop Asset Score Preview Scores is recommended as a first step in engaging building managers to develop full Asset Scores. Asset Score Tool outputs can help building managers quickly identify opportunities for improvement and then work with the utility incentive administrator and energy service providers to develop their retrofit plan. Where full Asset Scores are available, analysis using a quadrant matrix with ENERGY STAR scores is recommended to identify buildings that present the best opportunities for operational-behavioral improvements versus ones with opportunities for upgrades to physical building systems. This workflow and the tools will help cities, utility incentive administrators, building portfolio managers and energy service providers develop energy programs and strategies for screening and analysis of buildings with the greatest energy savings potential. This report describes the project approach and research results to inform future coordination of ESPM and Asset Score data, including the use of benchmarking data to generate Preview scores. Given better awareness of energy performance, building managers can make more informed decisions to reduce energy consumption and carbon emissions. With cities, states and jurisdictions adopting benchmarking and auditing ordinances, there are substantial amounts of data submitted to cities that could be used to inform investments in energy efficiency.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Pascua Yaqui Tribe Energy Audit (Final Report)

The Pascua Yaqui Tribe has the goal of reducing energy use and costs in its government facilities and housing. In a proactive effort to meet the Tribe's needs an energy audit was performed to accomplish the following goals: Develop an energy efficiency implementation strategy. Prepare an energy audit to identify cost-effective energy efficiency opportunities. Plan and conduct a level II energy audit in tribal government buildings and tribal housing. The audit encompassed four tribal government buildings and a group of residential structures. The purpose of this project was to assess the various facilities energy use in order to inform a means to lower annual consumption. An evaluation of each facility's historical energy and major energy-consuming equipment was performed, and energy conservation measures (ECM's) were identified. An average of 4 ECM's where recommended for each facility. If each facility's recommended ECM's are implemented, the average calculated yearly benefits to the government and residential buildings would result in a 48.3% reduction in electrical energy/costs savings and a 14.4% reduction in natural gas energy/costs savings. Recommended projects for implementation include: Interior Lighting Upgrade, Exterior Lighting Upgrade, Solar Pool Covers, Retro-Commissioning, Low Volt Fixtures, Plug Load Management System, Occupancy Sensor Control, and Solar PV for government/casino buildings and appliance, window, HVAC, Weather Stripping, and water heaters replacement in residences.

03 NATURAL GAS↗

Standard Energy Efficiency Data Platform

The SEED platform is expected to be a building energy performance data management tool that provides federal, state and local governments, building owners and operators with an easy, flexible and cost-effective method to collect information about groups of buildings, oversee compliance with energy disclosure laws and demonstrate the economic and environmental benefits of energy efficiency. It will allow users to leverage a local application to manage data disclosure and large data sets without the IT investment of developing custom applications. The first users of SEED will be agencies that need to collect, store, and report/share large data sets generated by benchmarking, energy auditing, retro-commissioning or retrofitting of many buildings. Similarly, building owners and operators will use SEED to manage their own energy data in a common format and centralized location. SEED users will also control the disclosure of their information for compliance requirements, recognition programs such as ENERGY STAR, or data sharing with the Buildings Performance Database and/or other third parties at their discretion.

Cheifetz, D. Magnus↗

A National Framework for Energy Audit Ordinances

A handful of U.S. cities have begun to incorporate energy audits into their building energy performance policies. Cities are beginning to recognize an opportunity to use several information tools to bring to real estate markets both motivation to improve efficiency and actionable pointers on how to improve. Care is necessary to combine such tools as operational ratings, energy audits, asset ratings, and building retro-commissioning in an effective policy regime that maximizes market impact. In this paper, the authors focus on energy audits and consider both the needs of the policies' implementers in local governments and the emerging standards and federal tools to improve data collection and practitioner engagement. Over the past two years, we have compared several related data formats such as New York City's existing audit reporting spreadsheet, ASHRAE guidance on building energy auditing, and the DOE Building Energy Asset Score, to identify a possible set of required and optional fields for energy audit reporting programs. Doing so revealed tensions between the ease of data collection and the value of more detailed information, which had implications for the effort and qualifications needed to complete the energy audit. The resulting list of data fields is now feeding back into the regulatory process in several cities currently working on implementing or developing audit policies. Using complementary policies and standardized tools for data transmission, the next generation of policies and programs will be tailored to local building stock and can more effectively target improvement opportunities through each building's life.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Tackling the Giants: Applying Smart Labs Principles to Constant Air Volume Lab Buildings

Laboratories typically consume 3 to 10 times more energy than similarly sized commercial buildings, and as much as 50% of that energy is wasted by inefficient and poorly operating fume hoods and ventilation systems. One challenge faced by older laboratory buildings is the heating, ventilation, and air-conditioning systems serving many of these buildings. The older systems are usually constant air volume (CAV) systems that maintain constant ventilation rates that cause excess airflow and inefficient energy use. Variable air volume systems can be more efficient systems with sensors to detect the need for a change in volumetric flow rate; however; renovation of ventilation systems can create disruption to ongoing research and operations along with considerable up-front costs. When a Smart Labs program is implemented, an organization has a systems-based management approach that yields a high-performing laboratory building. As decarbonization continues as a priority for sites, buildings with CAV systems are difficult to address. This work centers around practical guidance for improving lab buildings with CAV. In conjunction with industry input on top technology solutions and best practices, recommendations will include performing a laboratory ventilation risk assessment in conjunction with robust retro-commissioning work, which is a crucial step in the Smart Lab process. By applying Smart Labs principles, the aging laboratory building stock of 153,343 (Lawrence Berkeley National Laboratory [LBNL] 2017), comprising roughly 500,000 lab spaces in the United States, can be brought to safe and high-performance operations.

building↗

Building Tune-Up Accelerator Program (Final Technical Report)

In 2016, the City of Seattle passed a mandatory Building Tune-Up requirement for all commercial buildings 50,000 square feet (SF) and larger as part of its Climate Action strategy. The requirement is phased in by size with large buildings (greater than 200,000 SF) required first. This allowed Seattle’s Office of Sustainability & Environment (OSE) to offer the Building Tune-Up Accelerator (TUA) Program to the “mid-size” building market (less than 100,000 SF) to meet the requirements early. With funding from the US DOE, a package of technical and financial support was developed for building owners and energy service providers to encourage this hard-to-reach market to participate in the tune-up—and even go beyond requirements for greater energy savings. Seattle City Light, the municipal electric utility, offered participants a simple per square foot financial incentive. Partners at the University of Washington Integrated Design Lab, Smart Buildings Center and Pacific Northwest National Lab (PNNL) offered service provider trainings, analytical tools and technical support. This final technical report summarizes the program, projected energy and emissions savings and lessons learned from program development to implementation to final evaluation for the 102 buildings that participated.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗