Search NASA⌕ Search

SEARCH · Search NASA

Results for “rotor angle stability”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

Hierarchical Power Flow Control in Smart Grids: Enhancing Rotor Angle and Frequency Stability with Demand-Side Flexibility

Large-scale integration of renewables in power systems gives rise to new challenges for keeping synchronization and frequency stability in volatile and uncertain power flow states. To ensure the safety of operation, the system must maintain adequate disturbance rejection capability at the time scales of both rotor angle and system frequency dynamics. This calls for flexibility to be exploited on both the generation and demand sides, compensating volatility and ensuring stability at the two separate time scales. This article proposes a hierarchical power flow control architecture that involves both transmission and distribution networks as well as individual buildings to enhance both small-signal rotor angle stability and frequency stability of the transmission network. The proposed architecture consists of a transmission-level optimizer enhancing system damping ratios, a distribution-level controller following transmission commands and providing frequency support, and a building-level scheduler accounting for quality of service and following the distribution-level targets. Furthermore, we validate the feasibility and performance of the whole control architecture through real-time hardware-in-loop tests involving real-world transmission and distribution network models along with real devices at the Stone Edge Farm Microgrid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Data-Driven Adaptive Damping Controller for Wind Power Plants with Doubly-Fed Induction Generators

This paper presents an adaptive damping controller for wind power plants in which the turbines are equipped with doubly-fed induction generators. The controller is designed to respond to an input control signal that is triggered according to the system operating conditions. A processing unit continuously estimates the electromechanical modes of oscillation based on real-time streaming data acquired from a phasor measurement unit that is strategically positioned on the grid. The decision to trigger (or not trigger) the control signal is automatic, based on the relative damping of the dominant mode. The modes are estimated using the dynamic mode decomposition algorithm with time-delay embedding. Numerical simulations performed on the two-area system demonstrate that the proposed controller enhances the rotor angle stability for both small-signal and large disturbances, and is adaptive to changing grid conditions.

damping controller↗

Data-Driven Adaptive Damping Controller for Wind Power Plants with Doubly-Fed Induction Generators: Preprint

This paper presents an adaptive damping controller for wind power plants in which the turbines are equipped with doubly-fed induction generators. The controller is designed to respond to an input control signal that is triggered according to the system operating conditions. A processing unit continuously estimates the electromechanical modes of oscillation based on real-time streaming data acquired from a phasor measurement unit that is strategically positioned on the grid. The decision to trigger (or not trigger) the control signal is automatic, based on the relative damping of the dominant mode. The modes are estimated using the dynamic mode decomposition algorithm with time-delay embedding. Numerical simulations performed on the two-area system demonstrate that the proposed controller enhances the rotor angle stability for both small-signal and large disturbances, and is adaptive to changing grid conditions.

61 RADIATION PROTECTION AND DOSIMETRY↗

Toward 100% Renewable Power Grids: A Review

The transition to a 100% renewable power grid remains beset by significant technical challenges. This paper critically examines the obstacles arising from the variability and unpredictability of renewable energy sources (RES), which complicate the real-time balancing of power generation and load demand. In addition to traditional stability concerns (e.g., rotor angle, voltage, and frequency stability), the increasing penetration of inverter-based resources (IBRs) introduces novel challenges, including resonance stability issues and converter-driven dynamics. Moreover, the dynamic behavior and fault response of IBRs diverge markedly from those of conventional synchronous generators, rendering traditional protection schemes increasingly inadequate. This paper reviews state-of-the-art solutions in power balancing, grid flexibility, stability enhancement, and advanced protection strategies, discussing their implications for future grid design. The analysis provides a comprehensive assessment of recent technological advancements, thereby outlining critical research directions essential for achieving a resilient, 100% renewable power grid.

100% renewable power grid↗

Web-based wide-area monitoring platform for ringdown and clustering analytics in power systems

This paper introduces an open-source research platform for monitoring the Mexican interconnected power grid, allowing real-time processing and information extraction of the grid’s dynamic condition. Moreover, the platform is a Python-based development that embeds different ringdown and clustering analytics tools. In the case of ringdown analysis, the modal information can be extracted using some of the most known algorithms, i.e., Prony analysis, eigensystem realization algorithm (ERA), and matrix pencil (MP). For clustering analysis, the coherent behaviour of generator and non-generator buses is provided by applying recent state-of-the-art techniques such as affinity propagation, K-means, hierarchical agglomerative clustering, and typicality data analysis. The results of up to 93 PMUs show that this open-source platform suits researchers’ and engineers’ power system dynamic analysis requirements.

Clustering↗

Approximation of the Frequency-Amplitude Curve Using the Homotopy Analysis Method

The Frequency-Amplitude (F-A) curve on power system oscillation under a large disturbance characterizes how a natural oscillation mode transitions to nonlinear oscillations with growing amplitudes and decaying frequencies. The existing formulation of the F-A curve is derived by solving elliptical integrals on oscillation of a single-machine-infinite-bus equivalent about the targeted oscillation mode. The formula is in a form of infinite series and needs to sum a large number of terms for satisfactory accuracy. This paper introduces an explicit, approximate expression obtained from the Homotopy Analysis Method on the F-A curve. The proposed F-A curve expression is derived from an SMIB system and verified on the IEEE 3-machine 9-bus system to show how the oscillation frequency of a dominant mode varies with oscillation amplitude under large disturbances.

frequency-amplitude (F-A) curve↗

Control of energy storage to reduce electric power system off-nominal frequency deviations

A hybrid power generation system is formed by the combination of an energy storage system (ESS) and a rotating synchronous power generator (SPG). Energy is stored in or released from the ESS in response to measurements of the at least one angle parameter, selected from rotor, torque, or power angle of the SPG, to provide active frequency damping of electrical power output. The control of ESS energy exchange increases the stabilizing impact of the SPG inertia on the frequency of electricity in an electrical network or power grid. The hybrid power generation system can have an effective equal area criterion for stability limit that is greater than that of the SPG operating without the ESS. The hybrid power generation system can enable the electrical network to have a greater proportion of variable or distributed energy resource (DER) power generation systems without otherwise exceeding stability limits.

Vartanian, Charles K.↗

A Hybrid-Learning Algorithm for Online Dynamic State Estimation in Multimachine Power Systems

With the increasing penetration of distributed generators in the smart grids, having knowledge of rapid real-time electromechanical dynamic states has become crucial to system stability control. Conventional Supervisory Control and Data Acquisition (SCADA)-based dynamic state estimation (DSE) techniques are limited by the slow sampling rates, while the emerging phasor measurement units (PMUs) technology enables rapid real-time measurements at network nodes. Using generator bus terminal voltages, we propose a hybrid-learning DSE (HL-DSE) algorithm to estimate the synchronous machine rotor angle and speed in real time. The HL-DSE takes the power system model into account and trains neuroestimators with real-time data in an online manner. Compared with traditional DSE methods, the HL-DSE overcomes limitations by using a data-driven approach in conjunction with the physical power system model. The time efficiency, accuracy, convergence, and robustness of the proposed algorithm are tested under noises and fault conditions in both small- and large-scale test systems. Simulation results show that the proposed HL-DSE is much more computationally efficient than widely used Kalman filter (KF)-based methods while maintaining comparable accuracy and robustness. In particular, HL-DSE is over 100 times faster than square-root unscented KF (SR-UKF) and 80 times faster than extended KF (EKF). The advantages and challenges of the HL-DSE are also discussed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Step Towards Machine Learning-based Coherent Generator Grouping for Emergency Control Applications in Modern Power Grid

A dynamic neural network (NN) based multi-class classifier is proposed for improving online prediction of coherent generator groups (CGGs), following the occurrences of various contingencies in the power grid. This is motivated by the increasing availability of the measurements from phasor measurement units (PMUs) and the number of grouping schemes is limited. The proposed method consists of three steps. First, by performing offline simulations, a library of system dynamic responses characterized by post-contingency rotor angles and speeds of individual generators is obtained. To generate sufficient data, up to N-2 contingencies and the uncertain parameters associated with the power grid including type and location of disturbance and fault clearing times are modeled. Secondly, the training data-set is produced by generating labels for individual contingencies using a hierarchical clustering method based on rotor angle and speed data. Lastly, the dynamic NN models are trained for online applications such as emergency controls and controlled islanding. The proposed method is tested on the standard 16-generator 68-bus system to demonstrate its performance. Furthermore, the impact of the sample data lengths on the CGG numbers is evaluated. It is interesting to observe that the time domain stability behaviors can be determined by examining the changes in the CGG numbers.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

UAE6 - Wind Tunnel Tests Data - UAE6 - Sequence K - Raw Data

Sequence K: Step AOA, Probes (P) This sequence was designed to quantify the 3-D blade static angle-of-attack response in the presence of rotational influences by varying the blade pitch angle. Sequence K used an upwind, rigid turbine with a 0° cone angle. The wind speeds ranged from 6 m/s to 20 m/s, and data were collected at yaw angles of 0° and 30°. The rotor rotated at 72 RPM. Blade and probe pressure measurements were collected. The teeter dampers were replaced with rigid links, and these two channels were flagged as not applicable by setting the measured values in the data file to -99999.99 Nm. The teeter link load cell was pre-tensioned to 40,000 N. The blade pitch angle ramped continuously at 0.18°/s over a wide range of increasing and decreasing pitch angles. A step sequence was also performed. The blade pitch was stepped 5°, the flow was allowed to stabilize, and the pitch angle was held for 8 seconds. Then the pitch angle step was repeated. Again, a wide range of pitch angles was obtained, both increasing and decreasing. The file lengths for this sequence varied from 96 seconds to 6 minutes, depending on the pitch angle range. Some short points were collected at 0° yaw and 3° pitch to verify the functionality of the instrumentation. The file name convention used the initial letter K, followed by two digits specifying wind speed, followed by two digits for yaw angle, followed by RU, RD, or ST, followed by the repetition digit. The angle-of-attack motion was differentiated by RU (ramp up), RD (ramp down), and ST (step down then step up). This sequence is related to sequences L and R.

17 WIND ENERGY↗

UAE6 - Wind Tunnel Tests Data - UAE6 - Sequence L - Raw Data

Sequence L: Step AOA, Parked (P) This sequence was designed to quantify the 3-D blade static angle-of-attack response in the absence of rotational influences by varying the blade pitch angle. This test sequence used an upwind, rigid turbine with a 0° cone angle. Wind speeds of 20 m/s and 30 m/s were used, and all data were collected at a yaw angle of 0°. The rotor was parked with the instrumented blade fixed at 0° azimuth, and the rotor lock was installed (see Appendix A). Blade and probe pressure measurements were collected. The teeter dampers were replaced with rigid links, and these two channels were flagged as not applicable by setting the measured values in the data file to -99999.99 Nm. The teeter link load cell was pre-tensioned to 40,000 N. The blade pitch angle ramped continuously at 0.18°/s over a wide range of increasing and decreasing pitch angles. A step sequence was also performed. The blade pitch was stepped 5°, the flow was allowed to stabilize, and the pitch angle was held for 8 seconds. Then the pitch angle step was repeated. Again, a wide range of pitch angles was obtained, both increasing and decreasing. The file lengths for this sequence varied from 5 to 10 minutes, depending on the pitch angle range. The file name convention used the initial letter L followed by two digits specifying wind speed, followed by 00 for yaw angle, followed by RU, RD, or ST, followed by the repetition digit. The angle-of-attack motion was differentiated by RU (ramp up), RD (ramp down), and ST (step down, then step up). This sequence is related to sequences K and R.

17 WIND ENERGY↗

UAE6 - Wind Tunnel Tests Data - UAE6 - Sequence R - Raw Data

Sequence R: Step AOA, No Probes (P) This sequence was designed to quantify the effect of the five-hole probes on the 3-D blade static angle-of-attack response in the presence of rotational influences by repeating Sequence K without five-hole probes. This test sequence used an upwind, rigid turbine with a 0° cone angle. The wind speeds ranged from 6 m/s to 20 m/s, and data were collected at yaw angles of 0° and 30°. The rotor rotated at 72 RPM. Blade pressure measurements were collected. The five-hole probes were removed and the plugs were installed. Plastic tape 0.03-mm-thick was used to smooth the interface between the plugs and the blade. The teeter dampers were replaced with rigid links, and these two channels were flagged as not applicable by setting the measured values in the data file to –99999.99 Nm. The teeter link load cell was pre-tensioned to 40,000 N. During post-processing, the probe channels were set to read –99999.99. The blade pitch angle ramped continuously at 0.18°/s over a wide range of increasing and decreasing pitch angles. A step sequence was also performed. The blade pitch was stepped 5°; the flow was allowed to stabilize; and the pitch angle was held for 5 seconds. Then the pitch angle step was repeated. Again, a wide range of pitch angles was obtained, both increasing and decreasing. The file lengths for this sequence varied from 96 seconds to 6 minutes, depending on the pitch angle range. Some short points were collected at 0° yaw and 3° pitch to ascertain the functionality of the instrumentation and repeatability over time. The file name convention used the initial letter R, followed by two digits specifying wind speed, followed by two digits for yaw angle, followed by RU, RD, or ST, followed by the repetition digit. The angle of attack motion was differentiated by RU (ramp up), RD (ramp down), and ST (step down, then step up). This sequence is related to Sequences K and L.

17 WIND ENERGY↗

Dopants, Isotope, Pressure and Lead Sequestration for Hybrid Perovskite Materials

Dopants, Isotope, Pressure and Lead Sequestration for Hybrid Perovskite Materials The soaring power conversion efficiency (PCE) of solution process-based organic-inorganic hybrid perovskites solar cells (PSCs) assures their membership in the competitive photovoltaic technologies. However, stability, toxicity and scalability are the three grand challenges that still impedes the market adoption of PSCs. Careful fundamental studies on how their fascinating optoelectronic properties is related to their structures may provide leads to these challenges and also spin off new applications. In this talk, I will present our recent study on the dopants, isotope and pressure effects on hybrid perovskite materials (HPMs). We discovered an interesting bipolar electron injection in LiCl-doped MAPbI 3 -based UV detectors that respond to the energy of UV photons in distinguished photocurrents polarity. We also investigated how the underline interaction between the mass of the cationic rotors and the inorganic lattice in HPMs by isotope effect. In-situ synchrotron X-ray and time-resolved photoluminescence revealed abnormal optoelectronic properties of HPMs by modulating their bond angles and bond lengths using high pressure techniques. Moreover, I will also discuss our new technology to sequestrate lead leakage on perovskite solar cells that can absorb >99% leaked Pb ions under severe device damge while without sacrificing the PCE under normal operational conditions.

Xu, Tao↗

Topological Mixed Valence Model for Twisted Bilayer Graphene

Song and Bernevig (SB) have recently proposed a topological heavy-fermion description of the physics of magic angle twisted bilayer graphene (MATBG), involving the hybridization of flat-band electrons with a relativistic conduction sea. Here, we explore the consequences of this model, seeking a synthesis of understanding drawn from heavy-fermion physics and MATBG experiments. Our work identifies a key discrepancy between measured and calculated on-site Coulomb interactions, implicating renormalization effects that are not contained in the current model. With these considerations in mind, we consider a SB model with a single, renormalized on-site interaction between the f electrons, containing a phenomenological heavy-fermion binding potential on the moiré A A sites. This feature allows the simplified model to capture the periodic reset of the chemical potential with filling and the observed stability of local moment behavior. We argue that a two-stage Kondo effect will develop in MATBG as a consequence of the relativistic conduction band: Kondo I occurs at high temperatures, establishing a coherent hybridization at the Γ points and a non-Fermi liquid of incoherent fermions at the moiré K points; at much lower temperatures, Kondo II leads to a Fermi liquid in the flat band. Utilizing an auxiliary-rotor approach, we formulate a mean-field treatment of MATBG that captures this physics, describing the evolution of the normal state across a full range of filling factors. By contrasting the relative timescales of phonons and valence fluctuations in bulk heavy-fermion materials with that of MATBG, we are led to propose a valley-polaron origin to the Coulomb renormalization and the heavy-fermion binding potential identified from experiment. We also discuss the possibility that the two-fluid, non-Fermi liquid physics of the relativistic Kondo lattice is responsible for the strange-metal physics observed in MATBG. Published by the American Physical Society 2025

Lau, Liam L. H. (ORCID:0000000166039088)↗

UAE6 - Wind Tunnel Tests Data - UAE6 - Sequence 8 - Raw Data

Sequences 8 and 9: Downwind Sonics (F,P) and Downwind Sonics Parked (P) This test sequence used an upwind, rigid turbine with a 0° cone angle. The wind speed ranged from 5 m/s to 25 m/s. Yaw angles of 0° to 60° were achieved. The blade tip pitch was 3°. The rotor rotated at 72 RPM during Sequence 8, but it was parked during Sequence 9. Blade pressure measurements were collected. The five-hole probes were removed and the plugs were installed. Plastic tape 0.03-mm-thick was used to smooth the interface between the plugs and the blade. The teeter dampers were replaced with rigid links, and these two channels were flagged as not applicable by setting the measured values in the data file to –99999.99 Nm. The teeter link load cell was pre-tensioned to 40,000 N. During post-processing, the probe channels were set to read -99999.99. Sonic anemometers were mounted on a strut downwind of the turbine. The strut was mounted to the T-frame, which was rotated to align the anemometers aft of the 9% and 49% radius locations at hub height. Because of this configuration, the tunnel balance data are considered invalid. Sequence 9 was designed to compare the downwind sonic anemometer readings with the upwind sonic anemometers without interference from the turbine. The rotor was parked with the instrumented blade at 0° azimuth. All pressure measurements obtained in Sequence 9 are invalid because sufficient time for temperature stabilization did not occur, thus all associated data values were flagged as not applicable by setting the measured values in the data file to 0.0000 Pa. This test is further described in Appendix G.

17 WIND ENERGY↗

UAE6 - Wind Tunnel Tests Data - UAE6 - Sequence 9 - Raw Data

Sequences 8 and 9: Downwind Sonics (F,P) and Downwind Sonics Parked (P) This test sequence used an upwind, rigid turbine with a 0° cone angle. The wind speed ranged from 5 m/s to 25 m/s. Yaw angles of 0° to 60° were achieved. The blade tip pitch was 3°. The rotor rotated at 72 RPM during Sequence 8, but it was parked during Sequence 9. Blade pressure measurements were collected. The five-hole probes were removed and the plugs were installed. Plastic tape 0.03-mm-thick was used to smooth the interface between the plugs and the blade. The teeter dampers were replaced with rigid links, and these two channels were flagged as not applicable by setting the measured values in the data file to –99999.99 Nm. The teeter link load cell was pre-tensioned to 40,000 N. During post-processing, the probe channels were set to read -99999.99. Sonic anemometers were mounted on a strut downwind of the turbine. The strut was mounted to the T-frame, which was rotated to align the anemometers aft of the 9% and 49% radius locations at hub height. Because of this configuration, the tunnel balance data are considered invalid. Sequence 9 was designed to compare the downwind sonic anemometer readings with the upwind sonic anemometers without interference from the turbine. The rotor was parked with the instrumented blade at 0° azimuth. All pressure measurements obtained in Sequence 9 are invalid because sufficient time for temperature stabilization did not occur, thus all associated data values were flagged as not applicable by setting the measured values in the data file to 0.0000 Pa. This test is further described in Appendix G.

17 WIND ENERGY↗