Search NASA⌕ Search

Engineering topics

Bainy, Romulo [University of Idaho]

Publications and source records attributed to Bainy, Romulo [University of Idaho].

Evaluation of a Reduced-Order Model for IBR Fault Response Representation via OEM Blackbox Models

This paper presents a fully implemented inverter reduced-order-model (ROM) in an EMT simulation (PSCAD) library component for direct user utilization in protection studies. The developed inverter ROM has the following features: Equivalent to a full inverter-based resource (IBR) inverter model with positive- and negative-sequence current formulation and representation. A Python script is developed to fully automate this process, including training data generation, ROM parameter training, updating parameters, and model verification and validation. The ROM is validated using both IEEE 2800-compliant and non-compliant OEM modes in a real-world system, building confidence of its usability by protection engineers.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluation of a Reduced-Order Model for IBR Fault Response Representation via OEM Blackbox Models: Preprint

Driven by the need to capture the electromagnetic transients of transmission lines, inverter switching behavior, and detailed control systems, electromagnetic transient (EMT) studies have become increasingly important in industry, such as IBR interconnection study and fault study. However, original equipment manufacturer (OEM) inverter models typically include extensive parameters and proprietary settings that are unavailable to protection engineers. This paper introduces a data-driven, reduced-order model (ROM) developed as a PSCAD library component for use in EMT-based fault studies. The ROM replicates key OEM model behaviors without requiring detailed knowledge of control design or parameterization. The accompanying Python automation scripts streamline data generation, parameter fitting, and validation. The ROM's performance is demonstrated through comparison with both IEEE 2800-compliant and non-compliant OEM models in a real-world power system. Relay responses show nearly identical results, while simulation runtime is reduced by an average of 32.8\%, highlighting the ROM's practicality for protection engineers.

14 SOLAR ENERGY↗

Studying the Impact of Momentary Cessation of IBRs Compliant With IEEE Std. 2800-2022 on Transmission Line Protection Elements

This paper examines the impact of inverter-based resource (IBR) momentary cessation timing on transmission system protection relays. IEEE Std. 2800 mandates voltage ride-through, requiring IBRs to remain online during voltage disturbances. However, for severe voltage dips (|V| = 0.1 p.u.), the standard permits current blocking. In practice, vendors implement momentary cessation with varying delays, potentially affecting relay operation if IBRs cease too early. This article studies the impact of the time IBRs enter momentary cessation on transmission line protective relays. Using an electromagnetic transient (EMT) simulation, this study models IBR momentary cessation with tunable delays in a realistic transmission network. COMTRADE files generated from EMT simulations are analyzed in MATLAB using detailed protective relay models. Results indicate that IBRs must sustain operation for at least one cycle to ensure proper relay response; otherwise, relays may fail to oper- ate. These findings guide IBR vendors in optimizing momentary cessation settings to enhance transmission line protection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Generic and Multifunctional Electromagnetic Transient Model for Grid-Following Inverters

This article presents a generic and multi-functional electromagnetic transient (EMT) dynamic model of grid following (GFL) inverter-based resource (IBR) using the PSCAD software platform. The features of the developed model includes the flexibility in selecting various types and combinations of DC sources covering PV modules, battery modules, ideal DC source module, as well as flexibility in selecting either switched or averaged model of inverter. This model also covers exhaustive lists of controller logic covering open-loop/closed-loop PQ dispatch control, DC voltage and AC terminal voltage control along with the conventional current control designed in dq-domain, ate- domain and positive-negative sequence domain. Moreover, this model is equipped with the flexibility in selecting various types of current limiting schemes that includes saturation-based as well as latching-based current limiter, anti-windup protection. Moreover, the EMT model is agnostic to the MVA rating and is suitable for interfacing transmission systems by being complaint with the IEEE Std. 2800. The generality in the power circuits and the multi-functional options in operation and control of the developed EMT model makes it suitable for both academia and industry to study various power system aspects not limited to but such as fault behavior of GFL IBR and impacts on protection system, transient stability of a system interfaced with large number of GFL IBRs etc.

14 SOLAR ENERGY↗

Analysis of Line Distance Elements for Various Ibr Controllers and System Conditions

The large-scale penetration of inverter-based resources in power systems has challenged protection engineers because of the different fault behaviors these sources provide compared to conventional generation systems. The main challenges include a low level of fault current magnitude, unpredictable angles of sequence currents, and lack of inertia that can lead to maloperation of conventional phasor-based protection elements. This paper presents a sensitivity analysis of transmission line distance protection elements during phase-to-ground and phase-to-phase faults for different inverter controllers and power system conditions. It also summarizes which line protection elements remain secure near IBR terminations and identifies the ones affected by the inverter-based response. The paper concludes by highlighting that regulating negative-sequence current injection during the fault aids correct protection decisions, but does not address the entire challenge. Finally, alternative protection elements to those affected by the inverter fault response are discussed.

24 POWER TRANSMISSION AND DISTRIBUTION↗