Grey-Box System Identification of Grid-Forming Inverters

This paper demonstrates the use of grey-box system identification methods for simplifying and understanding the nonlinear power dynamics of grid-forming inverters (GFMs). The power and frequency outputs of complex high-order GFM models are fed into system identification software in order to fit them to a predetermined LTI system and learn system parameters such as (synthetic) inertia and droop constants. The same process is then run for a high-order synchronous generator model, and the outputs are fit to the same set of LTI equations. Simulation of a network of GFM inverters with diverse control architecture is also performed for the same process. The intent is threefold: first, to demonstrate the appropriateness of unified LTI models for describing the power and frequency dynamics of individual resources and connected networks, in order to facilitate analysis of larger heterogeneous networked systems; second, to discover the relationship between internal control parameters of GFMs and their externally observed values; and third, to validate that grey-box data-driven system identification techniques can be a valuable tool to discover the values of important parameters in the absence of explicit vendor models.

analytical models↗

Equivalent-Circuit Models for Grid-Forming Inverters under Unbalanced Steady-State Operating Conditions: Preprint

Positive- and negative-sequence equivalent-circuit models are put forth to capture the operation of grid-forming (GFM) inverters in unbalanced steady-state operating conditions acknowledging the impact of current limiting. The particular control architecture examined adopts droop control (for primary control), nested inner-current and outer-voltage control (in the stationary reference frame), and it is adaptable to two different types of current limiting (current-reference saturation and virtual-impedance limiting). We anticipate the proposed models to be of interest in modeling, analysis, and simulation of GFM inverters in unbalanced settings that may arise, e.g., in the face of faults. Validation of the equivalent-circuit models is pursued via comparison with full-order electromagnetic-transient (EMT) simulations for representative balanced and unbalanced faults.

equivalent-circuit models↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: Droop, Virtual Synchronous Machine (VSM), and dispatchable Virtual Oscillator Control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy, and with no explicit tuning of the solver, lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

electromagnetic transient simulation↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations: Preprint

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: droop, virtual synchronous machine (VSM), and dispatchable virtual oscillator control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy with up to 150x lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

circuit-equivalent model↗

Large-Signal Stability of Phase-Balanced Equilibria in Single-Phase Grid-Forming Inverter Systems

This article explores the setup where large numbers of single-phase grid-forming inverters with droop control across distribution networks self-organize into a stable and balanced system with 120° phase offsets across aggregates in the absence of balanced three-phase generating resources or external communication. A suite of circuit- and system-theoretic notions are leveraged to derive a dynamical model for phase-angle differences across aggregates of inverters connected in the three phases. Focusing on this model, large-signal stability is established and the region of attraction of the phase-balanced equilibria is determined with the aid of a Lyapunov function. Experimental validation for a bench-top prototype network is included to support the analytical developments. Altogether, the effort supports the vision of facilitating balanced operation of distribution networks with grid-forming inverters during service disruptions at the bulk transmission network.

Droop control↗

Performance Specifications for Grid-Forming Technologies

Standards and specifications for inverter-based resources (IBRs) focus primarily on grid-following (GFL) technologies at present. Therefore, these may generally not be appropriate for application in power systems to ensure acceptable operation with grid-forming (GFM) technologies. In some cases, the direct application of prevailing standards and specifications may not be appropriate for - or may even inadvertently limit the potential of - GFM resources. The Universal Interoperability for Grid- Forming Inverters (UNIFI) Consortium is a U.S. Department of Energy funded effort to advance GFM technology. The UNIFI team brings together academic, industrial, and national-lab researchers as well as industry stakeholders (utilities, system operators, vendors) to collaboratively pursue advances in a broad range of GFM technologies. This paper introduces a set of system- and unit-level specifications driven by consensus across the UNIFI project team. These are intended to seamlessly integrate GFM technologies at any scale into power-systems operation and control in a vendor-agnostic manner. A suite of illustrative simulation results that demonstrate the application of and adherence to the proposed specifications are included.

grid-forming inverter↗