Search NASA⌕ Search

Engineering topics

Gong, Maozhong

Publications and source records attributed to Gong, Maozhong.

Advanced grid-forming (GFM) inverter controls, modeling and system impact study for inverter dominated grids

Our main goals in this project are to understand: 1) the stability of the power system with very high penetration of PV or other inverter-based resources (IBR), 2) the interactions among IBRs and traditional generators, and 3) the impact of the GFM inverters on bulk power system. To achieve these goals, we took a holistic research and development approach. First, an impedance-based large system modeling and stability analysis tool was developed to aid the large IBR system small-signal stability analysis. Second, consensus-based control and transient overload ride through were developed to control and coordinate multiple GFM inverters in a large system to maintain transient stability during big grid events. Third, high fidelity electromagnetic transient (EMT) IBR models were developed and integrated into a large reduced WECC model to study the system impact from IBRs. Lastly, extensive validation tests of the GFM control which was developed in this project and implemented in two 1MW commercial solar inverters were performed using different validation platforms, e.g., control hardware-in-the-loop (CHIL) platform, power hardware- in-the-loop (PHIL) platform, and a real PV plant.

14 SOLAR ENERGY↗

Performance Specifications for Grid-Forming Technologies

Standards and specifications for inverter-based resources (IBRs) focus primarily on grid-following (GFL) technologies at present. Therefore, these may generally not be appropriate for application in power systems to ensure acceptable operation with grid-forming (GFM) technologies. In some cases, the direct application of prevailing standards and specifications may not be appropriate for - or may even inadvertently limit the potential of - GFM resources. The Universal Interoperability for Grid- Forming Inverters (UNIFI) Consortium is a U.S. Department of Energy funded effort to advance GFM technology. The UNIFI team brings together academic, industrial, and national-lab researchers as well as industry stakeholders (utilities, system operators, vendors) to collaboratively pursue advances in a broad range of GFM technologies. This paper introduces a set of system- and unit-level specifications driven by consensus across the UNIFI project team. These are intended to seamlessly integrate GFM technologies at any scale into power-systems operation and control in a vendor-agnostic manner. A suite of illustrative simulation results that demonstrate the application of and adherence to the proposed specifications are included.

grid-forming inverter↗

A Stability Analysis Tool for Bulk Power Systems Using Black-Box Models of Inverter-Based Resources

This paper presents a small-signal stability analysis tool for large-scale power systems with high penetration of inverter-based resources (IBRs). Firstly, a network transfer function matrix (NTFM), which represents the information of the system topology, transmission lines, loads, IBRs locations, etc., is derived to model the entire power system network. Secondly, small-signal perturbation method is applied to obtain the sequence impedance/admittance models of the block-box IBRs considering the frequency cross-coupling effects. With the obtained NTFM as well as IBR models, a multi-input, multi-output (MIMO) feedback system is constructed, and the generalized Nyquist criterion (GNC)-based stability method is employed to analyze the stability of the entire power system. Furthermore, based on the developed stability analysis method, sensitivity analysis is conducted on an unstable case to identify which parameter has a high impact on the system stability. As a result, different test cases based on a modified IEEE 14- bus system as well as a reduced 240-bus WECC system are studied to verify the proposed stability analysis tool.

42 ENGINEERING↗

A Stability Analysis Tool for Bulk Power Systems Using Black-Box Models of Inverter-based Resources

This paper presents a small-signal stability analysis tool for large-scale power systems with high penetration of inverter-based resources (IBRs). Firstly, a network transfer function matrix (NTFM), which represents the information of the system topology, transmission lines, loads, IBRs locations, etc., is derived to model the entire power system network. Secondly, small-signal perturbation method is applied to obtain the sequence impedance/admittance responses of IBRs considering the frequency cross-coupling effects. With the obtained NTFM as well as IBRs' models, a multi-input, multi-output (MIMO) feedback system is constructed, and the generalized Nyquist criterion (GNC)-based stability method is employed to analyze the stability of the entire power system. Different testing cases based on a modified IEEE-14 bus system are leveraged to verify the proposed stability analysis tool.

Sun, Dongsen↗

Provably-Stable Overload Ride-Through Control for Grid-Forming Inverters Using System-Wide Lyapunov Function Analysis

A key challenge associated with a grid-forming (GFM) inverter based resource (IBR) is its behavior during severe grid disturbances: since a GFM inverter regulates voltage in the fast timescale instead of current or power, it may experience a transient overload of current, power and/or energy during a severe grid disturbance. While many promising control strategies for overload ride-through have been proposed over the past two decades, transient stability of the system during and after the transition to an overload ride-through control mode remains difficult to guarantee. In this work, a novel overload ride-through control strategy is proposed for a system of grid-forming inverters that takes both self-protection and system-wide transient stability into account. A proposed system-level supervisory control uses slow communication to pre-emptively assign a set of local ride through control parameters to individual GFM IBR, including a current-limiting virtual reactance, that guarantees that synchronism is still preserved for any set of anticipated grid disturbances. At the core of the supervisory control lies a Lyapunov-function-based routine capable of establishing a strong, albeit conservative, transient stability guarantee for the system. Here, the proposed overload ride-through control strategy is validated via numerical integration of a reduced-order model, as well as through detailed electromagnetic transient (EMT) simulation.

30 DIRECT ENERGY CONVERSION↗

A New Impedance-Based Modeling and Stability Analysis Approach for Power Oscillations Between Grid-Forming Inverters

This paper presents a new modeling and analysis approach to address the small-signal stability issues among interconnected grid-forming (GFM) inverters. A novel phasor domain “power impedance” model is developed to capture the terminal characteristics of GFM inverters. Based on the developed models, a sum-type impedance stability criterion is proposed to analyze the power oscillations between GFM Inverters. The developed models are validated with EMT simulations and the stability analysis results using the proposed stability criterion can match both EMT simulations and eigenvalue analysis. In addition, the application of the developed model can be extended to the stability analysis of large-scale power system with high penetration of GFM inverters.

Liu, Hanchao↗

Virtual synchronous generator system and method with virtual inertia control

A virtual synchronous generator device disclosed. The device includes an inverter and inverter controller having a power control portion, a power reserve portion, a power point tracking control portion, and a virtual inertia control portion. The power reserve portion determines an amount of power to be reserved and sends a signal, indicative of the determined amount of power to the power point tracking controller. The power point tracking controller determines a power point that is less than a MPP, and provides a signal to the power control portion indicative of the determined power point. The inertia control portion determines a virtual inertia and provides a signal indicative of the virtual inertia to the power control portion. The power control portion provides a power control signal to the inverter based on the power point tracking signal and the inertia command signal.

42 ENGINEERING↗

Energy Storage for Frequency Control in High Photovoltaic Power Grids

Frequency stability of power systems becomes more vulnerable with the increase of solar photovoltaic (PV). Energy storage provides an option to mitigate high PV impact. Using the United States Eastern Interconnection (EI) and Texas Interconnection (ERCOT) power grid models, this paper investigates the capabilities of using energy storage to improve frequency stability of high PV power grids. The study result helps to identify the potential and impact factors in utilizing energy storage to regulate frequency in high renewable power grids.

14 SOLAR ENERGY↗