Inverter Testing for Verification of Hawaiian Electric Rule 14H

As utilities increasingly require inverters to perform grid-supportive functions, it is challenging to ensure that those functions are properly configured in the field. This paper presents details of inverter testing related to Hawaiian Electric's latest rule 14H interconnection requirements to validate that field installation procedures result in the intended advanced inverter behavior. The latest Volt-VAR, Volt-Watt, and frequency-Watt curves in Hawaiian Electric's Source Requirement Document (SRD) V1.1 for UL 1741 Supplement A were tested for two inverter manufacturers used in the utility territory. Both inverters were found to be largely compliant, though several discrepancies were identified and reported to the manufacturers. The results are presented and discussed here.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Results of Recent and Historical Comparisons Between Absolute Cavity Pyrgeometer (ACP), InfraRed Integrating Sphere (IRIS)

Results of seven comparisons between ACPs and IRISs. Difference between the longwave irradiance measured by the ACPs and IRISs versus the irradiance measured by the WISG. The longwave irradiance measured by the ACPs, IRISs, and AERI versus the irradiance measured by the WISG. Recommendations to establish the world reference for measuring the atmospheric longwave irradiance with traceability to the International System of Units (SI).

54 ENVIRONMENTAL SCIENCES↗

NREL Comparison of Absolute Cavity Pyrgeometers and Pyrgeometers Traceable to the World Infrared Standard Group and the Infrared Integrating Sphere: September 23-October 4, 2019

The comparison of the absolute cavity pyrgeometers (ACPs) with a precision infrared radiometer (PIR) pyrgeometer traceable to the World Infrared Standard Group (WISG) and a Kipp & Zonen (KZ) pyrgeometer traceable to WISG and the InfraRed Integrating Sphere Radiometer (IRIS) was held during the National Renewable Energy Laboratory (NREL) Pyrheliometer Comparison (NPC-2019) from September 23 to October 4, 2019. Data from all instruments was collected during nighttime clear sky conditions only. The irradiance measured by the ACPs, PIR, and CG4 pyrgeometers collected 30 seconds during the measurement runs. The measurement runs lasted for two hours, while the calibration runs lasted for 6 minutes. During the comparison, the average (av) irradiance difference measured by three ACPs varied from 0.2 W/m 2 to 0.8 W/m 2 , with a standard deviation (sd) from 0.4 W/m 2 to 0.8 W/m 2 . The average irradiance difference measured by the three ACPs minus the irradiance measured by the PIR was 7.1 W/m 2 and sd 1.0 W/m 2 , and the average irradiance difference measured by the KZ traceable to WISG was 8.1 W/m2 and sd 0.9 W/m 2 , and average irradiance difference measured by the KZ traceable to IRIS was 4.0 W/m2 and sd 0.9 W/m 2 .

14 SOLAR ENERGY↗

Inverter Testing for Verification of Hawaiian Electric Rule 14H: Preprint

As utilities increasingly require inverters perform grid-supportive functions, it is challenging to ensure that those functions are properly configured in the field. This paper details inverter testing carried related to Hawaiian Electric's latest rule 14H interconnection requirements to validate that field installation procedures result in the intended advanced inverter behavior. The latest Volt-VAR, Volt-Watt, and frequency-Watt curves in Hawaiian Electric's Source Requirement Document (SRD) V1.1 for UL 1741 Supplement A were tested for two inverter manufacturers used in the utility territory. Both inverters were found to be largely compliant, though several discrepancies were identified and reported to the manufacturers to be addressed. The results are presented and discussed here.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Estimating Customer Impact of Volt-Watt Using Only Smart Meter Voltage Data

The autonomous inverter control mode known as volt-watt control can be useful as a backstop against high customer voltages outside of the ranges specified in ANSI C84.1 (i.e. above 1.05-1.06 per unit). Volt-watt control mitigates high voltages by directly reducing the active power output of a distributed energy resource based on local voltage measurements. Therefore volt-watt control also can impact the energy produced by the DER (e.g. PV system), especially for customers with persistently high voltages, and in such cases it is difficult to determine exactly how much the DER has been curtailed because it is not generally known exactly how much energy the PV system could have produced. These slides propose a relatively simple method of estimating the DER's energy curtailment using only data from the utility advanced metering infrastructure (AMI) data). The method proves surprisingly accurate when validated against detailed quasi-static time-series simulations and against limited field data.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Low-Cost Multiparameter Device for Solar Resource Applications

The National Renewable Research Laboratory (NREL) Solar Radiation Research Laboratory (SRRL), in collaboration with Arable Labs Inc., deployed, calibrated, and characterized Arable Lab's Mark low-cost, multiparameter sensor system. Arable Labs was selected by the U.S. Department of Energy for a small business voucher to work with NREL to tap into the knowledge and expertise Arable needs to tailor and evaluate the Mark device for broader solar energy applications. The device is a complete and independent unit. It is a self-powered, off-the-shelf solution for remote solar irradiance and meteorological sensing and data collection. Calibration of devices against the SRRL instruments provides an understanding of the quality of a new instrument compared to peers. The characterization process provides an understanding of the variability compared to high-quality instruments and essentially provides methods to correct the sources of the variabilities.

14 SOLAR ENERGY↗

Residential Advanced Photovoltaic Inverter Pilot Study Results for Select Distribution Secondaries in Hawai'i

Penetration levels of residential rooftop solar photovoltaic (PV) generation on the Hawaiian island of O'ahu have increased significantly in recent years, with many circuits now at the limits of their PV hosting capacity. NREL and Hawaiian Electric have used this opportunity to deploy advanced inverters at new customer installations that would not otherwise have been approved, as a pilot study to gain first-hand operational field data and experience on the impact of inverter-based grid support functions. At each customer location, the deployed advanced inverters were remotely controlled and monitored. Additionally, customer AMI (smart meter) and secondary distribution transformer data was also available for the analysis. The analysis focused on quantifying the customer behind-the-meter voltage rise due to PV production, determining the customer voltage rise with advanced inverters in unity power factor as well as advanced grid support function modes, and estimating the curtailment when inverters have Volt-VAR and Volt-Watt enabled. The results show that: 1) Behind-the-meter voltage rise is often not negligible. 2) An inverter's operating point on a Volt-VAR/Volt-Watt curve depends strongly on the design of the secondary system on which it is installed. 3) The mitigation of voltage rise on the secondary system using Volt-VAR may not be effective if only a small proportion of inverters have grid support enabled, or if the reactance/resistance (X/R) ratio of the grid is low. 4) Volt-Watt curtailment can be estimated using co-located irradiance sensors but there may be opportunities to estimate it using inverter internal electrical measurements. 5) Estimated curtailment is very low for the locations analyzed to date.

14 SOLAR ENERGY↗

Advanced Inverter Voltage Controls: Simulation and Field Pilot Findings

This report describes work performed by the Hawaiian Electric Companies and the National Renewable Energy Laboratory (NREL) to model and simulate advanced inverter grid-support functions and to validate and expand on those simulations through a field pilot study. This work builds on earlier research, referred to as the Voltage Regulation Operational Strategies study. The objective of both is to investigate functionalities available in most photovoltaic (PV) inverters to modulate active and reactive power autonomously based on local voltage measurements for the purpose of mitigating off-nominal grid voltage conditions. Specifically of interest are volt/volt-ampere reactive (VAR) control and volt/watt control, the effect of those functions on quasi-steady-state feeder voltages, and the impact of the functions on PV energy production. Because volt/VAR and volt/watt control autonomously adjust inverter output based on local conditions without requiring communication with any other devices, they are good candidates to increase PV hosting capacity when it is limited by voltage constraints in a feeder with very large numbers of PV systems.

14 SOLAR ENERGY↗

Distribution Feeder Modeling for Time-Series Simulation of Voltage Management Strategies

This paper presents techniques to create baseline distribution models using a utility feeder from Hawai'ian Electric Company. It describes the software-to-software conversion, steady-state and time-series validations of a utility feeder model. It also presents a methodology to add secondary low-voltage circuit models to accurately capture the voltage at the customer meter level. This enables preparing models to perform studies that simulate how customer-sited resources integrate into legacy utility distribution system operations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Value Streams from Distribution Grid Support Using Utility-Scale Vanadium Redox Flow Battery: NREL-Sumitomo Electric Battery Demonstration Project

The National Renewable Energy Laboratory (NREL) collaborated with Sumitomo Electric to provide research support in modeling and optimally dispatching a utility-scale vanadium redox flow battery (VRFB) energy storage. The objective of the project was to identify value streams from using utility-scale VRFB for local grid support use-cases, including voltage regulation (droop), capacity firming, peak shaving and valley filling, and energy arbitrage. This project was also supported by San Diego Gas and Electric (SDGandE). SDGandE provided data and approval to operate their VRFB energy storage system on an SDGandE distribution feeder. NREL worked with Sumitomo Electric to evaluate optimal dispatch strategies to VRFB, analyze the technical impacts, and calculate the associated cost-benefit ratio of substation-level energy storage on an SDG&E distribution feeder. To support this research, NREL evaluated the impacts of the battery use cases suggested by Sumitomo on the SDGandE host feeder. In addition to evaluating the battery use case, this effort identified possible ways to monetize the benefits from distribution feeder support.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distribution Feeder Modeling for Time-Series Simulation of Voltage Management Strategies: Preprint

This paper presents techniques to create baseline distribution models using a utility feeder from Hawai'ian Electric Company. It describes the software-to-software conversion, steady-state, and time-series validations of a utility feeder model. It also presents a methodology to add secondary low-voltage circuit models to accurately capture the voltage at the customer meter level. This enables preparing models to perform studies that simulate how customer-sited resources integrate into legacy utility distribution system operations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Representative Day Selection Using Statistical Bootstrapping for Accelerating Annual Distribution Simulations

Capturing technical and economic impacts of solar photovoltaics (PV) and other distributed energy resources (DERs) on electric distribution systems can require high-time resolution (e.g. 1 minute), long-duration (e.g. 1 year) simulations. However, such simulations can be computationally prohibitive, particularly when including complex control schemes in quasi-steady-state time series (QSTS) simulation. Various approaches have been used in the literature to down select representative time segments (e.g. days), but typically these are best suited for lower time resolutions or consider only a single data stream (e.g. PV production) for selection. We present a statistical approach that combines stratified sampling and bootstrapping to select representative days while also providing a simple method to reassemble annual results. We describe the approach in the context of a recent study with a utility partner. This approach enables much faster QSTS analysis by simulating only a subset of days, while maintaining accurate annual estimates.

14 SOLAR ENERGY↗

Simulation of Hawaiian Electric Companies Feeder Operations with Advanced Inverters and Analysis of Annual Photovoltaic Energy Curtailment

The Hawaiian Electric Companies achieved a consolidated Renewable Portfolio Standard (RPS) of approximately 26% at the end of 2016. This significant RPS performance was achieved using various renewable energy sources - biomass, geothermal, solar photovoltaic (PV) systems, hydro, wind, and biofuels - and customer-sited, grid-connected technologies (primarily private rooftop solar PV systems). The Hawaiian Electric Companies are preparing grid-modernization plans for the island grids. The plans outline specific near-term actions to accelerate the achievement of Hawai'i's 100% RPS by 2045. A key element of the Companies' grid-modernization strategy is to utilize new technologies - including storage and PV systems with grid-supportive inverters - that will help to more than triple the amount of private rooftop solar PV systems. The Hawaiian Electric Companies collaborated with the Smart Inverter Technical Working Group Hawai'i (SITWG) to partner with the U.S. Department of Energy's National Renewable Energy Laboratory (NREL) to research the implementation of advanced inverter grid support functions (GSF). Together with the technical guidance from the Companies's planning engineers and stakeholder input from the SITWG members, NREL proposed a scope of work that explored different modes of voltage-regulation GSF to better understand the trade-offs of the grid benefits and curtailment impacts from the activation of selected advanced inverter grid support functions. The simulation results presented in this report examine the effectiveness in regulating voltage as well as the impact to the utility and the customers of various inverter-based grid support functions on two Hawaiian Electric distribution substations.

14 SOLAR ENERGY↗

Data-Driven Residential Load Modeling and Validation in GridLAB-D

Accurately characterizing the impacts of high penetrations of distributed energy resources (DER) on the electric distribution system has driven modeling methods from traditional static snap shots, often representing a critical point in time (e.g., summer peak load), to quasi-static time series (QSTS) simulations capturing all the effects of variable DER, associated controls and hence, impacts on the distribution system over a given time period. Unfortunately, the high time resolution DER source and load data required for model inputs is often scarce or non-existent. This paper presents work performed within the GridLAB-D model environment to synthesize, calibrate, and validate 1-second residential load models based on measured transformer loads and physics-based models suitable for QSTS electric distribution system modeling. The modeling and validation approach taken was to create a typical GridLAB-D model home that, when replicated to represent multiple diverse houses on a single transformer, creates a statistically similar load to a measured load for a given weather input. The model homes are constructed to represent the range of actual homes on an instrumented transformer: square footage, thermal integrity, heating and cooling system definition as well as realistic occupancy schedules. House model calibration and validation was performed using the distribution transformer load data and corresponding weather. The modeled loads were found to be similar to the measured loads for four evaluation metrics: 1) daily average energy, 2) daily average and standard deviation of power, 3) power spectral density, and 4) load shape.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Voltage Support Study of Smart PV Inverters on a High-Photovoltaic Penetration Utility Distribution Feeder

This paper reports on tools and methodologies developed to study the impact of adding rooftop photovoltaic (PV) systems, with and without the ability to provide voltage support, on the voltage profile of distribution feeders. Simulation results are provided from a study of a specific utility feeder. The simulation model of the utility distribution feeder was built in OpenDSS and verified by comparing the simulated voltages to field measurements. First, we set all PV systems to operate at unity power factor and analyzed the impact on feeder voltages. Then we conducted multiple simulations with voltage support activated for all the smart PV inverters. These included different constant power factor settings and volt/VAR controls.

14 SOLAR ENERGY↗

Technologies to Increase PV Hosting Capacity in Distribution Feeders

This paper studies the distributed photovoltaic (PV) hosting capacity in distribution feeders by using the stochastic analysis approach. Multiple scenario simulations are conducted to analyze several factors that affect PV hosting capacity, including the existence of voltage regulator, PV location, the power factor of PV inverter and Volt/VAR control. Based on the conclusions obtained from simulation results, three approaches are then proposed to increase distributed PV hosting capacity, which can be formulated as the optimization problem to obtain the optimal solution. All technologies investigated in this paper utilize only existing assets in the feeder and therefore are implementable for a low cost. Additionally, the tool developed for these studies is described.

14 SOLAR ENERGY↗

Feeder Voltage Regulation with High-Penetration PV Using Advanced Inverters and a Distribution Management System: A Duke Energy Case Study

Duke Energy, Alstom Grid, and the National Renewable Energy Laboratory teamed up to better understand the impacts of solar photovoltaics (PV) on distribution system operations. The core goal of the project is to compare the operational - specifically, voltage regulation - impacts of three classes of PV inverter operations: 1.) Active power only (Baseline); 2.) Local inverter control (e.g., PF...not equal...1, Q(V), etc.); and 3.) Integrated volt-VAR control (centralized through the distribution management system). These comparisons were made using multiple approaches, each of which represents an important research-and-development effort on its own: a) Quasi-steady-state time-series modeling for approximately 1 year of operations using the Alstom eTerra (DOTS) system as a simulation engine, augmented by Python scripting for scenario and time-series control and using external models for an advanced inverter; b) Power-hardware-in-the-loop (PHIL) testing of a 500-kVA-class advanced inverter and traditional voltage regulating equipment. This PHIL testing used cosimulation to link full-scale feeder simulation using DOTS in real time to hardware testing; c) Advanced visualization to provide improved insights into time-series results and other PV operational impacts; and d) Cost-benefit analysis to compare the financial and business-model impacts of each integration approach.

14 SOLAR ENERGY↗

Locational Sensitivity Investigation on PV Hosting Capacity and Fast Track PV Screening

A 15% PV penetration threshold is commonly used by utilities to define photovoltaic (PV) screening methods where PV penetration is defined as the ratio of total solar PV capacity on a line section to peak load. However, this method doesn't take into account PV locational impact or feeder characteristics that could strongly change the feeder's capability to host PVs. This paper investigates the impact of PV location and phase connection type on PV hosting capacity, and then proposes a fast-track PV screening approach that leverages various PV hosting capacity metric responding to different PV locations and types. The proposed study could help utilities to evaluate PV interconnection requests and also help increase the PV hosting capacity of distribution feeders without adverse impacts on system voltages.

14 SOLAR ENERGY↗