Evaluation of a Reduced-Order Model for IBR Fault Response Representation via OEM Blackbox Models

This paper presents a fully implemented inverter reduced-order-model (ROM) in an EMT simulation (PSCAD) library component for direct user utilization in protection studies. The developed inverter ROM has the following features: Equivalent to a full inverter-based resource (IBR) inverter model with positive- and negative-sequence current formulation and representation. A Python script is developed to fully automate this process, including training data generation, ROM parameter training, updating parameters, and model verification and validation. The ROM is validated using both IEEE 2800-compliant and non-compliant OEM modes in a real-world system, building confidence of its usability by protection engineers.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluation of a Reduced-Order Model for IBR Fault Response Representation via OEM Blackbox Models: Preprint

Driven by the need to capture the electromagnetic transients of transmission lines, inverter switching behavior, and detailed control systems, electromagnetic transient (EMT) studies have become increasingly important in industry, such as IBR interconnection study and fault study. However, original equipment manufacturer (OEM) inverter models typically include extensive parameters and proprietary settings that are unavailable to protection engineers. This paper introduces a data-driven, reduced-order model (ROM) developed as a PSCAD library component for use in EMT-based fault studies. The ROM replicates key OEM model behaviors without requiring detailed knowledge of control design or parameterization. The accompanying Python automation scripts streamline data generation, parameter fitting, and validation. The ROM's performance is demonstrated through comparison with both IEEE 2800-compliant and non-compliant OEM models in a real-world power system. Relay responses show nearly identical results, while simulation runtime is reduced by an average of 32.8\%, highlighting the ROM's practicality for protection engineers.

14 SOLAR ENERGY↗

Studying the Impact of Momentary Cessation of IBRs Compliant With IEEE Std. 2800-2022 on Transmission Line Protection Elements

This paper examines the impact of inverter-based resource (IBR) momentary cessation timing on transmission system protection relays. IEEE Std. 2800 mandates voltage ride-through, requiring IBRs to remain online during voltage disturbances. However, for severe voltage dips (|V| = 0.1 p.u.), the standard permits current blocking. In practice, vendors implement momentary cessation with varying delays, potentially affecting relay operation if IBRs cease too early. This article studies the impact of the time IBRs enter momentary cessation on transmission line protective relays. Using an electromagnetic transient (EMT) simulation, this study models IBR momentary cessation with tunable delays in a realistic transmission network. COMTRADE files generated from EMT simulations are analyzed in MATLAB using detailed protective relay models. Results indicate that IBRs must sustain operation for at least one cycle to ensure proper relay response; otherwise, relays may fail to oper- ate. These findings guide IBR vendors in optimizing momentary cessation settings to enhance transmission line protection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

How Inverter-Based Resources (IBRs) Affect Protection Relay Elements

This presentation starts with the details of IEEE 2800-2022 requirements of IBR for balanced and unbalanced faults. Then, it shows how to design a droop based GFM control to be IEEE 2800-2022 compliant. An performance evaluation is carried out to see if three OEM GFM inverters 2800-2022 compliant or not. And finally we show how IEEE 2800-2022 complaint and non-compliant GFM inverter will impact the transmission line protection elements, such as directional element and FID. Finally, recommendations are made if the GFM is not IEEE 2800-2022 compliant to disable the protection elements that rely on reliable and regulated negative sequence current.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Comprehensive Study of the Impact of Inverter-Based Resource (IBR) Modeling and Control on Protection Relay Elements

Inverter-based resources (IBRs) exhibit fault responses that differ significantly from those of synchronous generators, which can challenge the reliable operation of many commonly used power system protection elements. The fault response of IBRs is primarily influenced by their control algorithms and configurations, but the impact of these controls on protection relays is not yet fully understood. This presentation provides a comprehensive study of how IBR modeling and controls affect transmission line protection. Key modeling and control aspects include the DC source, inverter model, power level control, current control, and current limiting. The study reveals that certain aspects - such as the type of DC source (battery, PV, or hybrid), inverter model (average vs. switching), and power level control methods (PQ dispatch vs. Vdc-Vac control for grid-following IBRs, and droop vs. VSM for grid-forming IBRs) - do not significantly affect relay response. However, faster control loops, such as current control and current limiting, do influence the relay behavior. Additionally, the study explores the effects of other factors, including momentary cessation, operating points, fast/slow current responses, and grid strength on relay performance. Finally, the study offers recommendations for both IBR and protection engineers to improve IBR fault response and enhance the reliability of protection systems.

14 SOLAR ENERGY↗

Analysis of Line Distance Elements for Various Ibr Controllers and System Conditions

The large-scale penetration of inverter-based resources in power systems has challenged protection engineers because of the different fault behaviors these sources provide compared to conventional generation systems. The main challenges include a low level of fault current magnitude, unpredictable angles of sequence currents, and lack of inertia that can lead to maloperation of conventional phasor-based protection elements. This paper presents a sensitivity analysis of transmission line distance protection elements during phase-to-ground and phase-to-phase faults for different inverter controllers and power system conditions. It also summarizes which line protection elements remain secure near IBR terminations and identifies the ones affected by the inverter-based response. The paper concludes by highlighting that regulating negative-sequence current injection during the fault aids correct protection decisions, but does not address the entire challenge. Finally, alternative protection elements to those affected by the inverter fault response are discussed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

How Inverter-Based Resources (IBRs) Affect Protection Relay Elements

Inverter-based resources (IBRs) exhibit fault responses that differ significantly from those of synchronous generators, which can challenge the reliable operation of many commonly used power system protection elements. The fault response of IBRs is primarily influenced by their control algorithms and configurations, but the impact of these controls on protection relays is not yet fully understood. This presentation provides a comprehensive study of how IBR modeling and controls affect transmission line protection. Key modeling and control aspects include the DC source, inverter model, power level control, current control, and current limiting. The study reveals that certain aspects - such as the type of DC source (battery, PV, or hybrid), inverter model (average vs. switching), and power level control methods (PQ dispatch vs. Vdc-Vac control for grid-following IBRs, and droop vs. VSM for grid-forming IBRs) - do not significantly affect relay response. However, faster control loops, such as current control and current limiting, do influence the relay behavior. Additionally, the study explores the effects of other factors, including momentary cessation, operating points, fast/slow current responses, and grid strength on relay performance. Finally, the study offers recommendations for both IBR and protection engineers to improve IBR fault response and enhance the reliability of protection systems.

14 SOLAR ENERGY↗